04.05
3 - Description
Siemens AG 7VV3003-8TA74
ENGLISH 13
SICROWBAR 7VV3003 DC-Surge Suppressor Operating Instructions
Order No.
7VV3003-
5JG32
5KG32
5LG32
5MG32
Igniting voltage
V
1600
±
100 2200
±
150 2600
±
150 3000
±
150
Maximum power pulse current
kA
10.5
10.5
10.5
10.5
Critical voltage gradient
V/µs
1000
1000
1000
1000
Critical current gradient
A/µs
300
300
300
300
I2t value
A
2
s
239 * 10
6
239 * 10
6
239 * 10
6
239 * 10
6
Dimensions (HxWxD)
(Dimension diagram see
Section 4)
mm 350x265x285
350x265x285 350x265x285 350x265x285
Weight
(approx.)
kg
20 20 20 20
Typical load current path for the three device power ranges
I(t)
0
2000
4000
6000
8000
10000
12000
0
5
10
15
20
25
30
t[s]
I[A]
T3801N
T2001N
T901N
10s
10% Imax
(1)
(2)
(3)
(1) 7VV3003-5AG32
-5BG32
-5CG32
-5DG32
(2) 7VV3003-5EG32
-5FG32
-5GG32
-5HG32
(3) 7VV3003-5JG32
-5KG32
-5LG32
-5MG32
here:
τ
=4.34s
Fig. 1
Re-make time (recovery time)
30min
30min
30min
t
*
*
*
A single trip is possible after a waiting time of
30 min.
300min
300min
t
* *
* *
After two trips within 30 min., a recovery time of
300 min. must be observed.
*
= SICROWBAR 7VV3003 DC surge suppressor trip
Fig. 2
Содержание 7VV3003-5AG32