IV420E Rev.00 SIEL S.p.A.
Installation and user manual
Date of issue: 2019-01-29
Pag. 47 di 72+ FR
Aging Load Rate:
The value can be 18~100%
,
default value: 60%
Bypass Switches Limit:
Cross currents occur during the transfer between bypass
mode and normal mode, which impacts the system. This parameter specifies
the number of transfers between bypass mode and normal mode within 1 hour,
which ensures system security. The value can be 3 to 10, and is 10 by default.
Temp Sensor Switch:
temperature sensor compensation switch, when need to connect
battery temperature sensor, please charge the value to enable.
Temp Sensor Select:
temperature sensor type select. Has tow types: NTC and RS485.
NTC for single and short distance. Rs485 for multiple and far distance.