Article number
6DL1131-6TH00-0PH1
Address area
Address space per module
• Address space per module, max.
2 byte; + 2 bytes for QI information
Digital inputs
Digital inputs, parameterizable
Yes
Pulse extension
Yes; 0.5 s, 1 s, 2 s
Time stamping
Yes
Time stamp (with precision of 1 ms)
No
Edge evaluation
Yes; rising edge, falling edge, edge change
Signal change flutter
Yes; 2 to 32 signal changes
Flutter observation window
Yes; 0.5 s, 1 s to 100 s in 1-s steps
Input current
for 10 k switched contact
– for signal "0"
0.35 to 1.2 mA
– for signal "1"
2.1 ... 6.4 mA
for unswitched contact
– for signal "0", max. (permissible quies‐
cent current)
0.5 mA
– for signal "1"
typ. 8 mA
for NAMUR encoders
– for signal "0"
0.35 to 1.2 mA
– for signal "1"
2.1 ... 6.4 mA
Input delay (for rated value of input voltage)
• tolerated changeover time for changeover
contacts
300 ms
for NAMUR inputs
– at "0" to "1", max.
17 ms
– at "1" to "0", max.
25 ms
Cable length
• shielded, max.
600 m
• unshielded, max.
200 m
Encoder
Connectable encoders
• NAMUR encoder/changeover contact accord‐
ing to EN 60947
Yes
• Single contact / changeover contact uncon‐
nected
Yes
• Single contact / changeover contact connec‐
ted with 10 kΩ
Yes
• 2-wire sensor
Yes; Acc. to NAMUR
– permissible quiescent current (2-wire
sensor), max.
1.2 mA
Diagnoses
Technical specifications
8.1 Technical specifications
DI 16xNAMUR HA
38
Equipment Manual, 08/2019, A5E39293880-AD
Содержание 6DL1131-6TH00-0PH1
Страница 6: ...Security information DI 16xNAMUR HA 6 Equipment Manual 08 2019 A5E39293880 AD ...
Страница 8: ...Preface DI 16xNAMUR HA 8 Equipment Manual 08 2019 A5E39293880 AD ...
Страница 10: ...2D Matrix code QR code EAN code DI 16xNAMUR HA 10 Equipment Manual 08 2019 A5E39293880 AD ...
Страница 14: ...Product overview 4 3 Terminal blocks DI 16xNAMUR HA 14 Equipment Manual 08 2019 A5E39293880 AD ...
Страница 30: ...Parameters 6 5 Flutter monitoring DI 16xNAMUR HA 30 Equipment Manual 08 2019 A5E39293880 AD ...