PC tools
27
Siemens AB
Security Products
03.2014
7
PC tools
We recommend that a PC is connected to an SR35i and the software is installed
before any routers or Codoors so that the connection with each wireless unit may
be verified as installation progresses.
7.1 Bewator Entro Installer program
The
Bewator Entro Installer
program can be used for both configuring equipment
and verifying the connection.
Detection of new units
If a site is
not yet
configured in the PC database and new units are connected the
installer program will try to detect all available units, i.e. all units with the correct
segment ID and installation key. The address and type of each unit will automati-
cally be stored and displayed.
Configuring
All SR35i controllers connected to the PC are listed. The
Segment ID
and the
In-
stallation key
of any SR35i can be displayed. These parameters are needed for
creating the wireless network.
For enabling each RF30-EM Codoor to seek to connect to the SR35i, it must be
configured with these parameters and a unique address as described in the instal-
lation manual. Similarly each RF9 must be configured with the Segment ID and a
unique address.
The PC shows every RF9 and RF30-EM that it detects, with their addresses. This
enables a name to be given to each unit. Also check that the unit is intended to be
in the network position shown.
System information
Under the System Menu, click on System Information for a graphical summary of
the whole network. Select any unit for a summary of its address and system status
(units, addresses, firmware versions etc.) or to update the firmware.
7.2 Door monitor program
This
Door monitor
program is used for displaying and searching the logs recording
events, but also for some system commands (e.g. remotely unlocking doors).
Events related to the wireless network are also displayed. This includes e.g. com-
munication problems, low batteries, mechanical problem at door environment etc.
While verifying communication over the network, status changes displayed by this
program can be useful.
The program can preferably be used for displaying complementary status infor-
mation when verifying the overall communication.