IV386 Rev.000 SIEL S.p.A.
Data di emissione: 2015-10-02
Pag. 105 di 263 + FR
TECHNICAL DATA
UPS models
SAFEPOWER EVO-HF 160
SAFEPOWER EVO-HF 200
INPUT STAGE
Nominal voltage
380-400-415 Vac Three-phase with neutral (4 wire)
Nominal frequency
50-60Hz
Maximum input current
(1)
316A
383A
Nominal battery current delivery
(2)
360A
450A
Input voltage tolerance accepted for no
battery intervention (referred to 400V AC)
20% @ 100% load
-40% +20% @50% load
Input frequency tolerance accepted for no
battery intervention (referred to 50/60Hz)
20%
40-72Hz
Input current harmonic distortion
THDi = 2.5%
(3)
Input power factor
0.99
Power Walk In mode
Programmable from 1 to 125 sec. at steps of 1 sec
OUTPUT STAGE
Nominal Voltage
(4)
380/400/415 V AC three-phase with neutral (4 wire)
Nominal frequency
(5)
50/60Hz
Output nominal current
232A
290A
Apparent nominal output power
160kVA
200kVA
Active nominal output power
160kW
200kW
Output power factor
1
Short circuit current
Up to 2.7 x In
Output voltage precision (referred to
output voltage 400V AC)
1%
Static stability
(6)
0.5%
Dynamic stability
3% resistive load
(7)
Output voltage harmonic distortion with
linear load and normalized distortion
0.5% with linear load
3% with distorted load
Admissible crest factor with distorted load
3:1
Frequency accuracy in free running mode
0.01%
Inverter overload
(Vin>364VAC )
103% infinite, 110% 60 min, 125% 10 min, 150% 1min
Bypass Overload
110% Infinite,125% 60 minutes, 150% 10 minutes
BATTERY CHARGE STAGE
Nominal voltage
240VDC
Maximum recharging current
(8)
25A (50A optional)