Siemens 5WG1205-2AB21 Скачать руководство пользователя страница 3

3

Siemens

Datasheet

A6V11980238_en--_a

Smart Infrastructure

2021-01-28

  Administrator function via password

It is configurable. Maximum 3 passwords are available.

  Administrator function via bus

The whole device or selected function pages can be locked to disable user screen

operation.

  Multi-usage color strip

The color strip is designed not only as a decoration, but also for multiple indication

usage, such as indication of KNX programming mode, seasonal changes and alarm

information.

  On site customization possible for theme (wallpaper), screen saver, and configurable

icons

Type summary

Product no.

Stock no.

Description

Operating voltage

UP 205/21

5WG1205-2AB21

5" touch panel, vertical  DC 24…30 V

Accessories

No.

Product

Description

1

Mounting plate

For fitting onto a conduit box

1)

2

Screws

2)

Only for China market

Note:

1)

 Conduit box needs to be ordered separately.

2)

 #6/32 flat head machine screw is for US market.

Ordering

When ordering, specify product quantity, product number / stock number and name: e.g.

UP 205/21 (5WG1205-2AB21) 5" touch panel.

Product documentation

Title

Document ID

Mounting instructions

A6V11980235

Application manual

A6V12035440

CE declaration

A5W00138763A

RCM declaration

A5W00138764A

Environmental product declaration

A5W00137325A

Related documents such as environmental declarations, CE declarations, etc., can be

downloaded at the following Internet address:

http://siemens.com/bt/download

Technical documentation and ETS application can be downloaded at

http://www.siemens.com/gamma-td

 (S-Mode).

To search for the technical documentation, you can enter the product type in

http://www.siemens.com/gamma-td

.

Содержание 5WG1205-2AB21

Страница 1: ...ontroller and or ventilation Interface and operation for VRF devices VRF Variable Refrigerant Flow Display of temperature humidity air quality energy metering value etc Schedule event management and basic logic function Configurable navigation for up to 15 function pages Administrator function via password or bus objects Proximity sensor adjustment of screen brightness buzzer Customization possibl...

Страница 2: ...ff and Auto operation mode changes 4 modes Comfort Standby Economy and Protection VRF Variable Refrigerant Flow interface allows TC5 to act as the user interface to operate VRF or VRV Variable Refrigerant Volume air conditioning devices with a VRF gateway Enhanced floor heating control has dedicated timer and scene function There is indication of heating valve on off and timer operation on screen ...

Страница 3: ...No Product Description 1 Mounting plate For fitting onto a conduit box 1 2 Screws 2 Only for China market Note 1 Conduit box needs to be ordered separately 2 6 32 flat head machine screw is for US market Ordering When ordering specify product quantity product number stock number and name e g UP 205 21 5WG1205 2AB21 5 touch panel Product documentation Title Document ID Mounting instructions A6V1198...

Страница 4: ...ensor Auxiliary power supply connection terminal Note Entering programming mode Click the setting icon in home page Goes to General Enable KNX programming then the colorful strip turns red and device can be configured via ETS KNX programming function need to be done by professional engineers Make sure this function is disabled during daily operation and if it is enabled The device can operate norm...

Страница 5: ... device Wiring Equipped with protective features against over voltage over current short circuit and reverse polarity in the power supply All connectors must be soldered using tin wires Otherwise resistance will be generated in the contacts over time which cause unstable operation The device is powered with direct current Avoid reversing the positive and negative poles of the power supply When con...

Страница 6: ... accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of ...

Страница 7: ...ree of housing as per EN 60529 IP30 Environmental conditions Storage EN 60721 3 1 Class 1K3 Temperature 25 55 C Humidity 0 93 r h non condensing Transport EN 60721 3 2 Class 2K3 Temperature 25 70 C Humidity 0 93 r h non condensing Operation EN 60721 3 3 Class 3K5 Temperature 5 45 C Humidity 0 93 r h non condensing Mechanical conditions Storage EN 60721 3 1 Transport EN 60721 3 2 Operation EN 60721...

Страница 8: ...tained based on human detection not an obstacle Built in temperature sensor Measuring accuracy at 25 C NTC 100k 1 K Display 5WG1205 2AB21 5 inch color capacitance touch screen 480 854 pixel Dimensions mm w h d 5WG1205 2AB21 86 148 8 32 5 Weight without with package 5WG1205 2AB21 192 376 g Materials and colors 5WG1205 2AB21 Rear housing PC V0 Front panel 6063 aluminum Touch panel Glass Film Film ...

Страница 9: ...9 Siemens Datasheet A6V11980238_en _a Smart Infrastructure 2021 01 28 Diagrams Connection terminals DC DC Auxiliary power voltage DC 24 30 V KNX KNX KNX operating voltage DC 21 30 V ...

Страница 10: ...to change without notice Document ID A6V11980238_en _a Edition 2021 01 28 Dimensions mm Support Hand over the operating instructions and all other technical product information to the client Return faulty devices with a return delivery note to the local Siemens office For technical questions contact 49 911 895 7222 49 911 895 7223 support automation siemens com http www siemens com supportrequest ...

Отзывы: