7SR18 Performance Specification
Unrestricted ©2018 Siemens Protection Devices Limited
Page
7 of 44
1.2.1.2 Operational Features
Attribute
Value
Comments
0 % Dip Withstand Period
50 ms
Dip Immunity Acquisition Period
5 minutes
Typical time after switch on to
attain claimed immunity to dips
NOTE: Dips in supply that fall below the minimum voltage for a period greater than the
0 % Dip With stand Period will invoke a relay reset.
During conditions of auxiliary input voltage variations which are not described
(1)
in section 1.6.3.1, the relay
may enter a safety protection mode where a power supply shutdown occurs. This condition is designed to
protect the power supply from damage as well as prevent internal relay faults from developing into dangerous
situations. Once the relay has entered this safety mode, it may be necessary to reduce the auxiliary input
voltage to zero volts for up to 30 seconds before re-application of the auxiliary supply will cause the relay to
power up and operate normally.
(1) Using fuses as on/off switches or allowing batteries to run at very low cell voltages for extended periods and
then attempting to re-charge them, are examples of such auxiliary supply conditions.
1.2.2 AC Analogue Current
Nominal
Measuring Range
In
1 A & 5 A Phase and Earth
80 x
In
fn
50 Hz or 60 Hz
47.5 Hz to 52.5 Hz and 57 Hz to 63 Hz
Note. 1 A and 5 A nominal inputs are user selectable on each model.
1.2.2.1 Burden
1.2.2.2 Thermal Withstand
Overload Period
Overload Current
Phase and Earth
1 A
5 A
Continuous (1 hour)
4.0
xIn
3 minutes
5.0
xIn
2 minutes
6.0
xIn
3 seconds
57.7 A
202 A
2 seconds
70.7 A
247 A
1 second
100 A
350 A
1 cycle
700 A
2500 A
1.2.3 AC Analogue Voltage
Attribute Nominal
Operating Range
Vn
40 to 160 Vrms
0 to 200 Vrms
fn
50, 60Hz
47.5 to 52.5Hz and 57 to 63Hz
Attribute
Value – Phase and Earth
1 A
5 A
AC Burden
≤
0.1 VA
≤
0.3 VA
Input Impedance (typical)
0.05
Ω
0.01
Ω
Содержание 7SR18 Solkor
Страница 1: ...Energy Management 7SR18 Solkor Line Differential Relay Reyrolle Protection Devices ...
Страница 2: ...Siemens Protection Devices Limited 2 ...
Страница 93: ...7SR18 Configuration Guide Unrestricted Page 12 of 12 2015 Siemens Protection Devices Limited ...
Страница 161: ...7SR18 Performance Specification Unrestricted Page 44 of 44 2018 Siemens Protection Devices Limited ...
Страница 179: ...7SR18 Solkor Settings Guide Unrestricted Page 4 of 44 2016 Siemens Protection Devices Limited Typical Menu Structure ...
Страница 221: ...7SR181 Solkor Technical Manual Chapter 4 Page 2 of 80 2016 Siemens Protection Devices Limited ...
Страница 225: ...7SR181 Solkor Technical Manual Chapter 4 Page 6 of 80 2016 Siemens Protection Devices Limited ...
Страница 289: ...7SR181 Solkor Technical Manual Chapter 4 Page 70 of 80 2016 Siemens Protection Devices Limited ...
Страница 291: ...7SR181 Solkor Technical Manual Chapter 4 Page 72 of 80 2016 Siemens Protection Devices Limited ...
Страница 293: ...7SR181 Solkor Technical Manual Chapter 4 Page 74 of 80 2016 Siemens Protection Devices Limited ...
Страница 353: ...7SR18 Commissioning Maintenance Guide Unrestricted Page 54 of 54 2018 Siemens Protection Devices Limited ...