Description 

This document is valid for both the Siemens and 
Bewator branded products. 

PR500 is a proximity card reader for connection to 
SiPass/Bewator Entro, Bewator Omnis 2010, DC800 
or SiPass integrated. The PR500 is for both indoor 
and outdoor mounting.  The reader is compatible 
with both active and passive Entro cards and tags. 

Note! Different cards/tags are used for PR500-
Cotag and PR500-EM respectively.

 

The PR500 proximity reader reads cards or tags 
without them being in contact with the reader. The 
reader continuously transmits a low power radio 
frequency. When a card or tag is presented within 
the field of the reader it activates and transmits a 
unique identification number back to the reader. The 
reader then sends this code to the connected control 
unit in SiPass/Bewator Entro, Bewator Omnis 2010, 
DC800 or SiPass integrated.  

See Illustration 1 on page 6. 

Safety 

General safety precautions 

  Read the general safety precautions before 

operating the device. 

  Follow all warnings and instructions marked on 

the device. 

  Keep this document for reference. 

  Always pass this document on together with the 

product.  

  The device has been approved for use in the 

European Union. In countries outside the EU, the 
local conditions and regulations need to be 
checked before putting the device into service. 

  Please also take into account any additional 

country-specific, local safety standards or 
regulations concerning project planning, 
operation and disposal of the product. 

Target group 

Installer with expert knowledge of building 
installation technique or electronic installations. 

Standards and guidelines 

European directives 

This product complies with the requirements of the 
European Directives. The European declaration of 
conformity is available from: 
Siemens AB 
Security Products 
Englundavägen 7 
SE-171 24 Solna, Sweden

 

European Directive 1999/5/EC on Radio 
Equipment and Telecommunications Terminal 
Equipment (R&TTE): 

Compliance with the European Directive 1999/5/EC 
has been proven by testing according to the 
following standards: 

 EN 

301 

489-1 

  EN 301 489-3  

 EN 

300 

330-2 

Details of ordering 

Type PR500-Cotag, 

PR500-EM 

Part nr.  

Siemens 

PR500-Cotag: S24246-F4706-A1 
PR500-EM: S24246-F3913-A1 

Bewator 

PR500-Cotag: GBI:21-426 
PR500-EM: GBI:21-416 

Description Proximity 

reader 

Weight 0.11 

kg 

 

Technical data 

Supply voltage 
(nom.*): 

12 V DC – 24 V DC 

Absolute voltage 
ratings**: 

+10.6 V DC - +32 V DC

1)

 

Current consumption:

PR500-EM:

 

typ 22 mA@12V DC 
max 41 mA@12V DC 
typ 25 mA@24V DC 
max 43 mA@24VDC 

PR500-Cotag: 

typ 36 mA@12V DC 
max 61 mA@12V DC 
typ 36 mA@24V DC 
max 61 mA@24VDC 

Temperature range:  -30° C to +50° C 
Colour: Stone 
Material: UV-resistant 

ABS-plastic. 

Card read distance

2)

: Cotag: Up to 32 cm 

(active card). 
Cotag/EM4102: Up to 10 
cm (passive card). 

Dimensions 
(H x W x D): 

140 x 40 x 18,5 mm  

* Nominal voltage has margins for transformer tolerances, 
mains supply variations and interruptions. 
** Absolute voltage has no margins and should be used for 
guidance only

1) The PR500 is designed to be operated by 12V unregulated 
power supplies, or 24V battery-backed power supplies. 
Operating voltage range is 10.6 to 32.0V. The upper voltage 
is intended to be compatible with the charging of 24V lead-
acid batteries. Charge methods vary, and may be 
temperature dependent. 32V max is intended to be 
compatible with commonly used charging methods. If the 
upper operating voltage is exceeded then permanent damage 
may be caused. Installers and systems designers should 
check the max power supply voltage under all conditions. Do 
not operate the PR500 using unregulated 24V supplies. The 
PR500 current consumption can be significantly less than 100 
mA. The unloaded peak voltage from a nominal 24V 
unregulated supply will exceed the absolute max  
2) The Read range is stated in an undisturbed electrical 
environment, and that the reader is installed in accordance 
with Siemens AB instructions, with the card (IB928 or IB968) 
presented parallel to the reader.

 

Mounting and Mechanical 
Installation 

The reader can be mounted on all types of materials; 
it can be mounted behind glass or can even be flush 
mounted. The only limit is that the reader may not be 
completely surrounded by metal, if the reader is to 
be flush mounted then the distance to surrounded 
metal should be at least 3 cm, no metal should be 
directly in front of the reader. When flush mounting 
the reader, the maximum read range would reduce.  

Note!

 Avoid mounting the reader near sources of 

electrical noise, such as motors, generators, pumps, 
computer installations and mains cabling.  
If there is too much electrical noise in the reading 
area the amber LED flashes. 
The reader is supplied with the cover separate. If the 
cover has been fitted, remove it by pushing in the lug 
on its lower edge using a suitable screwdriver. At the 
bottom of the reader there is a knockout to facilitate 
cable entry if required. 
Mount the reader at a height of 1000 - 1200 mm 
(from the floor to the bottom edge of the reader).  
After installation, fit the top cover by locating its lugs 
at the top, pushing the bottom of the cover until it 
snaps into place. 
For outdoor mounting, we recommend that the 
terminals should be covered with a suitable 
compound, for example silicone grease. 

All other information regarding installation and 
programming can be found in the manual supplied 
with the control unit.  

Connection 

Connecting the PR500 to 
SiPass/Bewator Entro door central 
DC22, DC12 - or DC800 

Use a screened multicore cable (i.e. Belden 
9534/9535/9538) for connection between the reader 
unit and the door central. Maximum cable distance is 
50 metres.  

See Illustration 2 on page 6. 
Note!   

 For 

SiPass/Bewator Entro

: connect to the 

BCLINK terminal block. Set the link 

J4

 in the 

door central to 

+V = Vin

 For 

DC800

: Set jumper 

J1

 to 

Vin

 and jumper 

J4

 

to 

BCLINK

The power to the door central will then also be fed to 
the reader. 
When the PR500 is powered for the first time, the 
green and red LEDs light for 4 seconds. Then an 
Auto detect procedure starts for approx. 60 seconds 
where the three LEDs are lit (to configure for 
BCLINK protocol). It is important that cards or tags 
are not presented to the reader until this Auto detect 
procedure is completed. Once completed, the LEDs 
will turn off, a sound is heard and the reader is now 
ready for use. The readers LEDs are controlled 
exclusively by the host system. 

Connecting both Entry and Exit 
readers (BCLINK) 

If both Entry and Exit readers are to be used, the 
Exit reader must be set to an exit function. This is 
done with a link between terminal blocks 

HRN-Adr

 

and 

DA

 in the PR500 (before power-up). The 

initialising process will then be the same as above.  

See Illustration 3on page 6. 

Connecting the reader PR500 to 
Bewator Omnis 2010 E2V 

The drawing shows how the PR500 connects to the 
Bewator Omnis 2010 system where the node E2V is 
used. The power supply for the PR500 is connected 
to the E2V:s incoming power supply input. 

M24V

. Note that the incoming 0V also 

have to be connected to internal minus (on terminal 
block). 
Note that due to current limitations, no connections 
are made to the +12V power supply output terminals 
found within in the E2V.  The readers LEDs are 
controlled exclusively by the host system. 

See Illustration 4 on page 6 

Connecting the PR500 to SiPass 
integrated ADD5100 

The drawing shows how the PR500 connects to the 
SiPass integrated system where the ADD5100 (DRI) 
is used.  

See Illustration 5 on page 7. 
 

Содержание Bewator PR500EM

Страница 1: ...Siemens AB EN DE FR SV PR500 Cotag PR500 EM Card Reader Installation Guide PR500 Cotag PR500 EM ...

Страница 2: ...0 current consumption can be significantly less than 100 mA The unloaded peak voltage from a nominal 24V unregulated supply will exceed the absolute max 2 The Read range is stated in an undisturbed electrical environment and that the reader is installed in accordance with Siemens AB instructions with the card IB928 or IB968 presented parallel to the reader Mounting and Mechanical Installation The ...

Страница 3: ...ie Umgebung Der Leser muss entsprechend den Anweisungen von Siemens AB installiert worden sein und die Karte IB928 oder IB968 auf Leserhöhe gehalten werden Montage und Mechanische Installation Der Leser kann auf verschiedenen Materialien angebracht werden er lässt sich beispielsweise hinter Glas oder in die Wand einbauen Dabei darf der Leser nicht vollständig von Metall umgeben sein Wird er in ein...

Страница 4: ...tation 24 V non régulée La consommation électrique du PR500 peut être sensiblement inférieure à 100 mA Le pic de tension hors charge d une alimentation nominale non régulée de 24V dépassera le maximum absolu 2 La portée de lecture annoncée suppose que le lecteur soit installé dans un environnement sans interférences électriques et conformément aux instructions Siemens AB la carte IB928 ou IB968 do...

Страница 5: ...änd inte PR500 med oreglerad 24V DC PR500 strömförbrukning kan vara betydligt mindre än 100 mA En obelastad spänningstopp från ett nominellt 24V oreglerat aggregat kommer att överstiga absolut max 2 Läsavståndet avser en störningsfri miljö där läsaren har installerats helt enligt Siemens AB instruktioner och där kortet IB928 or IB968 hålls i samma höjd som läsaren Montering Läsaren kan monteras på...

Страница 6: ...6 Siemens AB 03 2011 Illustration 1 Illustration 2 Illustration 3 Illustration 4 ...

Страница 7: ...7 Siemens AB 03 2011 Illustration 5 ...

Страница 8: ...8 Siemens AB 03 2011 Mechanical Fixing dimensions Montage Abmessungen Dimensions de montage Monteringsmått ...

Страница 9: ......

Страница 10: ... Headquarters Englundavägen 7 SE 171 24 Solna Tel 46 8 629 0300 www buildingtechnologies siemens com 2011 Copyright by Siemens AB Data and design subject to change without notice Supply subject to availability Document no A24205 A335 N336 Edition 03 2011 ...

Отзывы: