![Siemens 7SR18 Solkor Скачать руководство пользователя страница 136](http://html.mh-extra.com/html/siemens/7sr18-solkor/7sr18-solkor_manual_383100136.webp)
7SR18 Performance Specification
Unrestricted ©2018 Siemens Protection Devices Limited
Page
19 of
2.2 46 Negative Phase Sequence Overcurrent
2.2.1 Reference
(46DT)
Parameter
Value
I
s
Setting
0.05, 0.06... 4.0
xIn
t
d
Delay setting
0.00, 0.01…20.00, 20.10… 100, 101… 1000, 1010…
10000, 10100… 14400 s
2.2.2
Operate and Reset Level (46DT)
Attribute
Value
I
op
Operate level
100 %
Is
,
±
5 % or
±
1%
In
Reset level
≥
95 %
I
op
Repeatability
±
1 %
Transient overreach
(X/R
≤
100)
≤
-5 %
Variation
-10 °C to +55 °C
≤
5 %
f
nom
± 5 %
≤
5 %
2.2.3
Operate and Reset Time (46DT)
Attribute
Value
t
basic
Element basic operate time
Switched from 0 to 2 x
Is
: 40 ms,
±
10 ms
Switched from 0 to 5 xI
s
: 30 ms,
±
10 ms
t
op
Operate time following delay
t
basic
+
t
d
,
±
1 % or
±
10 ms
Repeatability
±
1 % or
±
10 ms
Overshoot time
<40 ms
Disengaging time
< 60 ms
2.2.4 Reference
(46IT)
Parameter
Value
char
Characteristic setting
IEC-NI, -VI, -EI, -LTI; ANSI-MI, -VI, -EI; DTL
Tm
Time Multiplier setting
0.025, 0.05… 1.6, 1.7… 5, 6… 100
I
s
Setting
0.05, 0.06… 2.5
xIn
I
Applied Current (for operate time) IDMTL 2 to 20 x Is
t
d
Delay setting
0, 0.01… 20 s
t
res
Reset setting
ANSI DECAYING, 0, 1… 60 s
2.2.5
Operate and Reset Level (46IT)
Attribute
Value
I
op
Operate level
105 %
Is
,
±
4 % or
±
1%
In
Reset level
≥
95 %
I
op
Repeatability
±
1 %
Variation
-10 °C to +55 °C
≤
5 %
f
nom
± 5 %
≤
5 %
Содержание 7SR18 Solkor
Страница 1: ...Energy Management 7SR18 Solkor Line Differential Relay Reyrolle Protection Devices ...
Страница 2: ...Siemens Protection Devices Limited 2 ...
Страница 93: ...7SR18 Configuration Guide Unrestricted Page 12 of 12 2015 Siemens Protection Devices Limited ...
Страница 161: ...7SR18 Performance Specification Unrestricted Page 44 of 44 2018 Siemens Protection Devices Limited ...
Страница 179: ...7SR18 Solkor Settings Guide Unrestricted Page 4 of 44 2016 Siemens Protection Devices Limited Typical Menu Structure ...
Страница 221: ...7SR181 Solkor Technical Manual Chapter 4 Page 2 of 80 2016 Siemens Protection Devices Limited ...
Страница 225: ...7SR181 Solkor Technical Manual Chapter 4 Page 6 of 80 2016 Siemens Protection Devices Limited ...
Страница 289: ...7SR181 Solkor Technical Manual Chapter 4 Page 70 of 80 2016 Siemens Protection Devices Limited ...
Страница 291: ...7SR181 Solkor Technical Manual Chapter 4 Page 72 of 80 2016 Siemens Protection Devices Limited ...
Страница 293: ...7SR181 Solkor Technical Manual Chapter 4 Page 74 of 80 2016 Siemens Protection Devices Limited ...
Страница 353: ...7SR18 Commissioning Maintenance Guide Unrestricted Page 54 of 54 2018 Siemens Protection Devices Limited ...