3. Set a Modbus address
②
[MODBUS ADDRESS SELECTOR] for each SITRANS MX300.
Assign each Modbus address only once.
Gaps may exist. Example: 2, 5 and 7.
In the figure, Modbus address 2 is set.
4
3
2
1
Modbus address
Disabled
Disabled
Disabled
Disabled
1
Disabled
Disabled
Disabled
Enabled
[ENABLED]
2
Disabled
Disabled
Enabled
[ENABLED]
Disabled
3
Disabled
Disabled
Enabled
[ENABLED]
Enabled
[ENABLED]
4
Disabled
Enabled
[ENABLED]
Disabled
Disabled
5
Disabled
Enabled
[ENABLED]
Disabled
Enabled
[ENABLED]
6
Disabled
Enabled
[ENABLED]
Enabled
[ENABLED]
Disabled
7
Disabled
Enabled
[ENABLED]
Enabled
[ENABLED]
Enabled
[ENABLED]
8
Figure 5-1
In the figure, the Modbus address 2 is set
4. Connect all T-plugs together.
5. Plug the T-plug row onto the DIN rail.
Installing/mounting
5.6 Installing SITRANS MX300 on DIN rail