Outline quantities of C bus participants
28
Building Technologies
008725_h_en_--
Fire Safety & Security Products
06.2011
9.3
Gateway limitation (CK)
check gateway configuration
Memory limitation (RAM)
yes
no
use CK1143
type gateway
station type CC1143
visible on CK ?
–
CK1143 (E3H021):
–
suitable for stations CI1142, CC1142, CC1143
Limitation of CERLOOP address range
Max. 8 C bus stations (CI/CC) can be addressed by one gateway.
If there are more than 8 C bus stations (CC/CI), then these must be split over 2 gateways.
More than 2 gateways can also be configured for special applications.
The visibility of C bus stations (CC/CI) on gateways may only be defined per station, and not per area!
yes
no
use second
gateway of
correct type
number of
stations > 8 ?
the configuration of
the gateway is checked
The limit values for the station (CI/CC), the operating unit (CT/CI) and
additional AlgoWorks programs must also be checked!