Description
9229 9923 176 0B
27
2013-09-09
Rating plate
Technical data
Fig. 29
Technical data
Dimensions and weights
The dimensions of the vacuum circuit-breaker module can be taken from the rele-
vant dimension drawing. If required, these are available from your sales represent-
ative.
The weight is given on the rating plate of the vacuum circuit-breaker module (see
Fig. 28) or can be taken from the relevant dimension drawing.
Fig. 28
Example – vacuum circuit-breaker module rating plate 3AK
a
Manufacturer
b
Type designation
c
Works serial number
d
Rated voltage
U
r
e
Rated frequency
f
r
f
Rated short-circuit breaking current
I
sc
g
Rated power frequency withstand
voltage
U
d
h
Rated lightning impulse withstand
voltage
U
p
i
Quality control seal
k
Year of manufacture
m Rated operating current
I
r
n
Rated short-circuit duration
t
k
o
Mass m
p
Rated operating sequence
r
Classification to standard
Rated voltage*
U
r
kV
7.2
12
17.5
17.5
Rated operating current
I
r
A
1250, 2000, 2500, 3150, 4000**
1250, 2000,
2500
Rated lightning impulse withstand voltage (peak
value)
U
p
kV
60
75
95
95
Rated power frequency withstand voltage (effective
value)
U
d
kV
20 (32,
42***)
28 (42***)
38 (42***)
38 (42***)
Rated short-circuit breaking current
I
sc
kA
40/50
40
Distance between pole centres
mm
210
210
Rated operating sequence
A
B
A
O - 3 min - CO - 3 min - CO
B
CO - 30 min - CO
*
In the event of a rated frequency
f
r of 50/60 Hz
**
4000 A only with additional cooling
***
On request