Engineering and remote access
3.6 Cyclic and acyclic data
SITOP UPS1600 / BAT1600 / UPS1100
106
Equipment Manual, 07.2021, A5E37775406-11-76
3.6
Cyclic and acyclic data
The data communicated between SITOP UPS1600 and the PROFINET IO-Controller can be
viewed in SIMATIC STEP 7 or SIMATIC STEP 7 in the TIA Portal. Here, a distinction is made
between cyclic data (input/output data) and acyclic data (reading/writing data sets).
Input/output data
SITOP UPS1600 sends, in cyclic intervals (1 ms - 512 ms for IRT or 1 ms - 2048 ms for RT),
data about the actual operating states to the PROFINET IO-Controller. You will find more
information on this at Input and output data (Page 106).
Reading and writing data sets
Reading and writing data sets are sent acyclically from the SITOP UPS1600 to the
PROFINET IO-Controller or from the PROFINET IO-Controller to the SITOP UPS1600. Additional
information can be found at Reading and writing data sets (Page 107).
3.6.1
Input and output data
An overview of the input and output data, which is cyclically sent from the SITOP UPS1600 to
the PROFINET IO controller is provided in the following tables.
Slot
Subslot Data
Description
Data size
0
2
Input voltage
Input voltage is present:
•
0: NOT OK
•
255: OK
Unsigned8
Buffer mode
Buffer mode:
The load connected to the
SITOP UPS1600 is supplied via the
energy storage device connected
to the SITOP UPS1600:
•
0: inactive
•
255: active
Unsigned8
Ready for buffering
Ready for buffer operation as the
energy storage device of the buff-
er component has been sufficient-
ly charged.
•
0: NOT OK
•
255: OK
Unsigned8
Charge sufficient
Charge level sufficient: When this
flag is set, the required charge
level has been achieved:
•
0: NOT OK
•
255: OK
Unsigned8
Содержание 6EP4131-0GB00-0AY0
Страница 6: ...Overview SITOP UPS1600 BAT1600 UPS1100 6 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 12: ...Table of contents SITOP UPS1600 BAT1600 UPS1100 12 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 186: ...Troubleshooting 4 1 Hardware fault SITOP UPS1600 BAT1600 UPS1100 186 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 252: ...Technical data 8 8 Dimension drawing SITOP UPS1600 BAT1600 UPS1100 252 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 262: ...Environment SITOP UPS1600 BAT1600 UPS1100 262 Equipment Manual 07 2021 A5E37775406 11 76 ...