background image

 

 

BusAdapter 

34

 

Equipment Manual, 08/2020, A5E41449003-AB 

 

BusAdapter BA 2xLC 

7.1

 

Product overview 

Article number 

6ES7193-6AG00-0AA0 

View 

 

Figure 7-1 

BusAdapter BA 2xLC 

Properties 

 

You connect PROFINET IO fiber-optic cables to the PROFINET device via the BusAdapter 

BA 2×LC. To do this, screw the BusAdapter BA 2×LC to the PROFINET device and insert the 

PROFINET connection cable. 

 

You loop through the PROFINET via the integrated 2-port switch. 

Содержание 6ES7 193-6AP40-0AA0

Страница 1: ......

Страница 2: ...uct overview 3 BusAdapter BA 2xRJ45 4 BusAdapter BA 2xFC 5 BusAdapter BA 2xSCRJ 6 BusAdapter BA 2xLC 7 BusAdapter BA 2xM12 8 BusAdapter BA SCRJ RJ45 9 BusAdapter BA SCRJ FC 10 BusAdapter BA LC RJ45 11 BusAdapter BA LC FC 12 Strain relief 13 Dimension drawings A Accessories B Compatibility C ...

Страница 3: ...ly by personnel qualified for the specific task in accordance with the relevant documentation in particular its warning notices and safety instructions Qualified personnel are those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper use of Siemens products Note the following WARNING Siemens prod...

Страница 4: ...hnical specifications 19 5 BusAdapter BA 2xFC 20 5 1 Product overview 20 5 2 Connecting 21 5 3 Diagnostics 25 5 4 Technical specifications 26 6 BusAdapter BA 2xSCRJ 27 6 1 Product overview 27 6 2 Connecting 28 6 3 Diagnostics 31 6 4 Technical specifications 33 7 BusAdapter BA 2xLC 34 7 1 Product overview 34 7 2 Connecting 35 7 3 Diagnostics 39 7 4 Technical specifications 40 8 BusAdapter BA 2xM12 ...

Страница 5: ...chnical specifications 60 11 BusAdapter BA LC RJ45 61 11 1 Product overview 61 11 2 Connecting 62 11 3 Diagnostics 64 11 4 Technical specifications 65 12 BusAdapter BA LC FC 66 12 1 Product overview 66 12 2 Connecting 67 12 3 Diagnostics 69 12 4 Technical specifications 70 13 Strain relief 71 13 1 Product overview 71 13 2 Installing 72 A Dimension drawings 74 A 1 BusAdapter dimension drawings 74 A...

Страница 6: ...ons Ambient temperature in horizontal and vertical mounting position extended to min 30 C Conventions CPU When the term CPU is used in this manual it applies to the CPUs of the S7 1500 automation system as well as to the CPUs interface modules of the distributed I O system ET 200SP STEP 7 In this documentation STEP 7 is used as a synonym for all versions of the configuration and programming softwa...

Страница 7: ...nuous development to make them more secure Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used Use of product versions that are no longer supported and failure to apply the latest updates may increase customers exposure to cyber threats To stay informed about product updates subscribe to the Siemens Industrial Sec...

Страница 8: ...Mall The Industry Mall is the catalog and order system of Siemens AG for automation and drive solutions on the basis of Totally Integrated Automation TIA and Totally Integrated Power TIP You can find catalogs for all automation and drive products on the Internet https mall industry siemens com ...

Страница 9: ...the most of your Industry Online Support In mySupport you can store filters favorites and tags request CAx data and put together your personal library in the Documentation area Furthermore your data is automatically filled into support requests and you always have an overview of your current requests You must register once to use the full functionality of mySupport You can find mySupport on the In...

Страница 10: ...n can be found on the Internet under Application examples https support industry siemens com sc ww de sc 2054 SIMATIC Automation Tool You can use the SIMATIC Automation Tool to perform commissioning and maintenance activities simultaneously on various SIMATIC S7 stations as a bulk operation independent of the TIA Portal The SIMATIC Automation Tool provides a multitude of functions Scanning of a PR...

Страница 11: ...ng commissioning PRONETA features two core functions The topology overview independently scans PROFINET and all connected components PRONETA also scans configuration of the station name IP subnet mask and identification and maintenance data I M1 3 For more information refer to SIEMENS PRONETA https support industry siemens com cs ww de view 67460624 ...

Страница 12: ...er can be used for example for ET 200SP interface module and central processing unit CPU and Open Controller PN PN Coupler Switches Overview The SIMATIC BusAdapters can be ordered in the following versions BusAdapter Article number Property Figure BA 2xRJ45 6ES7193 6AR00 0AA0 PROFINET BusAdapter with standard Ethernet socket for standard RJ45 connector BA 2xFC 6ES7193 6AF00 0AA0 PROFINET BusAdapte...

Страница 13: ...etween two stations BA 2xLC 6ES7193 6AG00 0AA0 PROFINET BusAdapter with glass fiber optic cable connec tion for LC connector for appli cations with increased EMC and vibration shock load as well as electrical potential differences between two stations BA 2xM12 6ES7193 6AM00 0AA0 PROFINET BusAdapter with standard M12 connector D coded or as a pluggable push pull version with increased mechanical lo...

Страница 14: ...er PROFINET BusAdapter with POF PCF fiber optic cable direct connection of bus cable BA LC RJ45 6ES7193 6AG20 0AA0 Media converter PROFINET BusAdapter with glass fiber optic cable standard RJ45 connector BA LC FC 6ES7193 6AG40 0AA0 Media converter PROFINET BusAdapter with glass fiber optic cable direct connection of bus cable See also Strain relief Page 71 ...

Страница 15: ...00 0AA0 View Figure 4 1 BusAdapter BA 2 RJ45 Properties You connect PROFINET IO cable with RJ45 connector to the PROFINET device via the BusAdapter BA 2 RJ45 To do this screw the BusAdapter BA 2 RJ45 to the PROFINET device and insert the PROFINET connecting cable You loop through the PROFINET via the integrated 2 port switch ...

Страница 16: ...able 6XV1840 2A IE FC TP trailing cable 6XV1840 3AH10 IE FC TP Marine Cable 6XV1840 4AH10 IE FC TP robust cable 6XV1841 2 IE TP torsion cable 6XV1870 2F Please observe the specifications in the PROFINET Installation Guide https www profibus com Pin assignment The following table shows the signal name and description of the pin assignment of the BusAdapter BA 2 RJ45 Table 4 1 PROFINET IO pin assign...

Страница 17: ...usAdapter BA 2xRJ45 follow these steps 1 Plug the BusAdapter BA 2 RJ45 into the PROFINET device 2 Screw the BusAdapter BA 2 RJ45 to the PROFINET device 1 screw with 0 25 Nm tightening torque 3 Plug the RJ45 bus connector into the PROFINET port on the BusAdapter BA 2 RJ45 You can also swap steps 2 and 3 BusAdapter BA 2 RJ45 installed CPU BusAdapter BA 2 RJ45 PROFINET connecting cable Interface modu...

Страница 18: ...PROFINET IO interfaces Ensure that all devices are connected to the SELV PELV power supply or equivalent Only then are you permitted to operate the modules with PROFINET IO interfaces in LAN networks Local Area Networks A data transfer point that guarantees this degree of safety is prescribed for connection to the WAN Wide Area Network ...

Страница 19: ...atus and error displays LED Meaning Remedy LK1 LK2 off There is no Ethernet connection between the PROFINET IO interface of your PROFINET device and a communication partner e g IO controller Check whether the bus cable to the switch or IO con troller is disconnected on There is an Ethernet connection between the PROFINET IO interface of your PROFINET device and a communication partner e g IO contr...

Страница 20: ...A0 General information Product type designation BA 2x RJ45 Interfaces Number of PROFINET interfaces 1 Supports protocol for PROFINET IO Number of RJ45 ports 2 Number of SCRJ ports 0 Number of LC ports 0 Cable length Cu conductors 100 m Ambient conditions Ambient temperature during operation horizontal installation min 30 C horizontal installation max 60 C vertical installation min 30 C vertical in...

Страница 21: ... Figure 5 1 BusAdapter BA 2xFC Properties You connect PROFINET IO cable with FastConnect connection method to the PROFINET device via the BusAdapter BA 2xFC To do this screw the BusAdapter BA 2xFC with the connected PROFINET connection cable in place on the PROFINET device You loop through the PROFINET via the integrated 2 port switch ...

Страница 22: ...rnet Fast Connect Stripping Tool 6GK1901 1GA00 with green knife cassette 6GK1901 1B This guarantees fast and safe stripping Fast Connect Cable recommended types IE FC TP Standard Cable GP 2x2 6XV1840 2AH10 IE FC TP Trailing Cable 2x2 6XV1840 3AH10 IE FC TP Marine Cable 6XV1840 4AH10 IE FC TP Flexible Cable GP 2x2 6XV1870 2B IE FC TP Trailing Cable 2x2 6XV1870 2D IE TP Torsion Cable 2x2 6XV1870 2F ...

Страница 23: ...sAdapter BA 2xFC to the interface module https support industry siemens com cs ww de view 95886218 To connect PROFINET IO to the PROFINET device via the BusAdapter BA 2xFC follow these steps 1 Strip insulation from the sheath of the PROFINET connecting cable as follows Figure 5 2 PROFINET connecting cable 2 Pull back the locking slide and fold up the cover of the connection element 3 Pull up the w...

Страница 24: ...h the locking slide forwards as far as it will go 6 Screw the BusAdapter BA 2 FC to the PROFINET device 1 screw with 0 25 Nm tightening torque To do this use a screwdriver with a 3 to 3 5 mm blade alternatively TX10 Locking slide Shield contact Wire guide PROFINET connecting cable Figure 5 3 Connection of the PROFINET IO BusAdapter BA 2 FC ...

Страница 25: ... an ET 200SP CPU interface module as an example Note Installation guidelines for modules with PROFINET IO interfaces Ensure that all devices are connected to the SELV PELV power supply or equivalent Only then are you permitted to operate the modules with PROFINET IO interfaces in LAN networks Local Area Networks A data transfer point that guarantees this degree of safety is prescribed for connecti...

Страница 26: ...s and error displays LED Meaning Remedy LK1 LK2 off There is no Ethernet connection between the PROFINET IO interface of your PROFINET device and a communication partner e g IO controller Check whether the bus cable to the switch or IO controller is dis connected on There is no Ethernet connection between the PROFINET IO interface of your PROFINET device and a communication partner e g IO controll...

Страница 27: ...ROFINET interfaces 1 Supports protocol for PROFINET IO Number of FC FastConnect connections 2 Cable length Cu conductors 100 m Ambient conditions Ambient temperature during operation horizontal installation min 30 C horizontal installation max 60 C vertical installation min 30 C vertical installation max 50 C Altitude during operation relating to sea level Installation altitude above sea level max...

Страница 28: ...ter BA 2xSCRJ Properties Using BusAdapter BA 2 SCRJ you connect PROFINET IO to the PROFINET device optically with fiber optic cables via an SCRJ connector To do this screw the BusAdapter BA 2 SCRJ to the PROFINET device and plug in the SCRJ connector You loop through the PROFINET via the integrated 2 port switch SCRJ connector is suitable for POF and PCF ...

Страница 29: ...E SCRJ POF Plug or IE SC RJ PCF Plug You will find more Instructions in the installation instructions POF fiber optic cables with IE SCRJ POF plugs A5E00351141 PCF fiber optic cables with IE SCRJ PCF plugs A5E00835119 When installing the fiber optic cable make sure the bending radius is not less than permitted IE POF PCF standard cable 150 mm IE POF PCF trailing cable 60 mm The maximum lengths of ...

Страница 30: ...e PROFINET device 1 screw with 0 25 Nm tightening torque To do this use a screwdriver with a 3 to 3 5 mm blade alternatively TX10 3 Remove the blanking plugs from the PROFINET sockets 4 Hold the prepared connector by the housing Insert it into the PROFINET socket on the BusAdapter BA 2xLC until you hear it click into place The coding of the connectors ensures a safe connection CAUTION Risk of dama...

Страница 31: ...T 200SP interface module as an example Reusing used fiber optic cables Note Shorten both fiber optic cores by the amount of the curved lengths and reassemble the connectors This will prevent any attenuation losses caused by re bent heavily stressed portions of the fiber optic cores Reference For more information on the installation guidelines for fiber optic cables refer to the SIMATIC NET PROFIBU...

Страница 32: ...stics BusAdapter Equipment Manual 08 2020 A5E41449003 AB 31 6 3 Diagnostics LEDs The figure below shows the LED display on the BusAdapter BA 2xSCRJ LK1 green MT1 yellow LK2 green MT2 yellow Figure 6 3 LEDs on the BusAdapter BA 2xSCRJ ...

Страница 33: ...nnection be tween the PROFINET IO interface of your PROFINET device and a commu nication partner e g IO controller flashes Not relevant The Node flash test is running The RN ER MT LEDs are also flashing Not relevant off No error Not relevant on Fiber optic error Maintenance demanded attenua tion through the fiber optic cable is already so high that operation will soon no longer be possible Causes ...

Страница 34: ...uct type designation BA 2xSCRJ HW functional status from FS04 Interfaces Number of PROFINET interfaces 1 2 ports switch SCRJ FO Supports protocol for PROFINET IO Number of SCRJ ports 2 Number of LC ports 0 Cable length PCF 100 m Plastic FOC POF 50 m PCF GI 250 m Ambient conditions Ambient temperature during operation horizontal installation min 25 C horizontal installation max 60 C vertical instal...

Страница 35: ...3 6AG00 0AA0 View Figure 7 1 BusAdapter BA 2xLC Properties You connect PROFINET IO fiber optic cables to the PROFINET device via the BusAdapter BA 2 LC To do this screw the BusAdapter BA 2 LC to the PROFINET device and insert the PROFINET connection cable You loop through the PROFINET via the integrated 2 port switch ...

Страница 36: ... FO LC plug we recommend the FC FO Termination Kit LC 6GK1900 0RL00 0AA0 You can cleave the glass fiber precisely using the FC FO Termination Kit LC CAUTION Cleaving the glass fiber Wear protective glasses during the cleaving process Dispose of the remaining fibers in a suitable waste container Connector for PROFINET fiber optic cable connection IE FC FO LC Plug 10 duplex plugs 6GK1900 1RB00 2AB0 ...

Страница 37: ...ring IE FC FO Cable with the plug in connector IE FC FO LC Plug A5E36312721 When installing the fiber optic cable make sure the bending radius is not less than permitted IE FC FO Standard Cable GP 62 5 200 230 70 mm IE FC FO Trailing Cable 62 5 200 230 6XV1847 2C 88 mm The maximum lengths of the fiber optic cables are as follows IE FC FO Standard Cable GP 62 5 200 230 2 km IE FC FO Trailing Cable ...

Страница 38: ...screw with 0 25 Nm tightening torque To do this use a screwdriver with a 3 to 3 5 mm blade alternatively TX10 3 Remove the blanking plugs from the PROFINET sockets 4 Hold the prepared connector by the housing Insert it into the PROFINET socket on the BusAdapter BA 2xLC until you hear it click into place The coding of the connectors ensures a safe connection CAUTION Risk of damage to eyes Do not lo...

Страница 39: ...erface module Reusing used fiber optic cables Note Shorten both fiber optic cores by the amount of the curved lengths and reassemble the connectors This will prevent any attenuation losses caused by re bent heavily stressed portions of the fiber optic cores Reference For more information on the installation guidelines for fiber optic cables refer to the SIMATIC NET PROFIBUS Network Manual https su...

Страница 40: ...s and error displays LED Meaning Remedy LK1 LK2 off There is no Ethernet connection between the PROFINET IO interface of your PROFINET device and a communication partner e g IO controller Check whether the bus cable to the switch or IO controller is dis connected on There is no Ethernet connection between the PROFINET IO interface of your PROFINET device and a communication partner e g IO controll...

Страница 41: ...Interfaces Number of PROFINET interfaces 1 2 ports switch LC Multimode Glass Fibre Supports protocol for PROFINET IO Number of SCRJ ports 0 Number of LC ports 2 Wavelength of 1 270 1 380 nm corresponds to 100BASE FX Cable length Multimode graded index fiber 50 125 µm 3 km Multimode graded index fiber 62 5 125 μm 3 km Ambient conditions Ambient temperature during operation horizontal installation m...

Страница 42: ...ush pull sockets according to IEC 61076 2 012 Connection option of the PROFINET line using two connector versions Pluggable push pull version see the section Accessories required Standard M12 connector D coded with screw type terminal Increased mechanical load capacity High immunity against electromagnetic interference You loop through the PROFINET via the integrated 2 port switch ...

Страница 43: ...sing the push pull plug for the PROFINET connection Tools required 3 to 3 5 mm screwdriver alternatively TX10 torx Accessories required Push pull version Unlatching straps 6ES7193 6DL00 2AA0 M12 connecting cables with push pull connection system M12 connecting cable 0 5 m 6XV1 871 8AE50 M12 connecting cable 1 0 m 6XV1 871 8AH10 M12 connecting cable 1 5 m 6XV1 871 8AH15 M12 connecting cable 2 0 m 6...

Страница 44: ...M 6XV1870 8A N10 IE Connecting Cable M12 180 M12 180 15M 6XV1870 8A N15 Siemens pre assembled connector cable M12 D coded without push pull up to a maximum length of 100 m Currently only available as a custom made solution Mr Hertlein Tel 49 172 3172810 juergen hertlein siemens com is the main contact person for passive components that are not available as standard equipment in the catalog He impl...

Страница 45: ...t on the BusAdapter BA 2 M12 Tightening torque for the M12 screw connector is 0 4 0 5 Nm Procedure for push pull connectors Insert the connector axially into the socket till the connection clicks into place You can detach the connector with an axial pull on the outer unlocking sleeve To do so you need to first disassemble the BusAdapter Note Simple unlocking of the push pull connector without prev...

Страница 46: ...usAdapter BA 2xM12 to the interface module Note Installation guidelines for modules with PROFINET IO interfaces Ensure that all devices are connected to the SELV PELV power supply or equivalent Only then are you permitted to operate the modules with PROFINET IO interfaces in LAN networks Local Area Networks A data transfer point that guarantees this degree of safety is prescribed for connection to...

Страница 47: ...sier removal of push pull connectors fit the unlatching straps 6ES7193 6DL00 2AA0 under development Unlatching straps Strain relief Figure 8 3 Using accessories Compatibility of the M12 sockets used The M12 sockets used conform to IEC 61076 2 012 and can thus be used with the M12 push pull connectors as well as with conventional D coded M12 connectors with screwed connections ...

Страница 48: ...tatus and error displays LED Meaning Remedy LK1 LK2 off There is no Ethernet connection between the PROFINET IO interface of your PROFINET device and a com munication partner e g IO control ler Check whether the bus cable to the switch or IO controller is disconnected on There is an Ethernet connection between the PROFINET IO interface of your PROFINET device and a com munication partner e g IO co...

Страница 49: ...eral information Product type designation SIMATIC BusAdapter BA 2x M12 Interfaces Number of PROFINET interfaces 1 Supports protocol for PROFINET IO Number of M12 ports 2 Cable length Cu conductors 100 m Ambient conditions Ambient temperature during operation horizontal installation min 30 C No condensation horizontal installation max 60 C vertical installation min 30 C No condensation vertical ins...

Страница 50: ...ia the BusAdapter BA SCRJ RJ45 Optically with fiber optic cables FOC with an SCRJ connector to port 1 Electrically with a standard RJ45 connector to port 2 To do this screw the BusAdapter BA SCRJ RJ45 to the PROFINET device and plug in the SCRJ connector or the RJ45 connector You can loop through PROFINET IO via the integrated 2 port switch You can use any port of the BusAdapter for feeding or for...

Страница 51: ...2 SCRJ Page 28 Connecting the RJ45 connector You can find more information about the required tools accessories and procedures in the section Connecting BusAdapter BA 2 RJ45 Page 15 Pin assignment The following table shows the signal names and description of the pin assignment for the BusAdapter BA SCRJ RJ45 Table 9 1 PROFINET IO pin assignment with BusAdapter BA SCRJ RJ45 View Signal name Descrip...

Страница 52: ...pter BA SCRJ RJ45 to the interface module Note Installation guidelines for modules with PROFINET IO interfaces Ensure that all devices are connected to the SELV PELV power supply or equivalent Only then are you permitted to operate the modules with PROFINET IO interfaces in LAN networks Local Area Networks A data transfer point that guarantees this degree of safety is prescribed for connection to ...

Страница 53: ...and error displays LED Meaning Remedy LK1 LK2 MT off Not relevant There is no Ethernet connection be tween the PROFINET IO interface of your PROFINET device and a commu nication partner e g IO controller Check whether the bus cable to the switch or IO controller is disconnected on Not relevant There is an Ethernet connection be tween the PROFINET IO interface of your PROFINET device and a commu ni...

Страница 54: ...manded attenua tion through the fiber optic cable is already so high that operation will soon no longer be possible Causes and measures for the transmission route Replace the fiber optic cable if damaged or aged Ensure correct installation of the PROFINET plugs or PROFINET connectors Adhere to maximum length of 50 m for POF cable or 100 m for PCF cable Ensure that the FOC connectors fit secure ly ...

Страница 55: ...type designation BA SCRJ RJ45 HW functional status from FS04 Interfaces Number of PROFINET interfaces 1 2 ports SCRJ RJ45 Supports protocol for PROFINET IO Number of RJ45 ports 1 Number of SCRJ ports 1 Number of LC ports 0 Cable length PCF 100 m Plastic FOC POF 50 m PCF GI 250 m Cu conductors 100 m Ambient conditions Ambient temperature during operation horizontal installation min 25 C horizontal ...

Страница 56: ...BusAdapter BA SCRJ FC The BusAdapter BA SCRJ FC has one port for connection of a copper cable and one port for connection of a fiber optic cable Screw the BusAdapter BA SCRJ FC with the attached Fast Connect bus cable onto the interface module and plug in the SCRJ connector You loop through the PROFINET IO via the integrated 2 port switch You can use any port of the BusAdapter for feeding or for l...

Страница 57: ...necting BusAdapter BA 2 FC Page 21 Pin assignment The following table shows the signal name and description of the pin assignment of the BusAdapter BA SCRJ FC Table 10 1 PROFINET IO pin assignment with BusAdapter BA SCRJ FC View Signal name Description Receive Data Transmit Data 1 RD_N Receive Data 2 TD_N Transmit Data 3 RD Receive Data 4 TD Transmit Data Procedure To connect PROFINET IO to the PR...

Страница 58: ... using an ET 200SP interface module as an example Note Installation guidelines for modules with PROFINET IO interfaces Ensure that all devices are connected to the SELV PELV power supply or equivalent Only then are you permitted to operate the modules with PROFINET IO interfaces in LAN networks Local Area Networks A data transfer point that guarantees this degree of safety is prescribed for connec...

Страница 59: ...3 Diagnostics BusAdapter 58 Equipment Manual 08 2020 A5E41449003 AB 10 3 Diagnostics LEDs The figure below shows the LEDs on the BusAdapter BA SCRJ FC LK1 green MT yellow LK2 green Figure 10 3 LEDs on the BusAdapter BA SCRJ FC ...

Страница 60: ... tion between the PROFINET IO interface of your PROFINET device and a communication partner e g IO controller flashes Not relevant The Node flash test is run ning The RN ER MT LEDs are also flashing Not relevant off No error Not relevant on Fiber optic error Maintenance demanded attenuation through the fi ber optic cable is already so high that operation will soon no longer be possible Causes and ...

Страница 61: ...SCRJ FC HW functional status from FS04 Interfaces Number of PROFINET interfaces 1 2 ports SCRJ FC Supports protocol for PROFINET IO Number of FC FastConnect connections 1 Number of SCRJ ports 1 Number of LC ports 0 Cable length PCF 100 m Plastic FOC POF 50 m PCF GI 250 m Cu conductors 100 m Ambient conditions Ambient temperature during operation horizontal installation min 25 C horizontal installa...

Страница 62: ...ce via the BusAdapter BA LC RJ45 Optically with glass fiber optic cables with an LC connector to port 1 Electrically with a standard RJ45 connector to port 2 To do this screw the BusAdapter BA LC RJ45 to the PROFINET device and plug in the LC connector or the RJ45 connector You can loop through PROFINET IO via the integrated 2 port switch You can use any port of the BusAdapter for feeding or for l...

Страница 63: ...2 LC Page 35 Connecting the RJ45 connector You can find more information about the required tools accessories and procedures in the section Connecting BusAdapter BA 2 RJ45 Page 15 Pin assignment The following table shows the signal name and description of the pin assignment of the BusAdapter BA LC RJ45 Table 11 1 PROFINET IO pin assignment with BusAdapter BA LC RJ45 View Signal name Description Re...

Страница 64: ... using an ET 200SP interface module as an example Note Installation guidelines for modules with PROFINET IO interfaces Ensure that all devices are connected to the SELV PELV power supply or equivalent Only then are you permitted to operate the modules with PROFINET IO interfaces in LAN networks Local Area Networks A data transfer point that guarantees this degree of safety is prescribed for connec...

Страница 65: ... 11 2 Status and error displays LED Meaning Remedy LK1 LK2 off There is no Ethernet connection between the PROFINET IO interface of your PROFINET device and a communication partner e g IO controller Check whether the bus cable to the switch or IO controller is disconnected on There is no Ethernet connection between the PROFINET IO interface of your PROFINET device and a communication partner e g I...

Страница 66: ...faces Number of PROFINET interfaces 1 2 ports switch LC RJ45 Supports protocol for PROFINET IO Number of RJ45 ports 1 Number of SCRJ ports 0 Number of LC ports 1 Wavelength of 1 270 1 380 nm corresponds to 100BASE FX Cable length Cu conductors 100 m Multimode graded index fiber 50 125 µm 3 km Multimode graded index fiber 62 5 125 μm 3 km Ambient conditions Ambient temperature during operation hori...

Страница 67: ...BusAdapter BA LC FC Optically with glass fiber optic cables with an LC connector to port 1 Electrically with direct connection of the Fast Connect bus cable to port 2 Screw the BusAdapter BA LC FC with the attached Fast Connect bus cable onto the PROFINET device and plug in the LC connector You loop through the PROFINET IO via the integrated 2 port switch You can use any port of the BusAdapter for...

Страница 68: ...ments and procedures in the section Connecting BusAdapter BA 2 LC Page 35 Connecting FastConnect bus cable You can find more information about the required tools accessories and procedures in the section Connecting BusAdapter BA 2 FC Page 21 Pin assignment The following table shows the signal name and description of the pin assignment of the BusAdapter BA LC FC Table 12 1 PROFINET IO pin assignmen...

Страница 69: ...er BA LC FC to the interface module Note Installation guidelines for modules with PROFINET IO interfaces Ensure that all devices are connected to the SELV PELV power supply or equivalent Only then are you permitted to operate the modules with PROFINET IO interfaces in LAN networks Local Area Networks A data transfer point that guarantees this degree of safety is prescribed for connection to the WA...

Страница 70: ...tatus and error displays LED Meaning Remedy LK1 LK2 off There is no Ethernet connection between the PROFINET IO interface of your PROFINET device and a communication partner e g IO controller Check whether the bus cable to the switch or IO controller is disconnected on There is no Ethernet connection between the PROFINET IO interface of your PROFINET device and a communication partner e g IO contr...

Страница 71: ...rfaces Number of PROFINET interfaces 1 Supports protocol for PROFINET IO Number of FC FastConnect connections 1 Number of SCRJ ports 0 Number of LC ports 1 Wavelength of 1 270 1 380 nm corresponds to 100BASE FX Cable length Cu conductors 100 m Multimode graded index fiber 50 125 µm 3 km Multimode graded index fiber 62 5 125 μm 3 km Ambient conditions Ambient temperature during operation horizontal...

Страница 72: ...The strain relief is a mechanical protective device for the electrical PROFINET cables on the BusAdapter The strain relief is suitable for all optical and electrical PROFINET cables of the BusAdapter The strain relief is an optional accessories The cable ties are not included in the delivery We recommend cable ties with a width of 4 8 mm The maximum width is 7 0 mm The length of the cable tie is m...

Страница 73: ...nting of the strain relief BusAdapter and strain relief can be mounted separately Tools required Screwdriver TX10 torx Procedure To install the strain relief follow these steps 1 Press the strain relief below the BusAdapter seat of the PROFINET device Figure 13 2 Strain relief before mounting 2 Fasten the strain relief 1 screw with 0 7 to 0 8 Nm tightening torque 3 Plug the BusAdapter into the PRO...

Страница 74: ...uipment Manual 08 2020 A5E41449003 AB 73 4 Screw the BusAdapter to the PROFINET device 1 screw with 0 25 Nm tightening torque 5 Fasten each PROFINET cable individually to the strain relief with the cable ties Figure 13 3 Strain relief installed ...

Страница 75: ...on drawings The figure below shows the dimension drawing of the BusAdapter BA 2xRJ45 as an example Figure A 1 Dimensional drawing of BusAdapter BA 2xRJ45 A 2 Strain relief dimension drawings The figure below shows the dimension drawing of the strain relief Figure A 2 Strain relief dimension drawing ...

Страница 76: ... Reference identification label 10 mats with 16 labels each 6ES7193 6LF30 0AW0 The labels enable the reference identification labeling of the BusAdapter The labels can be or dered on a mat for thermal transfer and inkjet printers as optional ac cessories You insert the reference identifica tion label into the opening on the top of the BusAdapter Cables and connectors You can find the recommended c...

Страница 77: ...sion installable from BA 2xRJ45 V5 5 4 0 HSP0250 V1 0 V5 5 3 0 V13 BA 2xFC V5 5 4 0 HSP0250 V1 0 V5 5 3 0 V13 BA 2xSCRJ V5 5 4 0 HSP0250 V1 0 V5 5 3 0 V13 SP1 BA SCRJ R45 V5 6 0 0 HSP0250 V3 0 V5 5 4 0 V13 SP1 HSP0129 BA SCRJ FC V5 6 0 0 HSP0250 V3 0 V5 5 4 0 V13 SP1 HSP0129 BA 2xLC V5 6 0 0 HSP0250 V4 0 V5 5 4 0 V13 SP1 Upd6 HSP0158 BA LC RJ45 V5 6 0 0 HSP0250 V4 0 V5 5 4 0 V13 SP1 Upd6 HSP0158 B...

Отзывы: