Current Input Specifications

Specification

Value

Overload

15 Amps continuous,  300 Amps for 1 second, non-recurring

Impedance

2 m

Burden

0.0625 VA @ 6.25 Amps

Overrange Capability

The 1 Amp and 5 Amp phase current inputs provide 25% overrange
capability that allows current readings to be accurately displayed up to
125% of full scale.  For example, if the CT Primary setup register in the
Power Meter module has been set at 2000A full scale, the 9700 Power Meter
allows for readings up to 2500A.

The 1 Amp and 5 Amp phase current inputs also allows for up to 2000% of
full scale for a maximum duration of 1 second.  This provides a 20X fault
capture capability.  The 10 Amp phase current inputs on revenue meters
allow for up to 1000% of full scale for a maximum duration of 1 second,
providing a 10X fault capture capability.

Using Current Transformers

The 9700 Power Meter is compatible with CTs with 1 Amp, 5 Amp or 10
Amp full scale secondaries (depending on the options purchased).  The
current input ratings of all three-phase inputs and the I4 input are
equivalent.

The CT secondary should have a burden capacity greater than 3 VA.  The
length of the CT cabling should be minimized because long cabling
contributes to inaccuracy.  Also, the CT burden rating must exceed the
combined burden of the 9700 Power Meter plus cabling and any other
connected devices (burden is the amount of load being fed by the CT,
measured in Volt-Amps).

Overall accuracy depends on the combined accuracy of the 9700 Power
Meter, the CT, and the PTs (if used).

I4 Current Input Connection

I4 is typically used to measure the current flow in the neutral or ground
conductor.  Connection is optional.  The secondary rating of the CT
connected to the I4 input must be identical to that of the three phase current
inputs.

The primary rating for the CT connected to the I4 input can be different from
the three phase inputs, since the I4 input scaling can be programmed
independently.

2

38)

Refer to the 9700 Power
Meter User’s Guide for
Revenue Metering CT and
PT selection.

Содержание 9700

Страница 1: ...9700 Power Meter Installation and Basic Setup Instructions ...

Страница 2: ...rmation contained herein is general in nature and not intended for specific application purposes It does not relieve the user of responsibility to use sound practices in application installation operation and maintenance of the equipment purchased Siemens reserves the right to make changes at any time without notice or obligations Should a conflict arise between the general information contained i...

Страница 3: ...ion functions Do not hipot test voltage inputs refer to the label on the device for the maximum voltage level the device will withstand CAUTION Failure to observe the following may result in permanent damage to the device The 9700 Power Meter offers a range of hardware options that affect input ratings The serial number label of the 9700 Power Meter lists all equipped options Applying current leve...

Страница 4: ......

Страница 5: ...nnection Diagram 15 4 Wire Wye 3 Element 3 PT Connection Diagram 15 4 Wire Wye 2 Element 2 PT Connection Diagram 16 3 Wire Grounded Wye 3 Element Direct Connection Diagram 16 3 Wire Delta 2 Element 2 PT 3 CT Connection Diagram 17 3 Wire Delta 2 Element 2 PT 2 CT Connection Diagram 17 Single Phase Connection Diagram 18 Connecting the Status Inputs 18 Connecting the Auxiliary Analog Inputs 19 Connec...

Страница 6: ...implementation of both protocols to meet current market communications requirements Siemens therefore reserves the right to make improvements including changes to specifications at any time without notice or obligation 2000 Siemens Energy Automation Inc SIEMENS is a registered trademark of Siemens AG ACCESS WinPM Static Trip III SAMMS SEABus ISGS and Isolated Multi Drop are trademarks of Siemens E...

Страница 7: ...hase Current and Power Supply connections 2 5 mm to 4 0 mm AWG 14 to AWG 12 2 2 SHORTING BLOCK orTEST BLOCK 22 AWG 0 50 mm shielded twisted pair 2 Refer to the section RS 232 Serial Cable Wiring Connections Use the wiring specifications found in Local or National Electrical Codes if they differ from specifications shown in this document RS 485 bus 9700 POWER METER RXD CD TXD Heartbeat TXD Captured...

Страница 8: ...h board 15 3 8mm Mount flush on any flat surface Wire sizes will vary depending on application YOU MUST REMOVETHE JUMPER ON BOARD A IF AN EXTERNAL POWER SUPPLY IS USED I O BOARD requires a supply power if more than 6 analog devices are used or if a custom cable is used for connection to the 9300 Power Meter If the supplied cable is used and 6 or less analog devices are installed I O BOARD A receiv...

Страница 9: ...10BASE T 10BASE FL 6 6 LINK T 22 AWG 0 50 mm twisted shielded pair 2 Category 3 4 or 5 UTP 62 5 125 m multimode fiber µ Power Voltage and CurrentTerminal Strip COM1 MG7 Captured wire connectors RJ45 connector ST type connector Getting More Information 4S IV 1IXIV 9WIV W YMHI 9700 Power Meter operation and usage details displaying data making configuration changes customizing operation using output...

Страница 10: ...ing the enclosure size allow for extra space for all wiring intermediate terminal strips shorting blocks or any other required components The mounting enclosure should not impede ventilation Mounting the Base Unit The 9700 Power Meter base unit can be mounted flush against any flat surface The unit provides four slots on its mounting flange for this purpose The 9700 Power Meter is typically mounte...

Страница 11: ... 32 5 0 7 5 167 7 21 1 6 6 783 Top View with Mounting Slot Locations PP PP PP PP PP P P PP PP PP PP PP PP PP PP P P Side View End View P P PP PP P P PP PP ...

Страница 12: ...required behind the panel to allow for cable connection The length of the interconnecting cable supplied limits the distance between the mounting locations of the MGT and the base unit The maximum cable length is 61 m 200 ft RearView Top View P P P P PP PP PP P P PP P P PP PP PP Mounting Holes and Panel Cutout P P P P P P PP PP ORFDWLRQV PP PP 238 Refer to the last page of this guide for a full si...

Страница 13: ... behind the board to allow for cable connection and for the I O devices Refer to the following mounting diagram End View Top View P P PP PD 3 1 803 5 PP P P P P OHDUDQFH IRU VFUHZ SODFHV PP GLDPHWHU 1 ORQ VWDQGRII SODFH PP PP PP Mounting the Expansion Board Power Supply Depending on the I O options supplied with the 9700 Power Meter you may have one or two external power supplies Mount the power s...

Страница 14: ...trates all the dimensions required for mounting Top View Side and End Views 0 PP 0RXQWLQJ ROH 0 PP 0RXQWLQJ ROH PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP P24 48 Option The P24 48 external power supply must be mounted within 18 inches 45 cm of the external I O board Top View Side and End Views PP PP WKUHDG 3ODFHV PP PP PP PP PP PP ...

Страница 15: ...table on the following page Note that the optional analog input board the I O expansion boards additional power supplies MGT accessories and the revenue meter key are all ordered as separate items They do not appear in the options box on the 9700 Power Meter s label The acceptable power supply range is indicated here See the power supply discussion below for more details The current input option i...

Страница 16: ...ter itself If control relays are used with the external I O modules there should be a bypass mechanism installed Terminal Strips All connections to the 9700 Power Meter base unit are made to terminal strips and cable headers at either side of the unit The terminal strip for phase voltage current and supply power input is a barrier type for which ring or spade terminals may be used to simplify conn...

Страница 17: ...om the voltage source it is monitoring as long as it is within the supply range The basic model has a nominal power supply range of 100 to 240 VAC but will operate correctly from 85 VAC up to 264 VAC Applying power above 264 VAC can cause permanent damage to the power supply The unit can also be powered by 110 to 300 VDC Supply current can be as high as 1 Amp 56 W dependent on whether an MGT unit ...

Страница 18: ... inputs and their relationship is critical to the correct operation of the unit All phase voltage sense leads should be protected by breakers or fuses at their source Voltage Input Specifications Voltage input ranges are defined by ordering options see Direct Connection Voltage input overload withstand rating is 1500 VAC RMS continuous and 2500 VAC RMS for one second non recurring Input impedance ...

Страница 19: ...ch as 220 VAC V1 Input Connection The 9700 Power Meter uses the V1 input as the reference for frequency for all power and energy related measurements For any system configuration the V1 input must be connected to ensure accurate readings and correct operation of the 9700 Power Meter Voltage Reference Vref Input Connection The voltage reference terminal Vref of the 9700 Power Meter serves as the ze...

Страница 20: ...mp 5 Amp or 10 Amp full scale secondaries depending on the options purchased The current input ratings of all three phase inputs and the I4 input are equivalent The CT secondary should have a burden capacity greater than 3 VA The length of the CT cabling should be minimized because long cabling contributes to inaccuracy Also the CT burden rating must exceed the combined burden of the 9700 Power Me...

Страница 21: ...t Import Switchgear Chassis Ground CTs Fuses Fuses 2A PTs A B C N LINE V3 V2 V1 I1 I2 I3 I4 V1 V2 V3 Vref I11 I12 I21 I22 I31 I32 I41 I42 L N _ Supply Power dependent on equipped power supply option 3 A slow blow 3 A slow blow 238 The 9700 Power Meter senses the line to neutral or ground voltage and current for each phase creating an equivalent three element metering configuration VOLTS MODE shoul...

Страница 22: ...LINE A B N Fuses 2A CTs C CT Shorting Switch or Test Block Export Import Switchgear Chassis Ground Supply Power dependent on equipped power supply option 2 A slow blow 2 A slow blow LOAD V1 V2 V3 Vref V1 V2 V3 I11 I12 I21 I22 I31 I32 I1 I2 I3 _ L N 238 This 2 element scheme requires only 2 PTs In this configuration the phase B voltage displayed by the meter is derived from the phase A and C voltag...

Страница 23: ...I31 I32 I41 I3 I42 I4 _ L N 3 A slow blow Switchgear Chassis Ground LOAD Import Export CTs PTs Fuses LINE C B A CT Shorting Switch or Test Block 3 A slow blow Supply Power dependent on equipped power supply option 238 For ungrounded floating 3 wire open Delta systems the 9700 Power Meter always requires PTs and senses the line to line voltages between each of the phases The 9700 Power Meter can be...

Страница 24: ...ze that is appropriate for your application and complies with local electrical codes The 9700 Power Meter uses a current sensing technique to monitor contact status by providing an internal 30 VDC supply for self excitation These inputs can be used for dry contact sensing applications but not for voltage sensing applications Note that no ground or external voltage connections are required 238 Conn...

Страница 25: ... label on the 9700 Power Meter for the AUX rating Connections to the analog inputs are made via a captured wire type terminal block on the 9700 Power Meter Use a wire size that is appropriate for your application and complies with local electrical codes Assignment and input scaling for each input is user programmable via the Analog Input modules See the 9700 Power Meter User s Guide for details Ty...

Страница 26: ...g I O Devices to the Expansion Boards on the next page for details on power requirements for analog I O devices Like the 9700 Power Meter itself there are two power supply options for the external I O board the P240 and the P24 48 option The P240 external power supply can be powered by 100 to 240 VAC but will operate correctly from 85 VAC up to 264 VAC Applying power above 264 VAC can cause perman...

Страница 27: ...B When using an external power supply with Expansion Board A you must remove the jumper JMPR on the board see the diagram on page 2 Failure to do so will void the 9700 Power Meter warranty Connecting I O Devices to the Expansion Boards To install an I O device simply plug it in to an appropriate slot and tighten the fastening screw There are several restrictions governing the use of the Expansion ...

Страница 28: ...er supply is required for Expansion Board B in any configuration To use the maximum number of analog I O devices two power supplies must be used one for each expansion board Note that if a separate power supply is used with Expansion Board A then the jumper JMPR must be removed from the board Failure to remove the jumper will void the 9700 Power Meter s warranty Analog Device Restrictions Directio...

Страница 29: ...fault configuration 6 6 6 Any combination up to 6 total Board A WITH Optional Power Supply 7 15 15 Board full Board A WITHOUT Optional Power Supply default configuration Board B 13 21 21 A 6 AI B 7 AI 8 AO A 6 AO B 7 AI 8 AO A 6 AO B 15 AO A 6 AI B 15 AO Board A WITH Optional Power Supply Board B 14 30 30 Both boards full I O Device Connections Expansion boards provide captured wire type terminal ...

Страница 30: ...d input for input 1 and the even numbered input for input 2 For example if you are connecting to a module in slot 6 substitute input 13 for input 1 in the diagram and input 14 for input 2 in the diagram Analog Inputs GAIVDC1 GAIVDC5 GAIVDC10 GAIIDC420 GAIVDC5B GAIVDC10B GAITCR GAITCT GAITCJ GAITCK GAIRTD Analog Outputs GAOVDC5 GAOVDC10 GAOIDC420 GAOVDC5B GAOVDC10B Voltage or Current Transducer 2 1...

Страница 31: ...cing for example firmware upgrades 2 Anytime the 9700 Power Meter has powered down and powered back up test the digital outputs of the 9700 Power Meter to ensure that all your control condition s are occurring as expected 3 When you have verified all control operations relay control of the external equipment can be used 4 Do not use digital output modules on I O Expansion Board B for control appli...

Страница 32: ...n All inputs pass the ANSI IEEE C37 90 1989 surge withstand and fast transient tests Specification Value Baud Rates 300 to 19 200 bps Duplex Full Supported Protocols SEABus Modbus RTU GPS TRUETIME DATUM GPS ARBITER Isolation Optical isolation from all other inputs and outputs excluding the COM 1 RS 485 port isolation voltage is 750 V peak for 10 seconds 60 Hz Serial Cable Wiring Connections RS 232...

Страница 33: ...ns Male DB9 Pins Female DB25 Pins Female RPSXWHU 3RZHU 0HWHU 56 3RUW XQFWLRQ XQFWLRQ 7 5 5 7 6LJQDO URXQG 6 576 576 76 76 65 75 0RGHP 3RZHU 0HWHU 56 3RUW XQFWLRQ XQFWLRQ 7 5 5 7 6LJQDO URXQG 6 576 576 76 76 65 75 Computer Connections The cable used between a computer and external modem if used is a standard straight through RS 232 communications cable with a maximum length of 50 feet 15 2 m Refer ...

Страница 34: ...itialization strings Any changes to the Modem Init or Baud Rate setup registers while the modem is online will cause the modem to disconnect from the phone line RJ11 Pin Assignments The following diagram shows the pin assignments of a male RJ11 connector 7LS 5LQJ 5 If you ordered the MDMC option a cable is supplied with an RJ11 connector on one end and bare wire on the other Attach the bare wire e...

Страница 35: ... CARD COM 2 and COM 3 RS 485 connections are made on the top of the unit refer to the diagram on page 3 Terminal connections are marked as follows Marking Terminal Function SHLD RS 485 Shield electrically connected to chassis ground RS 485 Data Minus RS 485 Data Plus Up to 32 devices can be connected on a single RS 485 bus Use a good quality shielded twisted pair cable recommended for RS 485 appli...

Страница 36: ...n two cables should be connected This includes connection points on instruments converters and terminal strips Following this guideline ensures that both star and tee connections are avoided Ethernet Connections XPRESS CARD Only If you purchased the optional XPRESS CARD one 10Base T and or one 10Base FL Ethernet port will be available depending on ordering options specified Specifications are as f...

Страница 37: ...ir cable with a male RJ45 modular connector for connection to the 10Base T port or 62 5 125µm multimode fiber cable with ST type connectors for connection to the 10Base FL port Refer to 9700 Power Meter Basic Setup on page 32 for instructions on configuring the Ethernet communications link from the MGT ...

Страница 38: ...wer Meter The MGT interface is ideal for field installation quick device adjustments and use by maintenance personnel while at the installed location of the device The MGT provides a Quick Setup feature for basic setup operations To perform basic setup through the MGT press the button labeled SETUP and then the button labeled QUICK SETUP The following menu appears Press the QUICK SETUP button to a...

Страница 39: ...Setup Register Factory Default Function Volts Mode 4W WYE The power system s configuration WYE DELTA Single etc PT Prim 120 277 347 The Potential Transformer s primary winding rating for V1 V2 and V3 PT Sec 120 277 347 The Potential Transformer s secondary winding rating for V1 V2 and V3 CT Prim 5000 The Current Transformer s primary winding rating for I1 I2 and I3 CT Sec 5 The Current Transformer...

Страница 40: ...he serial number of the meter using the last four numbers before the dash For example serial number PA 970 B 01 Unit ID The default Unit ID values for Com 2 and Com 3 are 101 and 102 respectively Settings for Different Serial Ports The Baud Rate Unit ID and Protocol setup registers are available for each installed serial port The MGT displays CM1 CM2 or CM 3 to indicate communications ports 1 2 or...

Страница 41: ... and if subnetting is implemented Demand Settings The Demand menu accesses some of the setup registers in the factory configured Sliding Window Demand and Thermal Demand modules These registers control the timing of demand calculations The following setup registers and their current settings are displayed Setup Register module Factory Default Function Sub Intvl Sliding Window 900 The time in secon...

Страница 42: ...ng and transmitting data on the COM 1 port These LEDs are not a direct indication that the device is operational as communications may not occur until the device is fully configured These LEDs indicate communications activity on COM 1 only The XPRESS CARD indicates communications activity for the COM 2 and COM 3 ports using Rx and Tx LEDs located on either side of the COM 2 COM 3 captured wire con...

Страница 43: ... 32 5 0 7 5 167 7 21 1 6 6 783 MGT Mounting Holes and Panel Cutout Full SizeTemplate Use this diagram as a template for the MGT s cutout and mounting hole placement ...

Страница 44: ......

Страница 45: ... LXQP For More Information Visit WIE WMIQIRW GSQ EGGIWW Siemens Energy Automation Inc Siemens is a registered trademark of Siemens AG Specifications are subject to change without notice Windows is a trademark and Microsoft is a registered trademark of the Microsoft Corporation All others are of Siemens AG Order No XXIS 00101 0200 X XXXXXXXX Printed in the U S A ...

Отзывы: