20
COM
1
SET
U
P
PROTOCOL
The communications protocol
ION, Modbus RTU, Modbus
Master, DNP V3.00,
GPS:Truetime/Datum,GPS:
Arbiter, GPS:Arbiter-Vorne,
Factory, Ethergate, ModemGate
ION
BAUD RATE
The data rate, in bits per second
300
1
, 1200, 2400, 4800, 9600,
19200, 38400, 57600, 115200
9600
TRAN DELAY
The transmit delay in seconds
0 to 1
0.010
UNIT ID
Every meter on an RS-485 network
must have a unique Unit ID number 1 to 9999
From serial
number
2
MODE
Hardware mode for port
RS232 or RS485
RS232
FLOW CONTROL Specifies the handshake mode
when COM1 is set to RS232
RTS + DELAY or RTS/CTS
RTS +
DELAY
COM2 SETUP
PROTOCOL
The communications protocol
See COM1 protocol
ION
BAUD RATE
The data rate, in bits per second
300
1
, 1200, 2400, 4800, 9600,
19200, 38400, 57600, 115200
9600
TRAN DELAY
The transmit delay in seconds
0 to 1
0.010
UNIT ID
Every meter on an RS-485 network
must have a unique Unit ID number 1 to 9999
101
COM
3
S
ETUP
PROTOCOL
The communications protocol
ION, Modbus RTU, Modbus
Master, DNP V3.00,
GPS:Truetime/Datum,GPS:
Arbiter, GPS:Arbiter-Vorne,
Factory
ION
BAUD RATE
The data rate, in bits per second
300
1
, 1200, 2400, 4800, 9600,
19200, 38400, 57600, 115200
9600
TRAN DELAY
The transmit delay in seconds
0 to 1
0.010
UNIT ID
Every meter on an RS-485 network
must have a unique Unit ID number 1 to 9999
102
ANSWER HR
RINGS
The number of rings during defined
answer hours
0 to 255
1
NON-ANSWER
HR RINGS
The number of rings during defined
non-answer hours
0 to 255
5
COM4 SETUP
PROTOCOL
The communications protocol
ION, Modbus RTU, DNP V3.00,
Factory
ION
BAUD RATE
The data rate, in bits per second
1200, 2400, 4800, 9600,
19200
9600
TRAN DELAY
The transmit delay in seconds
0 to 1
0.010
UNIT ID
Every meter on an RS-485 network
must have a unique Unit ID number 1 to 9999
103
N
ETWORK SETUP
IP ADDRESS
Sets the IP address for the meter
000.000.000.000 to
999.999.999.999
none
SUBNET MASK
Used if subnetting applies to your
network
000.000.000.000 to
999.999.999.999
none
GATEWAY
Used in multiple network
configurations
000.000.000.000 to
999.999.999.999
none
DNS PRIMARY
Sets the address for the primary
DNS Server that is configured to
resolve domain names
000.000.000.000 to
999.999.999.999
none
DNS
SECONDARY
Sets the address for the secondary
DNS Server that is configured to
resolve domain names
000.000.000.000 to
999.999.999.999
none
Menu
Setting
Description
Range (Values)
Default
Содержание 9510