Auxiliary Voltage V
aux
– Alternating Voltage (AC)
Maximum inrush current at 230 V
≤ 22 A; after 250 μs: < 5 A
Power consumption
23 VA
Power-Supply Unit Output
Rated output voltage
2-pole terminal
Rated output current
Max. 600 mA
Behavior in case of short-circuit
Permanently short-circuit-proof
Power-failure backup
Min. 50 ms at rated load
Output-voltage status display
1 green RUN LED
Output voltage
DC 5 V; I
max
= 600 mA
Safety DIN EN 61010 Part 1
Overvoltage category
III
Degree of pollution
2
Fire-resistance rating as per UL 94
V0
Fuses
Soldered in place
2.0 A time delay
Replaceable
1.6 A time delay/AC 250 V/DC 300 V
Voltage Monitoring Relay
Relay
Standard relay, 1 break contact, isolated; 2-pole
terminal
Maximum contact voltage (resistive load)
AC 240 V
Maximum switching current
5 A
Maximum switching power
DC: 50 W at 300 V
DC: 270 W at 35 V
AC: 2000 VA
Permissible current for contacts
5 A
Technical Data
4.1 Device Data
Accessories, Wide-Range Power Supply Unit 24 V/5 V, Manual
23
C53000-G9050-C602-1, Edition 09.2019
Содержание 7XV5810-0.A00
Страница 8: ...8 Zubehör Weitbereichsnetzteile 24 V 5 V Handbuch C53000 G9050 C602 1 Ausgabe 09 2019 ...
Страница 20: ...20 Zubehör Weitbereichsnetzteile 24 V 5 V Handbuch C53000 G9050 C602 1 Ausgabe 09 2019 ...
Страница 30: ...30 Zubehör Weitbereichsnetzteile 24 V 5 V Handbuch C53000 G9050 C602 1 Ausgabe 09 2019 ...
Страница 36: ...6 Accessories Wide Range Power Supply Unit 24 V 5 V Manual C53000 G9050 C602 1 Edition 09 2019 ...
Страница 38: ...8 Accessories Wide Range Power Supply Unit 24 V 5 V Manual C53000 G9050 C602 1 Edition 09 2019 ...
Страница 50: ...20 Accessories Wide Range Power Supply Unit 24 V 5 V Manual C53000 G9050 C602 1 Edition 09 2019 ...
Страница 60: ...30 Accessories Wide Range Power Supply Unit 24 V 5 V Manual C53000 G9050 C602 1 Edition 09 2019 ...