Technical data
Power supply
Operating voltage
Bus current
Bus power consumption
DC 21…30 V, powered from bus
3.5 mA @ DC 24 V, 3.0 mA @ DC 30 V
< 90 mW
Auxiliary power voltage
Current
Power consumption
DC 24…30 V
< 150 mA @ DC 24 V, < 120 mA @ DC 30 V
< 3.6 W
Interface
KNX
KNX bus connection terminal: black/red
KNX auxiliary power supply: yellow/white
Max. communication objects: 688
Max. group addresses: 2000
Max. associations: 2000
Ambient conditions and protection classification
As per EN 62368-1 classification
Pollution class
Over-voltage class
2
II
Safety class
Class III
Protection degree of housing as per
EN 60529
IP30
Environmental conditions
●
Storage EN 60721-3-1
●
Class 1K3
Temperature: -25...55 °C
Humidity: 0...93 % r.h. (non-condensing)
●
Transport EN 60721-3-2
●
Class 2K3
Temperature: -25...70 °C
Humidity: 0...93 % r.h. (non-condensing)
●
Operation EN 60721-3-3
●
Class 3K5
Temperature: -5...45 °C
Humidity: 0...93 % r.h. (non-condensing)
Mechanical conditions
Storage EN 60721-3-1
Transport EN 60721-3-2
Operation EN 60721-3-3
Class 1M2
Class 2M2
Class 3M2
Standards, directives, and approvals
Electromagnetic compatibility
For use in residential, commercial and industrial
environments
EU conformity (CE)
A5W00138763A
*
RCM conformity
A5W00138764A
*
Environmental compatibility
The product environmental declaration
(A5W00137325A
*
) contains data on
environmentally compatible product design and
assements (RoHS compliance, materials
composition, packaging, environmental benefit,