Installation notes
AGG6.635 signal cable from the LMV6 to the AZL66. The AGG6.635 signal cable
is specified for use under the burner hood. If other signal cables are used, there is
no guarantee that the required cable features will be available.
Lay the AGG6.635 signal cable from the LMV6 to the AZL66 separately from other
cables.
Both the AGG6.635 signal cable and the AZL66 must be shipped and stored so
that no damage due to dust and water can occur during subsequent use in the
plant.
Prior to switching on the mains voltage, make certain that the AGG6.635 signal
cable has been connected to the AZL66 correctly.
The AZL66 must be used in a dry and clean environment.
The electrical power supply must be disconnected prior to installation.
The requirements of protection class
II
must be observed for the wiring.
Static charges must be avoided since they can damage the electronic components
of the AZL66 on contact.
Recommendation
: Use ESD equipment!
Caution
DIN EN 60335 and DIN EN 60730-2-5 must be complied with
Ensure that the electrical wiring inside the boiler complies with national and local
regulations.
The burner or boiler manufacturer must ensure degree of protection IP40 / IP54
for the LMV6 and AZL66 as per DIN EN 60529. Failure to observe this
information poses a risk of damaging the safety functions and a risk of electric
shock