background image

 

IV420E Rev.00 SIEL S.p.A. 

 

Installation and user manual 

Date of issue: 2019-01-29   

 

                                  Pag. 34 di 72+ FR 

 

4.3.2.3 Output

Click the output block to enter the output data display window, click 

return to return to the previous window, click home page to return to 
the main page.

 

 

 

 

Содержание 50-200kVA PF-1 UPS

Страница 1: ...ev 00 SIEL S p A Installation and user manual Date of issue 2019 01 29 Pag 0 di 52 FR 50 200kVA PF 1 UPS INSTALLATION AND USER MANUAL SAFEPOWER S KEEP FOR FUTURE REFERENCE for the entire life of the a...

Страница 2: ......

Страница 3: ...is an intelligent three phase in Three phase out high frequency online UPS designed by our R D team who is with years of designing experiences on UPS With excellent electrical performance perfect inte...

Страница 4: ...r cable connect 15 3 8 Battery connection 19 3 9 UPS parallel Installation 20 3 10 LBS installation 21 3 11 Computer access 22 4 Operation 24 4 1 Operation Modes 24 4 2 Turn on off UPS 26 4 3 The LCD...

Страница 5: ...arth the UPS before starting it 3 Don t open or damage battery for the liquid spilled from the battery is strongly poisonous and do harmful to body 4 Please avoid short circuit between anode and catho...

Страница 6: ...ystem of which input current is kept in balance No unbalance problem might occur Digital Control This series UPS is controlled by Digital Signal Processor DSP enhance it increases reliability performa...

Страница 7: ...ation 3 1 Unpacking and checking Don t lean the UPS when moving it out from the packaging Procedure Step 1 Use a pallet truck to transport the UPS to the installation position Step 2 Check the UPS pac...

Страница 8: ...019 01 29 Pag 6 di 72 FR Step 8 Remove the front panel and real panel to remove the L shaped bracket and the plates at the left and right side of the UPS that secures the cabinet and the pallet and se...

Страница 9: ...IV420E Rev 00 SIEL S p A Installation and user manual Date of issue 2019 01 29 Pag 7 di 72 FR Rear View 100kVA 120kVA Front View Side View...

Страница 10: ...IV420E Rev 00 SIEL S p A Installation and user manual Date of issue 2019 01 29 Pag 8 di 72 FR Rear View 160kVA Front View Side View...

Страница 11: ...IV420E Rev 00 SIEL S p A Installation and user manual Date of issue 2019 01 29 Pag 9 di 72 FR Rear View 200kVA Front View Side View...

Страница 12: ...ort Port for feedback protection or for battery breaker driver to prevent battery over drain after UPS shuts down 12 MAINTAIN AUXSWS port 13 REPO port 14 Intelligent Slot 1 SNMP card Relay card 15 Col...

Страница 13: ...e installed unless the internal and external of the equipment is fully dry Otherwise there will be in danger of electric shock Batteries should be mounted in an environment where the temperature is wi...

Страница 14: ...tion shall be fitted with protective devices that may avoid the risk of UPS overloaded Over current Protection device shall be installed at the distribution panel of the incoming main supply It may id...

Страница 15: ...s input and bypass input share a power source configure both types of input power cables as mains input power cables The cables listed in Table are used only when the following requirements are met Ro...

Страница 16: ...mped OT terminals M10 11mm 26N m 3 6 3 Recommended input front end and output back end circuit breakers UPS capacity Component Specifications 50kVA Mains input circuit breaker 100A 3P Bypass input cir...

Страница 17: ...zards involving electric shock and fire 3 7 Power cable connect Once the equipment has been finally positioned and secured connect the power cables as described in the following procedure Verify the U...

Страница 18: ...se L1 Vin L1 Primary input Phase L1 Vout L2 Output Phase L2 Vin L2 Primary input Phase L2 Vout L3 Output Phase L3 Vin L3 Primary input Phase L3 Vout N Output Neutral Vin N Input Neutral for primary an...

Страница 19: ...IV420E Rev 00 SIEL S p A Installation and user manual Date of issue 2019 01 29 Pag 17 di 72 FR 3 7 2 Dual input connection 50kVA 60kVA 100kVA 160kVA 200kVA...

Страница 20: ...Dual input operation make sure the copper wire between each input lines have been removed The AC input and the AC bypass supplies must be referenced to the same neutral point Choose appropriate power...

Страница 21: ...positive battery the BAT N is connected to the cathode of the positive battery and the anode of the negative battery the BAT is connected to the cathode of the negative battery factory setting of the...

Страница 22: ...each UPS input breaker is in off position and there is no any output from each UPS connected Battery groups can be connected separately or in parallel which means the system itself provides both sepa...

Страница 23: ...rce 2 The outputs of all the UPS must be connected to a common output bus 3 The length and specification of power cables including the bypass input cables and the UPS output cables should be the same...

Страница 24: ...UPS_1 UPS_2 UPS_M Input Output STS MASTER SLAVE Load M N 1 3 11 Computer access One end of a USB cable connect to the computer the other end connect to the USB port on the UPS Open the software Muser...

Страница 25: ...Append then goes to a window of Append equipment Put the UPS name into Equipment Name and UPS ID address into Equipment address Click the button Append then the connection between UPS computer is acco...

Страница 26: ...supplies the critical AC load There is no power interruption to the critical load The UPS will automatically return to Normal Mode when AC recovers Bypass mode If the inverter is out of order or if o...

Страница 27: ...de the UPS works at Line interactive mode so the UPS will transfer to bypass supply When the AC is out of set window the UPS will transfer from bypass to Inverter and supplies power from the battery a...

Страница 28: ...ypass mode to inverter mode then the bypass LED extinguishes and the inverter LED lights up No matter whether the UPS can work normally or not all the status will be shown on the LCD display 4 2 2 Tes...

Страница 29: ...ion until you have verified that there are no internal UPS faults Turn ON OUTPUT breaker Turn ON BYPASS breaker Turn ON MAINS breaker The UPS powers from the static bypass instead of the maintenance b...

Страница 30: ...door to easily access to the main power switch Switch OFF the MAINS breaker Switch OFF the BYPASS breaker Open the OUTPUT breaker The UPS shuts down To completely isolate the UPS from AC Mains all in...

Страница 31: ...anual Date of issue 2019 01 29 Pag 29 di 72 FR Click Set at User Set window At the window of Data Set click Work Mode choose Parallel for the value then click Set as shown in below picture If the UPS...

Страница 32: ...for the parallel UPS ID at the right side such as 1 then click Set as shown in below picture If the UPS sounds a beep that means the setting is correct CAUTION After changing the parallel system ID th...

Страница 33: ...UPS Connect all the UPS according to parallel cable installation and then power on the UPS 4 3 The LCD Display LCD control panel introduction 1 LED from top to bottom Fault bypass battery inverter 2...

Страница 34: ...flow state of UPS work and quickly enters real time data by clicking on the block 4 3 2 Status View the voltage and current of the main bypass output battery can also be entered through by real time d...

Страница 35: ...ck the main block to enter the main data display window click return to return to the previous window click home page to return to the main page 4 3 2 2 Bypass Click the bypass block to enter the bypa...

Страница 36: ...lation and user manual Date of issue 2019 01 29 Pag 34 di 72 FR 4 3 2 3 Output Click the output block to enter the output data display window click return to return to the previous window click home p...

Страница 37: ...ation and user manual Date of issue 2019 01 29 Pag 35 di 72 FR 4 3 2 4 Battery Click the battery block to enter the battery data display window click return to return to the previous window click home...

Страница 38: ...01 29 Pag 36 di 72 FR 4 3 3 Alarm View the alarm and history of the UPS and open or close the buzzer 4 3 3 1 Curr Alarm Click the curr alarm to enter the current alarm display window click return to...

Страница 39: ...w click return to return to the previous window click home page to return to the main page 4 3 3 1 Buzzer Click the buzzer mute then the buzzer will mute and the red block will change to green if the...

Страница 40: ...user manual Date of issue 2019 01 29 Pag 38 di 72 FR 4 3 4 Setting There are two levels the basic setting for user settings advanced setting for technical personnel please contact the relevant techni...

Страница 41: ...IV420E Rev 00 SIEL S p A Installation and user manual Date of issue 2019 01 29 Pag 39 di 72 FR 4 3 4 1 Basic Setting Click basic setting enter by input the correct password The user password is 111111...

Страница 42: ...ome page to return to the main page 4 3 4 1 2 Password Click password block enter user password setting page input old password and new password then click save confirm to save the change Password for...

Страница 43: ...Brightness Click the text to input new value and click the save config block to save Value range is 1 63 default value is 63 Click return to return to the previous window click home page to return to...

Страница 44: ...dow click home page to return to the main page Date format has 3 formats Date current date Time current time 4 3 4 1 5 Communication setting Click the text to select other value or input new value and...

Страница 45: ...s that the bypass voltage is not normal and that the bypass is unavailable NOTE When the voltage level is 380 V the value range is 10 15 20 and 25 default When the voltage level is 400 V the value ran...

Страница 46: ...IV420E Rev 00 SIEL S p A Installation and user manual Date of issue 2019 01 29 Pag 44 di 72 FR...

Страница 47: ...to save Click return to return to the previous window click home page to return to the main page Working Mode Select the work mode of UPS work mode Single mode Parallel mode ECO mode Auto Turn on Sel...

Страница 48: ...LBS master LBS slave Default is LBS disable Bypass rate tracking rate Inverter frequency tracking to bypass frequency rate The value range is 0 5 2 and is 1 by default SCR Over Temp Power Supply Speci...

Страница 49: ...system This parameter specifies the number of transfers between bypass mode and normal mode within 1 hour which ensures system security The value can be 3 to 10 and is 10 by default Temp Sensor Switch...

Страница 50: ...arallel mode The value can be 1 6 default value is 1 Cabinet Paral Basic Units Parallel cabinet number must modify the total parallel cabinet number after set work mode to parallel mode The value can...

Страница 51: ...V 230V 240V Output Ivn Volt Regu Inverter voltage regulated the value can be 5 0 5 step is 0 5 default value 0 4 3 4 2 4 Battery setting Battery Group Must modify the number to actual configuration th...

Страница 52: ...attery capacity The value can be 0 05 0 15 and is 0 1 by default Cell float voltage The float voltage value can be 2 23 2 30 V cell and is 2 25 V cell by default Cell boost voltage The battery equaliz...

Страница 53: ...be 1 60 1 90 and is 1 80 by default Float Temp Compen Coeff modify the voltage of compensation after enable the switch the value can be 0 001 0 007 cell and is 0 003 by default Boost Charge Setting B...

Страница 54: ...on The default value is Disable Battery abnormal BCB trip Enable or disable BCB trip single output The default value is Disable Bypass Feedback Enable or disable bypass feedback output The default val...

Страница 55: ...IV420E Rev 00 SIEL S p A Installation and user manual Date of issue 2019 01 29 Pag 53 di 72 FR 4 3 5 1 USB Wizard History Output download history and setting record by USB 4 3 5 1 1 Alarm Log Output...

Страница 56: ...p A Installation and user manual Date of issue 2019 01 29 Pag 54 di 72 FR 4 3 5 1 2 Setting Log Output 4 3 5 2 Battery Self Check can select check by Timing Daily Timing Weekly The default value is Ti...

Страница 57: ...on and user manual Date of issue 2019 01 29 Pag 55 di 72 FR 4 3 5 2 1 Timing Daily modify the check date time and check time 10S default 10min EOD 4 3 5 2 2 Timing Weekly modify the check date time an...

Страница 58: ...issue 2019 01 29 Pag 56 di 72 FR 4 3 6 Common INV ON OFF Battery test and Fault clear 4 3 6 1 INV ON OFF Single OFF Inverter OFF location UPS Single ON Inverter ON location UPS Parallel OFF Inverter O...

Страница 59: ...manual Date of issue 2019 01 29 Pag 57 di 72 FR 4 3 6 2 Battery Test 10S battery test for 10s 10min battery test for 10min EOD battery test to EOD 10 battery test down 10 capability 4 3 6 3 Fault cle...

Страница 60: ...and for LED Fault Bypass Battery Inverter 1 Initialized EXTINGUISH EXTINGUISH EXTINGUISH EXTINGUISH 2 Standby Mode EXTINGUISH EXTINGUISH X EXTINGUISH 3 No Output EXTINGUISH EXTINGUISH X EXTINGUISH 4 B...

Страница 61: ...it 21 04A Inverter relay Broken Beep continuously Fault LED lit 22 04D INV par cable Fault Twice per second Fault LED lit 23 051 Output Short Circuit Once per second Fault LED blinking 24 054 INV Comm...

Страница 62: ...Once per 2 seconds BYPASS LED blinking 20 142 Unit quantity mismatch Once per 2 seconds FAULT LED blinking 21 143 Parallel Overload Once per 2 seconds INVERTER LED blinking 22 144 Bypass Overload Onc...

Страница 63: ...gy of the UPS Network Management Relay card A 10 pin terminal is supported to offer the signals of Bypass Utility Failure Inverter On Battery Low UPS fault UPS Alarm and UPS Shutdown for HIPOWER serie...

Страница 64: ...2 Battery Mode 50 60 1 0 02 Hz Crest factor 3 1 Harmonic distortion THD 2 with linear load 4 with non linear load Efficiency 95 5 BATTERY Battery voltage Optional Voltage 180V 192V 204V 216V 228V 240...

Страница 65: ...de 1500m When 1500m lower the rated power for use Noise level 58dB 60dB 62dB 63dB 66dB 68dB PHYSICAL Dimension D W H mm 828x250x868 850x442x1100 850x442x1200 Net weight kg 80 83 147 155 190 230 STANDA...

Страница 66: ...s not indicate any failure but output do not have voltage Output cable does not well connected Output breaker do not switch on Make sure the output cable is well connected Switch on the output breaker...

Страница 67: ...scription Pin 1 Pin 1 PC 5V Pin 2 Pin 2 PC DPLUS signal Pin 3 Pin 3 PC DMINUS signal Pin 4 Pin 4 Signal ground Available function of USB Monitor UPS power status Monitor UPS alarm info Monitor UPS run...

Страница 68: ...UPS RS232 port Pin 2 Pin 2 UPS send PC receive Pin 3 Pin 3 PC send UPS receive Pin 5 Pin 5 ground Available function of RS232 Monitor UPS power status Monitor UPS alarm info Monitor UPS running param...

Страница 69: ...escription Pin 1 5 Pin 1 5 485 A Pin 2 4 Pin 2 4 485 B Pin7 Pin7 12Vdc Pin8 Pin8 GND Available function of RS485 Monitor UPS power status Monitor UPS alarm info Monitor UPS running parameters Timing o...

Страница 70: ...efinition of Male port Instruction Relay Dry Contact Port 5A 277Vac UPS Instruction Pin1 Normally NC Pin2 Normally NO Pin3 Pin4 Common Function 1 description default internal J6 jumper Drive the bypas...

Страница 71: ...n Definition of port Connection diagram Connection between the button and UPS REPO port Button UPS REPO Description Pin 1 Pin 1 EPO NO Pin 2 Pin 2 EPO 12V Pin 1 Pin 3 EPO NC Pin 2 Pin 4 EPO 12V A remo...

Страница 72: ...ins configurations via the output port as per Appendix 6 If the contactor coil exceeds the voltage current limits of the UPS output port a 24 Vcc source should be generated from the same source the co...

Страница 73: ...Route the cable with the other signal cables 2 Connect the UPS backfeed dry contact port 4 to the contactor C coil Route the cable with the other signal cables 3 Connect the fuse F and the coil of C...

Страница 74: ......

Отзывы: