Data for selecting a sensor
Input range (rated value)/input resistance
•
Current
Approx. 44 Ω
Permitted input current (destruction limit)
Approx. 50 mA (can be limited electronically)
Load of the two-wire transmitter:
Max. 750 Ω
Smoothing of the measured values
Yes, can be assigned parameters in 4 steps by
means of digital filtering
Step
None
Weak
Medium
Strong
Time constant
1 x cycle time
4 x cycle time
16 x cycle time
32 x cycle time
I&M functions
The I&M data can be read from the module using interface modules with the following order
numbers or firmware/product versions (or higher):
Interface module
Order number
Firmware version
Product version
IM151-1 HIGH FEATURE
6ES7151-1BA01-0AB0
V2.0
02
IM151-3 PN
6ES7151-3AA20-0AB0
V4.0
01
IM151-3 PN HIGH FEATURE
6ES7151-3AA20-0AB0
V4.0
01
IM151-3 PN FO
6ES7151-3BB21-0AB0
V4.0
01