22
SICAM AI Unit 7XV5674, Product Information
E50417-B1150-C492-A1, Edition 09.2012
11 Interfaces
Figure 11-1 Terminals on the Terminal Side
The conductor cross-section for the supply voltage
terminal (H) amounts to:
1.5 mm² (AWG 16) to 2.5 mm² (AWG 14) without
bootlace ferrule
1.5 mm² (AWG 16) with bootlace ferrule
Tightening torque
0.4 Nm to 0.5 Nm
(3.5 in-lb to 4.5 in-lb)
SICAM AI Unit with DC Inputs
and RS485 Interface
(D-sub Socket)
SICAM AI Unit with DC Inputs
and Optical Interface
(
ST connector)
NOTE
The device is provided with Phoenix FMC 1.5/ 9-ST-
3.81 plug connector for the (T) and (Q) connections.