7 / 14
A6V10881143_en--_d
Siemens
2021-06-01
Smart Infrastructure
Reg.
Name
R/W
Scaling
Range / enumeration
Device information
1281
Factory Index
R
Two bytes, each coding an ASCII
char.
00 5A
00 “Z”
Device is of Series “Z”
1282
Factory Date HWord
R
Two bytes, the lower coding the
Year (hex)
Reg. 1282 = 000F/Reg. 1283 = 0418
HWord
LWord
--
YY
MM
DD
Hex
00
0F
04
18
Dec
00
15
04
24
Mfg. date = 24 April, 2015
1283
Factory Date LWord
R
High byte: month (hex)
Low byte: day (hex)
1284-85 Factory SeqNo
R
Hword + LWord = Sequence
number (hex)
Read 1284
000A
Read 1285
A206
AA206(hex) = 696838 (dec)
1409-16
TypeASN
[Char_16..1]
R
Each register: Two bytes, each
coding an ASCII char.
ASN is coded beginning with reg.
1409
Example:
0x47 44 = GD
0x42 31 = B1
0x38 31 = 81
0x2E 31 = .1
0x45 2F = E/
0x4D 4F= MO
ASN = „GDB181.1E/MO“
Register 769 “Status”
Status
Bit 00
1 = Local override
Bit 06
1 = Adaption done
Bit 01
1 = Backup mode active
Bit 07
1 = Adaption in progress
Bit 02
1 = reserved
Bit 08
1 = Adaption error
Bit 03
1 = reserved
Bit 09
1 = Selftest failed
Bit 04
1 = Device jammed
Bit 10
1 = Selftest passed
Bit 05
1 = Nom. lifetime exceeded
Bit 11
1 = Invalid configuration
Supported function codes
Function codes
03 (0x03)
Read Holding Registers
04 (0x04)
Read Input Registers
06 (0x06)
Write Single Register
16 (0x10)
Write Multiple registers (Limitation: Max. 120 registers within one message)