$SSHQGL[
6-
9
&*&
1216 RMS FORMAT
RMS format for inverse time O/C protection
FUNDAMENTAL
[ ] Fundamental
TRUE RMS
[ ] True rms
1221 MAN.CLOSE
Manual close
I>> UNDELAYED
[ ] I>> undelayed
I>/Ip UNDELAYED [ ] I>/Ip undelayed
INEFFECTIVE
[ ] Ineffective
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
1500 O/C PROT. EARTH
1501 O/C EARTH
O/C protection for earth faults
ON
[ ] on
OFF
[ ] off
1502 IE>>
Pick-up value of the high-set stage IE>>
min. 0.05
I/In
max. 25.00
©©©©
1503 T-IE>>
Trip time delay of the high-set stage IE>>
min. 0.00
s
max. 60.00/Ñ
©©©©
1506 MEAS.REPET
Measurement repetition
NO
[ ] no
YES
[ ] yes
1511 CHARACTER.
Characteristic of the O/C stage IEp
NORMAL INVERSE
[ ] Normal inverse
VERY INVERSE
[ ] Very inverse
EXTREMELY INVERS [ ] Extremely inverse
USER CHARACTER. [ ] User characteristics
1512 IE>
Pick-up value of the overcurrent stage IE>
min. 0.05
I/In
max. 25.00
©©©©
1513 T-IE>
Trip time delay of the overcurrent stage IE>
min. 0.00
s
max. 60.00/Ñ
©©©©
1514 IEp
Pick-up value inverse time O/C stage IEp
min. 0.10
I/In
max. 4.00
©©©©
1515 T-IEp
Trip time delay inverse time O/C stage IEp
min. 0.00
s
max. 10.00/Ñ
©©©©
1516 RMS FORMAT
RMS format for inverse time O/C protection
FUNDAMENTAL
[ ] Fundamental
TRUE RMS
[ ] True rms
1521 MAN.CLOSE
Manual close
IE>> UNDELAYED
[ ] IE>> undelayed
IE>/IEp UNDELAY. [ ] IE>/IEp undelayed
INEFFECTIVE
[ ] Ineffective