Document No. 540-320

Installation Instructions

July 15, 2009

1   2   3   4   5   6   7   8   9  10 1

1

 12 13 14 15 16

Y2

Y1

TEC2032WDR1

ELECTRIC HEAT STAGE 3
(OPTIONAL); OR SPARE DO

ELECTRIC HEAT STAGE 2
(OPTIONAL); OR SPARE DO

ELECTRIC HEAT STAGE 1; OR,
2-POSITION HEATING VALVE 

AUTOZERO MODULE (OPTIONAL)
OR SPARE DO 

CCW

CW

COMMON

G

DI 2

DO 6

DO 5

DO 4

DO 3

DO 2

DO 1

AI3 / DI3

NO

C

NO

C

NO

C

NO

C

NO

C

NO

C

+

-

SPARE AI (100K     THERMISTOR)
OR SPARE DI (DRY CONTACT)  

DAMPER
ACTUATOR

WALL SWITCH (OPTIONAL)
OR SPARE DI (DRY CONTACT)

Figure 8.

Application 2032 and 2132 (CV with Electric

Reheat).

1   2   3   4   5   6   7   8   9  10 1

1

 12 13 14 15 16

CLOSED

OPEN

C

SPARE AI (100K     THERMISTOR)
OR SPARE DI (DRY CONTACT)  

AUTOZERO MODULE (OPTIONAL)
OR SPARE DO 

Y2

Y1

TEC2033WDR1

CCW

CW

COMMON

G

DI 2

DO 6

DO 5

DO 4

DO 3

DO 2

DO 1

AI3 / DI3

NO

C

NO

C

NO

C

NO

C

NO

C

NO

C

+

-

SPARE DO

WALL SWITCH (OPTIONAL)
OR SPARE DI (DRY CONTACT)

VALVE
ACTUATOR

DAMPER
ACTUATOR

Figure 9.

Application 2033 and 2133 (CV Hot Water

Reheat).

Siemens Building Technologies, Inc.

Page 5 of 6

Содержание 540-103

Страница 1: ...S Figure 1 Constant Volume Controller Electronic Output Control Applications 2030 2032 2033 2130 2132 2133 Secure Mode Applications Product Description These instructions explain how to field install or replace a Constant Volume Controller Electronic Output with or without Secure Mode or optional Autozero Module Shipping carton includes a controller assembly controller board and cover a mounting r...

Страница 2: ... Cabling and connectors See the section Cordless drill driver set Prerequisites MBC or RBC enclosure mounted with at least one open slot on the C BUS and AC power connected CE Compliance requirements met if needed Termination blocks installed if any Authorized modem installed if connection to a public telephone network is required One 115V or 230V receptacle depending on device to power the Trunk ...

Страница 3: ...s on the controller or Autozero Module Figure 5 Connect HI to HI and LO to LO The installation is complete CE Compliance If CE compliance is required the Equipment Controller must be mounted in a grounded metal enclosure and a ferrite filter must be placed approximately 1 cm from the end of the cable being shielded RTS cableand point wiring for AI3 Figure 4 TEC0320R3 1 2 cm 1 Place the filter 1 2 ...

Страница 4: ...h DO Use an interposing 24 Vac relay module such as P N such as P N 550 054 for any of the following VA requirements higher than 12 VA Separate transformers to power the load Direct current DC power requirements 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 AUTOZERO MODULE OPTIONAL OR SPARE DO Y2 Y1 TEC2030WDR1 CCW CW COMMON G DI 2 DO 6 DO 5 DO 4 DO 3 DO 2 DO 1 AI3 DI3 NO C NO C NO C NO C NO C NO C SPARE...

Страница 5: ...00K THERMISTOR OR SPARE DI DRY CONTACT DAMPER ACTUATOR WALL SWITCH OPTIONAL OR SPARE DI DRY CONTACT Figure 8 Application 2032 and 2132 CV with Electric Reheat 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 CLOSED OPEN C SPARE AI 100K THERMISTOR OR SPARE DI DRY CONTACT AUTOZERO MODULE OPTIONAL OR SPARE DO Y2 Y1 TEC2033WDR1 CCW CW COMMON G DI 2 DO 6 DO 5 DO 4 DO 3 DO 2 DO 1 AI3 DI3 NO C NO C NO C NO C NO C ...

Страница 6: ...ts are introduced Product or company names mentioned herein may be the trademarks of their respective owners 2009 Siemens Building Technologies Inc Siemens Building Technologies Inc Your feedback is important to us If you have Document No 540 320 1000 Deerfield Parkway comments about this document send them to Country of Origin US Buffalo Grove IL 60089 4513 SBT_technical editor us sbt siemens com...

Отзывы: