Connections and LEDs 

 

12 

Siemens AB

 

 

Security Products 

 

05.2015

 

 

7.6 Jumper 

settings 

 

Jumper Description 

Value 

LK1 + LK2 

BIAS 

These links enable the RS-485 bus biasing resistors. The 
resistors create a voltage divider to force the voltage to be 
less than the threshold of the receiver. This prevents invalid 
data bits that are picked up from the noise on the cable from 
being transmitted. 

Jumper placed across LK1 and LK2: 

 

RS485-FLN biasing resistors enabled. 

LK9 – LK16 

FOR OUTPUT CONTROL 

These links control the Fire Over-ride activation for each 
individual relay output 1-8. 

Depending on where you place the link, the relay output 
behaviour will be modified by FOR 1 input, FOR 2 input, or 
FOR will be disabled for that relay. 

LK9

FOR 1

FOR 2

DIS

LK10

LK11

 

Relay output RELAY1 OUT (LK9) is set to 

FOR 

disabled

,  

Relay output RELAY2 OUT (LK10) is set to 

FOR 1,

 

Relay output RELAY3 OUT (LK11) is set to 

FOR 2

LK17 and LK18 

+ LK21 and LK22 

FOR MODE 

Configuration of the Fire Override mode: 

– 

Enhanced FOR mode (monitored) 

– 

Normal FOR mode (floating).  

 

 

N

O

R

M

A

L

LK21 LK22

 

N

O

R

M

A

L

LK17 LK18

FOR 2

FOR 1

 

Jumpers placed over both links (e.g. FOR1): 

 

Input set to Normal FOR mode. 

Both jumpers removed (e.g. FOR2): 

 

Input set to Enhanced FOR mode. 

LK19 and LK20 + 
LK23 and LK24 

 

FOR AKTIVATION 

– 

FOR enabled 

 

Activation of the FOR input will cause the appropriate 
output relays to pick up or drop out depending on where 
the links LK9 – LK16 are placed. 

– 

FOR disabled 

 

The input will have no effect on the relays. 

 

 

 

FOR disabled 

FOR enabled 

LK25 

EOL TERMINATION (Serial Reader Interface) 

This link allows the Serial Card Interface communications channel to be terminated in noisy comms lines. 

Note: 

It is only to be fitted on the first unit or the last unit on the bus. 

LK26 

EOL TERMINATION (FLN System Bus) 

This link allows the RS485 bus communication channel to be terminated in lengthy comms lines – more than 
100 m at 115 kb/s. 

Note: 

Only units that are located at the ends of bus lines should have Link 26 set to on. 

LK27 

RESET (Restart)

 

Reset the ADE5300 retaining the unit’s firmware: 

– 

Interrupt the power supply to the unit for 1 sec or 

– 

Close link 27, wait for the activity LED to switch off, then remove LK2. 

LK28 

GP1 RESET MODE  

Reset the firmware: 

– 

Close LK28 

– 

Close link 27, wait for the activity LED to switch off, then remove LK2. 

– 

Remove LK28 before loading the new firmware 

ENABLE

LK19 LK20

FOR 1

ENABLE

LK23 LK24

FOR 2

LK2 

LK1 

Содержание ADE5300

Страница 1: ...Siemens AB Security Product SiPass integrated ADE5300 Eight Reader Interface Installation Manual ...

Страница 2: ...vorgängige schriftliche Ermächtigung ganz oder teilweise Dritten zugänglich machen oder außerhalb des Zweckes verwenden zu dem es ihm übergeben worden ist We reserve all rights in this document and in the subject thereof By acceptance of the document the recipient acknowledges these rights and undertakes not to publish the document nor the subject thereof in full or in part nor to make them availa...

Страница 3: ... data 7 5 Scope of delivery 7 6 Installation 8 7 Connections and LEDs 9 7 1 Connections 9 7 2 Port locations 10 7 3 Reader wiring 10 7 4 Wiring of monitored input 10 7 5 FOR inputs 11 7 6 Jumper settings 12 7 7 LEDs 13 8 Cable specifications 14 9 Programming and firmware download 14 10 Disposal 15 10 1 Record of proper waste management 15 ...

Страница 4: ...4 Siemens AB Security Products 05 2015 ...

Страница 5: ...mage or personal injury caused by improper use or non observance of these safety instructions In such case any guarantee expires PLEASE NOTE Connection commissioning and maintenance must only be carried out by suitably qualified personnel Correct and safe operation of this device depends on proper transport storage installation and connection as well as careful operation and maintenance DANGER Wor...

Страница 6: ...DC Enhanced mode requires the connection of 22 kOhm resistor circuits Cable must be shielded and total cable run resistance must not exceed 100 Ohms Fire Override FOR output 2 x Relay 2 A 30 V DC Local input 1 x passive device connection unsupervised Local output 1 x open collector 100 mA 9 7 12 V DC Reader Power supplies 8 x 400 mA 9 7 12 V DC 1 x 1 5 A 9 7 12 V DC Dimensions with baseplate W x H...

Страница 7: ...50 mm 9 84 Height 287 mm 11 30 Depht 50 mm 1 97 4 Ordering data Type Part no Designation Weight ADE5300 S24246 A2500 A1 Eight Reader Interface 1 3 kg 5 Scope of delivery 1 x ADE5300 mounted on base plate 1 x accessory bag resistors for monitored inputs 1 x installation manual English 1 x installation manual German ...

Страница 8: ...e cabinet backplane and proceed to step 3 It is recommended that you affix the ADE5300 at all four of the mounting locations provided Warning Do not apply power to the ADE5300 or associated components at this stage 3 Select the appropriate drill bit according to the mounting surface hole size and drill the holes in the locations marked if required 4 Fasten the ADE5300 base plate to the surface usi...

Страница 9: ...see Section 7 4 Wiring of monitored input Please note this applies to all inputs The total cable run resistance must not exceed 100 Ohms 5 Connect any auxiliary output devices to the AUX OUT ports open collector on the ADE5300 6 Connect each door opener to the appropriate RELAY OUT port on the ADE5300 Access doors can only be connected to output relays that are controlled by readers 7 For example ...

Страница 10: ... 1 2 OUT FOR outputs LOCAL IN Tamper input for local tamper detection LOCAL OUT Alarm output e g siren strobe light SRB RS485 Connection for a serial card reader SRB PWR Power output for serial card readers 7 3 Reader wiring Wiegand reader wiring Reader Type D0 D1 GRN RED 0 V 12 V Wiegand D0 D1 GRN RED 0 V 12 V RS 485 reader wiring Reader Type S 12 V 0 V RS 485 Shield or B or A 8V 12V 0V GND 7 4 W...

Страница 11: ... contact Fire alarm system output Fire alarm system OK contact between NO and COM closed In case of fire alarm or malfunction contact between NO and COM open FOR input enhanced mode Fire alarm system relay contact Fire alarm system output Fire alarm system OK contact between NO and COM closed In case of fire alarm or malfunction contact between NO and COM open The following diagram provides an exa...

Страница 12: ...ed over both links e g FOR1 Input set to Normal FOR mode Both jumpers removed e g FOR2 Input set to Enhanced FOR mode LK19 and LK20 LK23 and LK24 FOR AKTIVATION FOR enabled Activation of the FOR input will cause the appropriate output relays to pick up or drop out depending on where the links LK9 LK16 are placed FOR disabled The input will have no effect on the relays FOR disabled FOR enabled LK25...

Страница 13: ...VITY LED 1 LED blinking quickly Firmware needs to be downloaded 2 LED blinking slowly approx once per sec Firmware has been downloaded FLN COM The LED flashes when the ADE5300 is sending data to the AC5100 SRB COM The LED flashes when the ADE5300 is receiving data from an RS485 card reader RLY 1 8 The Output relays status is displayed as activated with green LEDs IN1 IN32 REX1 REX8 DC1 DC8 FOR1 IN...

Страница 14: ... 24 7 x 32 0 6 Tinned Copper Foam Polyethylene Aluminium foil Polyester tape no braid PVC 6 3 8 4 RS 422 4 2 24 7 x 32 0 6 Tinned Copper Foam Polyethylene Aluminium foil Polyester tape no braid PVC 6 3 8 4 RJ 45 8 4 24 Solid 0 6 Bare Copper Polyethylene Unshielded PVC 8 4 24 7 x 32 0 6 Tinned Copper RJ 12 8 4 24 Solid 0 6 Bare Copper Polyethylene Aluminium foil Polyester tape no braid PVC 8 4 24 7...

Страница 15: ...by the European Directive 2002 96 EC The correct disposal and separate collection of your old appliance will help prevent potential negative consequences for the environment and human health It is a precondition for reuse and recycling of used electrical and electronic equipment For more detailed information about disposal of your old appliance please contact your city office waste disposal servic...

Страница 16: ...al Headquarters Englundavägen 7 SE 171 24 Solna Tel 46 8 629 0300 www siemens com securityproducts 2015 Copyright by Siemens AB Data and design subject to change without notice Supply subject to availability Document No A24205 A335 B275 Edition 06 2015 ...

Отзывы: