7. Ensure the interface card is configured to set inputs to permanent detect if link to
Wimag access point timeouts. Ensure the ‘Activate error output’ and ‘Activate
detection zone outputs’ boxes are ticked, and ensure the ‘Timeout’ value is set to
3000 (30s).
Figure 33 : General Settings Screen
8. Set any other settings of the interface card as per the configuration sheet. Any
deviations from the configuration sheet should be recorded on said sheet.
9. On completion of the settings
– click on the ‘
Apply Settings
’ and allow the unit to
reboot
Figure 34 : Apply Settings Screen
10. Disconnect the Ethernet connector from the front of the card.
11. Pull the interface card from the rack
12. Re-
apply the ‘configuration link if removed.