5.5
Connecting cabinets
DANGER
Danger due to failure of the protective and monitoring equipment
The converter must be grounded to ensure that it operates safely and reliably. If the converter
is operated with insufficient grounding, then the protection and monitoring functions can fail.
Death, serious injury, or material damage will result.
● Always apply all of the necessary protective measures.
● Always observe the five safety rules when working with the converter.
● Follow these steps when grounding the machine:
– Establish the connections in a cabinet.
– Ensure that the connections are also established over several cabinets.
– Establish the ground connection for the whole plant immediately.
If several cabinets are set up as one unit, the grounding connections of the individual cabinets
must be connected with each other. A grounding lug connection cable is supplied with each
cabinet. To connect the ground connections for several cabinets, proceed as follows:
1. Insert the grounding cable
①
through the side panel of the cabinet.
Figure 5-2
Connecting the grounding for the cabinet units
2. Secure the grounding cable on the grounding lug
②
with an M12 screw.
3. Tighten the screw with a torque of 50 Nm.
5.5.1
Connecting the interface cable
Connecting the interface terminals of several cabinets
If the power section comprises several transport units, connect the cabinet interfaces with one
another.
The interface cable is located at the bottom section of the cabinet.
Assembly
5.5 Connecting cabinets
SINAMICS PERFECT HARMONY GH150 6SL3825
Operating Instructions 05/2020
65
Содержание 6SL3825
Страница 2: ...19 06 2020 09 58 V14 00 ...
Страница 12: ...Table of contents SINAMICS PERFECT HARMONY GH150 6SL3825 12 Operating Instructions 05 2020 ...
Страница 128: ...Maintenance 9 7 Repair SINAMICS PERFECT HARMONY GH150 6SL3825 128 Operating Instructions 05 2020 ...
Страница 130: ...Spare parts SINAMICS PERFECT HARMONY GH150 6SL3825 130 Operating Instructions 05 2020 ...
Страница 134: ...Service Support SINAMICS PERFECT HARMONY GH150 6SL3825 134 Operating Instructions 05 2020 ...
Страница 140: ...Quality documents SINAMICS PERFECT HARMONY GH150 6SL3825 140 Operating Instructions 05 2020 ...
Страница 142: ...Additional documents SINAMICS PERFECT HARMONY GH150 6SL3825 142 Operating Instructions 05 2020 ...
Страница 145: ......
Страница 146: ...Further Information www siemens com LDA Siemens AG Large Drives Applications Vogelweiherstr 1 15 90441 NÜRNBERG GERMANY ...