Push-button addressing  

Display current address (digits in reverse order) 

The Modbus address can be set without a separate tool by using the push-button and LED. 

To display the current address, press button <1s.  

Colors 

1-digits: 

red

 

10-digits: 

green

 

100-digits: 

orange

 

 

Example for address 124:

 

LED 

 

Note 

The address is entered and shown in reverse order. 

 

Set new address (digits in reverse order) 

1. 

Enter addressing mode

: press button > 1s until LED shines 

red

, then release button 

(before LED gets dark). 

2. 

Enter digits

: press button n-times 

 LED flashes per button press (feedback). 

Colors: 1-digits: 

red 

/ 10-digits: 

green 

/ 100-digits: 

orange

 

3. 

Store digits

: press button until LED shines in color of following digits –  release button,  

4. 

Save address

: press button until LED shines 

red 

(confirmation) 

 release button.  

An address can be stored at any time, i.e. after setting the 1-digits, or after setting the 1- 
and the 10-digits.  

5.  Entered address is repeated one times for confirmation. 

 

Note: If button is released before LED shines red, the address is discarded.

 

 

Examples 

Set address “124”: 

1.  Enter addressing mode 
2.  Set 1-digits: Press button 4-times 

 LED flashes 

red 

per button press  

3.  Store 1-digits: press button until LED shines 

green

 – release button 

4.  Set 10-digits: Press button 2-times 

 LED flashes 

green

 per button press 

5.  Store 10-digits: press button until LED shines 

orange

 – release button 

6.  Set 100-digits: Press button 1-times 

 LED flashes 

orange

 per button press 

7.  Store address: press button until LED shines 

red 

– release button  

 address is stored and displayed 1x for confirmation 

 
Set address “50”: 

1.  Enter addressing mode 
2.  Skip 1-digits: Hold button pressed until LED shines 

green 

– release button 

3.  Set 10-digits: Press button 5-times 

 LED flashes 

green

 per button press  

4.  Store address (skip 100-digits): hold button pressed until LED shines 

red 

– release button  

 address is stored and displayed 1x for confirmation 

 
Set address “5”: 

1.  Enter addressing mode 
2.  Set 1-digits: Press button 5-times 

 LED flashes 

green

 per button press  

3.  Store address: press button until LED shines 

red

  

 address is stored and displayed 1x for confirmation 

 

Содержание Acvatix GDB111.9E/MO

Страница 1: ...nal torque GLB111 9E MO with 10 Nm nominal torque Operating voltage AC 24 V For air handling units AHU and other heating cooling applications Modbus RTU communication UL listed For 2 port and 3 port control ball valves internally threaded connections VAI61 and VBI61 or externally threaded connections VAG61 and VBG61 DN15 to DN50 For 6 port control ball valve externally threaded connections VWG41 D...

Страница 2: ...ers 06 Write Single Register 16 Write Multiple registers max 120 registers within one message For a detailed description of specific functions please refer to the product documentation CE1Z4634 Type summary Product no Stock no Operating voltage Positioning signal Power consumption Posit time Manual adjuster Position feedback GLB111 9E MO S55499 D206 AC 24 V Modbus RTU 1 VA 0 5 W 3 VA 2 5 W 1 150 s...

Страница 3: ...I61 32 16 Rp 1 VBG61 32 16 G 2 B 16 32 VBI61 40 25 Rp 1 VBG61 40 25 G 2 B 25 40 VBG61 50 40 G 2 B 40 50 VBI61 50 Rp 2 40 63 50 1 Data sheet N4211 2 Data sheet N4212 VWG41 6 port control ball valve Ball valves with kvs m3 h DN G B1 9E internal threads Rp external threads5 G B pmax ps VWG41 20 G1B 0 25 4 25 20 200 5 Data sheet A6V10564480 Product no Stock no Description Doc type Doc number AST20 S55...

Страница 4: ...s and patterns Color Pattern Description Green steady Start up 1s on 5s off Fault free operation life pulse flashing Bus traffic Orange green 1s orange 1s green Device is in override control Orange 1s on 1 off Bus parameters not yet configured Orange 1s on 5s off Backup mode entered Red Steady Mechanical fault device jammed 1s on 5s off Internal error 0 1s on 1s off Invalid configuration e g Min M...

Страница 5: ... is repeated one times for confirmation Note If button is released before LED shines red the address is discarded Examples Set address 124 1 Enter addressing mode 2 Set 1 digits Press button 4 times LED flashes red per button press 3 Store 1 digits press button until LED shines green release button 4 Set 10 digits Press button 2 times LED flashes green per button press 5 Store 10 digits press butt...

Страница 6: ...rs 257 Opening direction RW 0 CW 1 CCW 258 Adaptive Mode RW 0 Off 1 On 259 Operating Mode RW 1 POS 260 MinPosition RW 0 01 0 100 261 MaxPosition RW 0 01 0 100 262 Actuator Running Time R s 1 150 513 Backup Mode RW 0 Go to BackupPosition 1 Keep last position 2 Disabled 514 Backup Position RW 0 01 0 100 515 Backup Timeout RW s 1 0 65535 516 Startup Setpoint RW 0 01 0 100 764 Modbus Address RW 1 247 ...

Страница 7: ...8 dec 1409 16 TypeASN Char_16 1 R Each register Two bytes each coding an ASCII char ASN is coded beginning with reg 1409 Example 0x47 44 GD 0x42 31 B1 0x38 31 81 0x2E 31 1 0x45 2F E 0x4D 4F MO ASN GDB181 1E MO Register 769 Status Status Bit 00 1 Local override Bit 06 1 Adaption done Bit 01 1 Backup mode active Bit 07 1 Adaption in progress Bit 02 1 reserved Bit 08 1 Adaption error Bit 03 1 reserve...

Страница 8: ...y actuators Mounting positions cf mounting instr A6V10920701 1 1 Related documents such as environmental declarations CE declarations etc can be downloaded at the following internet address http siemens com bt download Engineering If condensation occurs at the mounting site the use of the temperature adapter ALJ100 is recommended in order to protect the actuator If the medium temperature is 0 C th...

Страница 9: ...n nection between the Modbus master programming tool and peripheral devices i e non conflicting addresses and matching baudrate transmission format Full configuration over bus If the address is unique per segment when powered up the device can be accessed by the Modbus master or programming tool and the address and other parameters can then be set to the definitive values Partial configuration ove...

Страница 10: ...device for disposal in terms of European Directive 2012 19 EU and may not be disposed of as domestic garbage Dispose of the device through channels provided for this purpose Comply with all local and currently applicable laws and regulations Warranty Technical data on specific applications are valid only together with Siemens products listed under Equipment combinations Siemens rejects any and all...

Страница 11: ...r bus Clockwise CW Counter clockwise CCW Connection cables Cable length 0 9 m Power supply Communication Number of cores and cross sectional area 5 x 0 75 mm2 Service interface Terminal strip 7 pin grid 2 00 mm Communication Communication protocol Modbus RTU RS 485 galvanically separated Number of nodes Max 32 Address range 1 248 255 Default 255 Transmission formats 1 8 E 1 1 8 O 1 1 8 N 1 1 8 N 2...

Страница 12: ...ic compatibility Application For residential commercial and industrial environments GLB111 9E MO GDB111 9E MO EU Conformity CE A5W00000176 1 A5W0003842 1 RCM Conformity A5W00000177 1 A5W0003843 1 UL cUL AC 24 V UL 873 http ul com database Environmental compatibility The product environmental declaration A6V10209938 1 contains data on environmentally compatible product design and assessments RoHS c...

Страница 13: ... voltage AC 24 V 2 black BK G0 System neutral AC 24 V 6 violet VT REF Reference 8 grey GY Bus Modbus RTU 9 pink PK Bus Modbus RTU Note The operating voltage at terminals G and G0 must comply with the requirements under SELV or PELV Safety transformers with twofold insulation as per EN 61558 required they must be designed to be on 100 of the time Dimensions Actuator Dimensions in mm 100 mm 200 mm M...

Страница 14: ... 58 724 24 24 www siemens com buildingtechnologies Siemens Switzerland Ltd 2021 Technical specifications and availability subject to change without notice Dokument ID A6V10881143_en _d Ausgabe 2021 06 01 Temperature adapter optional Revision numbers Type Valid from rev no GLB111 9E MO B GDB111 9E MO C 42 70 64 162 8 23 5 ...

Отзывы: