Mounting
46
9229 9860 176 0E
2013-08-22
Removing the transport securing device from the undervoltage release
Undervoltage release (Y7)
available?
The vacuum circuit-breaker with an undervoltage release (Y7) 3AX1103 is supplied
with a transport securing device.
•
Remove the two top screws (60.2) of the mechanism box.
•
Remove the two bottom screws (60.2) of the mechanism box until the cover
(60.1) can be taken off.
•
Slightly tilt the cover (60.1) of the mechanism box and lift off.
•
Shift the locking screw of the striker from position A to B (see reference note in
mechanism box [60.] of the vacuum circuit-breaker).
•
Replace the cover (60.1) in the reverse order
•
and fasten the screws with a tightening torque of 10 Nm.
Fig. 64
Removing the cover
Fig. 65
Removing the transport securing device
A
B
Содержание 3AH3
Страница 4: ...4 9229 9860 176 0E 2013 08 22 Blank page ...
Страница 16: ...Transport storage and packing 16 9229 9860 176 0E 2013 08 22 Blank page ...
Страница 52: ...Operation 52 9229 9860 176 0E 2013 08 22 Blank page ...
Страница 58: ...Maintenance 58 9229 9860 176 0E 2013 08 22 Blank page ...
Страница 60: ...Index of keywords 60 9229 9860 176 0E 2013 08 22 Blank page ...
Страница 62: ...62 9229 9860 176 0E 2013 08 22 Blank page ...
Страница 63: ...9229 9860 176 0E 63 2013 08 22 Blank page Siemens Parts ...