![Siemens Bently Nevada 3500 Proximitor Скачать руководство пользователя страница 41](http://html.mh-extra.com/html/siemens/bently-nevada-3500-proximitor/bently-nevada-3500-proximitor_maintenance-and-troubleshooting-manual_374180041.webp)
3300 XL Proximity Transducer System Manual
24
Fault Type 4: V
XDCR
< V
SIG
< V
XDCR
+2.5 Vdc
Possible causes:
•
Faulty Proximitor
Sensor
•
Probe is incorrectly gapped (too far from target)
Check for fault condition Type 1 on page 14
R
JACKET
R
CORE
Measure resistance, R
JACKET
and R
CORE
:
Within specifications?
(See Specifications and Ordering Information)
No
Faulty Extension
Cable
Yes
Retest original system