21
PQ
SETUP
SWELL LIMIT
Specifies the magnitude above
which a power system input must
rise for a swell to be recorded
100 to 1000
106
SAG LIMIT
Specifies the magnitude below
which a power system input must
fall for a sag to be recorded
0 to 100
88
CHANGE
CRITERIA
Specifies the amount by which an
input must change during a
disturbance to be considered a new
sub-disturbance
0 to 100
10
NOMINAL
VOLTAGE
3
Specifies the nominal voltage of the
power system
0 to 1,000,000
0
EVENT PRIORITY Assigns a priority level to sag/swell
events
0 to 255
200
FO
RMA
T S
ETU
P
DIGIT GROUP
Specifies symbols used to delimit
thousands and decimal place
holder
1000.0 or 1,000.0 or 1000,0
1000.0
VOLTS DECIMAL Number of decimal places
displayed for voltages
1. to 123456789.XXX
1.XX
CURRNT
DECIMAL
Number of decimal places
displayed for currents
1. to 123456789.XXX
1.XXX
POWER DECIMAL Number of decimal places
displayed for power measurements 1. to 123456789.XXX
1.XXX
PHASE LABEL
Specifies how phases are labelled
ABC, RST, XYZ, RYB, RWB, 123
ABC
PF SYMBOL
LD (leading)/LG (lagging)
LD/LG, +/-, CAP/IND
LD/LG
DATE FORMAT
Specifies how dates are displayed
MM/DD/YYYY, DD/MM/YYYY,
YYYY/MM/DD
MM/DD/
YYYY
DISPLAY DST
Specifies whether or not DST is
displayed
Yes or No
Yes
DISPLA
Y
SETUP
UPDATE RATE
Sets when the display updates (in
seconds)
1 to 6
1
CONTRAST
Higher numbers are sharper
0 to 9
7
TIME SETUP
TZ OFFSET
Sets the time zone of the meter’s
location, relative to UTC
- 12:00 to +13:00
+00:00
DST OFFSET
Sets the daylight savings time offset
of the meter’s location
-3:00 to +3:00
+00:00
SYNC SOURCE
Sets the port to receive time
synchronization signals
Ethernet, COM1, COM2,
COM3, COM4
COM1
SYNC TYPE
Specifies whether time sync signals
are received in local time or UTC
Local Time or UTC
UTC
CLOCK SOURCE Specifies time sync source
Internal or COMM
Internal
LOCAL DATE
Sets the local date
Same format as specified in
Date Format setting
LOCAL TIME
Sets the local time
Menu
Setting
Description
Range (Values)
Default
Содержание 9510