![Siemens 2AI 2/4WIRE HF Скачать руководство пользователя страница 13](http://html.mh-extra.com/html/siemens/2ai-2-4wire-hf/2ai-2-4wire-hf_manual_376945013.webp)
2 AI I 2/4WIRE HF analog electronic module (6ES7134-4MB02-0AB0)
Manual, 04/2007, A5E01076111-01
13
Parameters
2
2.1
Parameters
Table 2-1
Parameters for analog input module
2AI I 2/4WIRE HF
Range of values
Default setting
Applicability
Group diagnostics (parameter assignment error,
internal error)
•
Disable
•
Enable
Disable
Module
Diagnostics: Overflow/underflow
•
Disable
•
Enable
Disable
Module
Diagnostics: Wire break
1
•
Disable
•
Enable
Disable
Channel
Smoothing
2
•
None
•
Weak
•
Medium
•
Strong
None
Channel
Type/range of measurement
•
Deactivated
•
4 to 20 mA, 2-wire
transmitter
•
4 to 20 mA, 4-wire
transmitter
•
± 20 mA
4 to 20 mA, 4-wire
transmitter
Channel
Interference frequency suppression
2
•
Disable
•
Enable
Disable
Module
1
Only in the measuring range 4 to 20 mA
2
Not with isochronous mode