Operation
178/214
Revision 06 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • 864-5091.9
Indications VOIS, VOIS R+,
CAPDIS -S1+/-S2+
Fig. 210: CAPDIS-S2+: Cover closed
Fig. 211: CAPDIS-S2+: Cover opened
①
"Test" button
②
Cover
③
LC display
④
Duct for signaling cables CAPDIS-M
⑤
Test socket L2
⑥
Earth socket
⑦
Test socket L3
⑧
Test socket L1
⑨
Short instructions
Indicatio
n
VOIS+, VOIS R
+
CAPDIS-S1+
CAPDIS-S2+
L1
L2
L3
L1
L2
L3
L1
L2
L3
A0
Operating voltage not present (CAPDIS-S2+)
A1
Operating voltage present
A2
• Operating voltage not present
• Auxiliary power not present (CAPDIS-S2+)
A3
Failure in phase L1, operating voltage at L2 and
L3 (for CAPDIS-Sx+ also earth-fault indication)
A4
Voltage (
not
operating voltage) present
A5
Indication: "Test" passed (lights up shortly)
A6
Indication: "Test" not passed (lights up shortly)
A7
Overvoltage present (lights up permanently)
A8
Indication: "ERROR" e.g., in case of missing
auxiliary voltage