Description
20
9229 9947 176 0C
2013-03-28
Motor (M1)
*) The operator's supply voltage may deviate from the rated supply voltage of the
vacuum circuit-breaker by -15 % to +10 %.
**) Built-in automatic circuit-breaker with C characteristic
Fig. 22
Recommendation for motor protection device
Contactor relay K1
After the supply voltage is applied and if the closing
spring is relaxed, the motor starts immediately and is
automatically deactivated internally after charging has
taken place.
Power consumption, maximum:
• in the event of direct voltage approx. 750 W
• in the event of alternating voltage approx. 1400 VA.
In the short charging time, the motor sometimes
operates in the overload range. See Fig. 22 for the rated
voltage for the required motor short-circuit protection.
Note: The motor protection devices are not included in
the delivery of the vacuum circuit-breaker and must be
ordered separately.
Fig. 21
Motor (50.4)
Rated supply voltage U*
)
V
DC
24
DC
48
DC
60
DC
110
AC 50/60 Hz
110
DC
220
AC 50/60 Hz
230
Recommended rated current of the protective
device I**
)
A
16
10
6
4
6
2
3
If simultaneous CLOSE and OPEN commands are
continuously applied to the vacuum circuit-breaker, it
returns to the open position after being closed.
Via the function of the contactor relay K1, the vacuum
circuit-breaker pauses there until the CLOSE command
is given again.
This prevents continuous closing and opening
(pumping).
Fig. 23
Contactor relay (69.)