Logical and physical structure
14
Building Technologies
008725_h_en_--
Fire Safety & Security Products
06.2011
5
Logical and physical structure
The logical structure in the CS1140 fire detection system is totally separate from
the physical structure. This allows for maximum flexibility. Display and operation
are oriented towards geographical and organizational aspects and are not depend-
ent on the detector network's effective hardware installation.
Geographical conditions ( –> building structure)
Main building (area)
1st
floor
2nd
floor
Ground
floor
1st floor (section)
1st
floor
Room 104
Room 103
Room 102
Room 101
Room 104 (object)
Logical structure
The logical structure is a map of a system's
geographical circumstances. It can be flexibly
adapted to the building structure, room use,
etc.
The logical structure within a control panel is
independent of the line arrangement of the
detector network.
Link
The lowest levels of the two structures are
linked to one another. The physical units (e.g.
detectors) at each logical or geographical
location are determined.
Physical structure
The physical structure is a map of the hard-
ware. It is provided by the hardware installa-
tion. The number of levels used depends on
the hardware used.
Logical structure
C-Bus
D-Bus
I-Bus
Area
Section
Zone
Element
Main
building
Ground
floor
1st
floor
2nd
floor
Ware-
house
Reception
Room
102
Room
103
Room
104
Canteen
EDP
room
Linking
Control terminal
Control unit
CC/CI
Function unit
Station
Device
CT11
Level 1
Line 1
Level 1
Line 2
Line 3
Line 4
Level 2
Level 3
DCW
DOW
Level 2
Physical structure