background image

 9

SE130/250T IP Ignition Protected thruster assembly      

versjon1.3 - 2015

  Explanation of electrical table 

- All cable lengths are the total of + and - (to and from). 

- Battery size is stated as minimum cold crank capacity, not Ah. 

- Use slow fuse rated to hold stated Amp-Draw for min. 5 minutes. 

* Cable size and main battery size when an extra bow battery with minimum the CCA mentioned as A is installed.

 

It is important that you use a good cable size and batteries with a high cranking capacity to feed the thruster, because it is the actual 

voltage at the motor while running the thruster that decides the output rpm of the motor and thereby the actual thrust. Please see the 

list below for advised min. sizes of cables and batteries. You can of course use larger cables for even better results.

  A main switch (*C) that can take the load without noticable voltage drop must be installed in the main positive lead so the power 

for the thruster can be turned off independently of the rest of the system when not on board or in emergencies. This should be placed 

in an easily accessible place and the boats instructions should include information that this should be turned off like the other main 

switches of the boat.

  We also advice to install a fuse (*D) in the positive lead for protection agains short circuiting of the main cables. This fuse should be 

of a adequate quality which normally means that it is physically large as these have less voltage drop than the simple / small ones. It 

should be of the slow type and sized to take the amperage draw for atleast 5 minutes.

  Remember to use ignition protected fuses and switches if fitted in areas that require this feature.

  A circuit breaker can be used instead of the fuse and main power switch as long as the functionality is the same.

  The cable ends must be fitted with terminals and these must be well isolated against contact with anything but the proper 

 

connection point.

  If the main switch and fuse are installed in the same gas area they also have to be ignition protected.

  The negative / minus cable connects to the (-) terminal. Bolt M10. Tighten with 25 Nm / 18,43 lb/ft.

  The positive / plus cable connects to the "+" terminal. Bolt M10. Tighten with 25 Nm / 18,43 lb/ft.

Electrical installation

 9

SP75Ti  /  SP95Ti ignition protected thruster assembly

   

1.2.1 - 2007

Explanation of electrical table
- All cable lengths are the total of + and - (to and from).

- Battery size is stated as minimum cold crank capacity, not Ah.

- Use slow fuse rated to hold stated Amp-Draw for min. 5 minutes.
* Cable size and main battery size when an extra bow battery with minimum the CCA mentioned as A is installed.

It is important that you use a good cable size and batteries with a high cranking capacity to feed the thruster, because it is the actual
voltage at the motor while running the thruster that decides the output rpm of the motor and thereby the actual thrust. Please see the list

below for advised min. sizes of cables and batteries. You can of course use larger cables for even better results.

A main switch (*C) that can take the load without noticable voltage drop must be installed in the main positive lead so the power for the
thruster can be turned off independently of the rest of the system when not on board or in emergencies. This should be placed in an easily

accessible place and the boats instructions should include information that this should be turned off like the other main switches of the boat.

We also advice to install a fuse (*D) in the positive lead for protection agains short circuiting of the main cables. This fuse should be of a
adequate quality which normally means that it is physically large as these have less voltage drop than the simple / small ones. It should

be of the slow type and sized to take the amperage draw for atleast 5 minutes.

Remember to use ignition protected fuses and switches if fitted in areas that require this feature.

A circuit breaker can be used instead of the fuse and main power switch as long as the functionality is the same.

The cable ends must be fitted with terminals and these must be well isolated against contact with anything but the proper connection point.

If the main switch and fuse are installed in the same gas area they also have to be ignition protected.

The negative / minus cable connects to the (-) terminal. Bolt M10. Tighten with 25 Nm / 18,43 lb/ft.

The positive / plus cable connects to the "+" terminal. Bolt M10. Tighten with 25 Nm / 18,43 lb/ft.

Electrical installation

Battery

12V or 24V

+

-

*D

*C

Counter Nut
Nut
Washer
Cable terminal
Washer
Counter Nut
Nut
Washer

50 mm2

95 mm2

120 mm2

150 mm2

N / A

N / A

O

OOO+

OOOO+

2xOOO

N / A

50 mm2

70 mm2

95 mm2

120 mm2

150 mm2

O

OO+

OOO+

OOOO+

2xOOO

35 mm2

35 mm2

50 mm2

70 mm2

95 mm2

120 mm2

2

2

O

OO+

OOO+

OOOO+

70 mm2

105 mm2

150 mm2

175 mm2

N / A

N / A

OO+

OOOO

2xOOO

2xOOOO

N / A

70 mm2

95 mm2

120 mm2

150 mm2

180 mm2

OO+

OOO+

OOOO+

2xOOO

2xOOOO

50 mm2

50 mm2

70 mm2

95 mm2

120 mm2

150 mm2

O

O

OO+

OOO+

OOOO+

2xOOO

Table for s election of m ain cable, 

battery, fuse and m ain-s witch 

s izes .

up to 7m  total 

+

 &

 -

7 - 14m  total 

+

 &

 -

14 - 21m  total 

+

 &

 -

21 - 28m  total 

+

 &

 -

28 - 35m  total 

+

 &

 -

36 - 45m  total 

+

 &

 -

M odel

Voltage

Current 

draw

M in. Cable 

dim ension

M in.Battery 

CCA by DIN

M in. Cable 

dim ension

M in. Cable 

dim ension

M in. Cable 

dim ension

M in.Battery 

CCA by Din

M in.Battery 

CCA by DIN

M in. Cable 

dim ension

M in. Cable 

dim ension

M in.Battery 

CCA by DIN

M in.Battery 

CCA by Din

550 CCA  Din    

1045 CCA  SA E  

600 CCA  Din    

1140 CCA  SA E

SP

 75

 T

i IP

12 V

480 A

550 CCA  Din    

1045 CCA  SA E  

24 V

240 A

300 CCA  Din    

570 CCA  SA E

12V 

Extr.batt

 *

300 A

300 CCA  Din    

570 CCA  SA E

300 CCA  Din    

570 CCA  SA E

350 CCA  Din    

665 CCA  SA E

350 CCA  Din    

665 CCA  SA E

350 CCA  Din    

665 CCA  SA E

550 CCA  Din    

1045 CCA  SA E

300 CCA  Din    

570 CCA  SA E

300 CCA  Din    

570 CCA  SA E

350 CCA  Din    

665 CCA  SA E

350 CCA  Din    

665 CCA  SA E

750 CCA  Din    

1425 CCA  SA E

750 CCA  Din    

1425 CCA  SA E

750 CCA  Din    

1425 CCA  SA E

SP

 95

 T

i IP

12 V

680 A

750 CCA  Din    

1425 CCA  SA E

12V 

Extr.batt

 *

400 A

350 CCA  Din    

665 CCA  SA E

24 V

340 A

400 CCA  Din    

760 CCA  SA E

400 CCA  Din    

760 CCA  SA E

M in.Battery 

CCA by Din

400 CCA  Din    

760 CCA  SA E

400 CCA  Din    

760 CCA  SA E

450 CCA  Din    

855 CCA  SA E

450 CCA  Din    

855 CCA  SA E

350 CCA  Din    

665 CCA  SA E

350 CCA  Din    

665 CCA  SA E

350 CCA  Din    

665 CCA  SA E

350 CCA  Din    

665 CCA  SA E

350 CCA  Din    

665 CCA  SA E

 

SE 60/185S ignition protected thruster assembly     

1.0 - 2007

  Explanation of electrical table 

- All cable lengths are the total of + and - (to and from). 

- Battery size is stated as minimum cold crank capacity, not Ah. 

- Use slow fuse rated to hold stated Amp-Draw for min. 5 minutes. 
* Cable size and main battery size when an extra bow battery with minimum the CCA mentioned as A is installed.

  It is important that you use a good cable size and batteries with a high cranking capacity to feed the thruster, because it is the actual 

voltage at the motor while running the thruster that decides the output rpm of the motor and thereby the actual thrust. Please see the 

list below for advised min. sizes of cables and batteries. You can of course use larger cables for even better results.

  A main switch (*C) that can take the load without noticable voltage drop must be installed in the main positive lead so the power 

for the thruster can be turned off independently of the rest of the system when not on board or in emergencies. This should be placed 

in an easily accessible place and the boats instructions should include information that this should be turned off like the other main 

switches of the boat.

  We also advice to install a fuse (*D) in the positive lead for protection agains short circuiting of the main cables. This fuse should be 

of a adequate quality which normally means that it is physically large as these have less voltage drop than the simple / small ones. It 

should be of the slow type and sized to take the amperage draw for atleast 5 minutes.

 Remember to use ignition protected fuses and switches if 

fitted

 in areas that require this feature.

  A circuit breaker can be used instead of the fuse and main power switch as long as the functionality is the same.

 The cable ends must be 

fitted

 with terminals and these must be well isolated against contact with anything but the proper connection 

point.

  If the main switch and fuse are installed in the same gas area they also have to be ignition protected.

  The negative / minus cable connects to the (-) terminal. Bolt M10. Tighten with 25 Nm / 18,43 lb/ft.

  The positive / plus cable connects to the "+" terminal. Bolt M10. Tighten with 25 Nm / 18,43 lb/ft.

Electrical installation

Model

Voltage Nominal 

current 

draw

Min. battery  

CCA

>7m total + & - 7-14m total + & - 15-21m total + & - 22-28m total + & - 28-35m total + & - 36-45m total + & -

Min.

Rec. Min.

Rec.

Min.

Rec.

Min.

Rec.

Min.

Rec.

Min.

Rec.

SE60/185S

12 V

340 A

DIN: 350 

SAE:665

mm

AWG

35 

1

50 

1/0

60 

2/0

95  

3/0

95 

3/0

2x 70 

2x 2/0

120 

4/0

2x95 

2x 3/0

2x 95 

2x 3/0

2x120 

2x 4/0

2x120

2x 4/0

280*

24 V

170 A

DIN: 175 

SAE: 332

mm

AWG

25 

1

35 

1

25 

1

35 

1

25 

1

35 

1

35 

1

50 

1/0

50 

1/0

60 

2/0

60 

2/0

70

2/0

Battery & cable recommendations:

Minimum and recommended cable dimensions can be identical due to  safety margins and cable heat considerations for short cable lenghts.

* Minimum or recommended cable cross section in mm

2

 

SP55S2i ignition protected thruster assembly

1.1 - 2006

Explanation of electrical table
- All cable lengths are the total of + and - (to and from).

- Battery size is stated as minimum cold crank capacity, not Ah.

- Use slow fuse rated to hold stated Amp-Draw for min. 5 minutes.
* Cable size and main battery size when an extra bow battery with minimum the CCA mentioned as A is installed.

It is important that you use a good cable size and batteries with a high cranking capacity to feed the thruster, because it is the actual
voltage at the motor while running the thruster that decides the output rpm of the motor and thereby the actual thrust. Please see the list

below for advised min. sizes of cables and batteries. You can of course use larger cables for even better results.

A main switch (*C) that can take the load without noticable voltage drop must be installed in the main positive lead so the power for the
thruster can be turned off independently of the rest of the system when not on board or in emergencies. This should be placed in an easily

accessible place and the boats instructions should include information that this should be turned off like the other main switches of the boat.

We also advice to install a fuse (*D) in the positive lead for protection agains short circuiting of the main cables. This fuse should be of a
adequate quality which normally means that it is physically large as these have less voltage drop than the simple / small ones. It should

be of the slow type and sized to take the amperage draw for atleast 5 minutes.

Remember to use ignition protected fuses and switches if fitted in areas that require this feature.

A circuit breaker can be used instead of the fuse and main power switch as long as the functionality is the same.

The cable ends must be fitted with terminals and these must be well isolated against contact with anything but the proper connection point.

If the main switch and fuse are installed in the same gas area they also have to be ignition protected.

The negative / minus cable connects to the (-) terminal. Bolt M10. Tighten with 25 Nm / 18,43 lb/ft.

The positive / plus cable connects to the "+" terminal. Bolt M10. Tighten with 25 Nm / 18,43 lb/ft.

Electrical installation

Battery

12V or 24V

+

-

*D

*C

Counter Nut
Nut
Washer
Cable terminal
Washer
Counter Nut
Nut
Washer

35 mm2

60 mm2

5 mm2

5 mm2

120 mm2

120 mm2

AWG 1

AWG OO 

AWG OOO

AWG OOOO

AWG OOOO

2 x AWG OOOO

25 mm2

25 mm2

35 mm2

35 mm2

50 mm2

50 mm2

AWG 4

AWG 4

AWG 2

AWG 2

AWG 1

AWG 1

Min.Battery 

CCA by Din

200 CCA Din 

380 CCA SAE

200 CCA Din 

380 CCA SAE

200 CCA Din 

380 CCA SAE

250 CCA Din 

475 CCA SAE

200 CCA Din 

380 CCA SAE

400 CCA Din 

760 CCA SAE

350 CCA Din 

665 CCA SAE

Min.Battery 

CCA by Din

12 V

330 A Din   

627 A SAE

350 CCA Din 

665 CCA SAE

24 V

160 A Din 

304 A SAE

200 CCA Din 

380 CCA SAE

SP5

5S2

IP

Min. Cable 

dimension

Min.Battery 

CCA by Din

350 CCA Din 

665 CCA SAE

400 CCA Din 

760 CCA SAE

400 CCA Din 

760 CCA SAE

Min.Battery 

CCA by DIN

Min. Cable 

dimension

Min. Cable 

dimension

Min.Battery 

CCA by DIN

16 - 19m total 

+

 &

 -

20 - 23m total 

+

 &

 -

24 - 27m total 

+

 &

 -

Model

Voltage

Current 

draw

Min. Cable 

dimension

Min.Battery 

CCA by DIN

Min. Cable 

dimension

Min. Cable 

dimension

Table for selection of main cable, 

battery, fuse and main-switch 

sizes.

up to 7m total 

+

 &

 -

8 - 11m total 

+

 &

 -

12 - 15m total 

+

 &

 -

 

SP55S2i ignition protected thruster assembly

1.1 - 2006

Explanation of electrical table
- All cable lengths are the total of + and - (to and from).

- Battery size is stated as minimum cold crank capacity, not Ah.

- Use slow fuse rated to hold stated Amp-Draw for min. 5 minutes.
* Cable size and main battery size when an extra bow battery with minimum the CCA mentioned as A is installed.

It is important that you use a good cable size and batteries with a high cranking capacity to feed the thruster, because it is the actual
voltage at the motor while running the thruster that decides the output rpm of the motor and thereby the actual thrust. Please see the list

below for advised min. sizes of cables and batteries. You can of course use larger cables for even better results.

A main switch (*C) that can take the load without noticable voltage drop must be installed in the main positive lead so the power for the
thruster can be turned off independently of the rest of the system when not on board or in emergencies. This should be placed in an easily

accessible place and the boats instructions should include information that this should be turned off like the other main switches of the boat.

We also advice to install a fuse (*D) in the positive lead for protection agains short circuiting of the main cables. This fuse should be of a
adequate quality which normally means that it is physically large as these have less voltage drop than the simple / small ones. It should

be of the slow type and sized to take the amperage draw for atleast 5 minutes.

Remember to use ignition protected fuses and switches if fitted in areas that require this feature.

A circuit breaker can be used instead of the fuse and main power switch as long as the functionality is the same.

The cable ends must be fitted with terminals and these must be well isolated against contact with anything but the proper connection point.

If the main switch and fuse are installed in the same gas area they also have to be ignition protected.

The negative / minus cable connects to the (-) terminal. Bolt M10. Tighten with 25 Nm / 18,43 lb/ft.

The positive / plus cable connects to the "+" terminal. Bolt M10. Tighten with 25 Nm / 18,43 lb/ft.

Electrical installation

Battery

12V or 24V

+

-

*D

*C

Counter Nut
Nut
Washer
Cable terminal
Washer
Counter Nut
Nut
Washer

35 mm2

60 mm2

5 mm2

5 mm2

120 mm2

120 mm2

AWG 1

AWG OO 

AWG OOO

AWG OOOO

AWG OOOO

2 x AWG OOOO

25 mm2

25 mm2

35 mm2

35 mm2

50 mm2

50 mm2

AWG 4

AWG 4

AWG 2

AWG 2

AWG 1

AWG 1

Min.Battery 

CCA by Din

200 CCA Din 

380 CCA SAE

200 CCA Din 

380 CCA SAE

200 CCA Din 

380 CCA SAE

250 CCA Din 

475 CCA SAE

200 CCA Din 

380 CCA SAE

400 CCA Din 

760 CCA SAE

350 CCA Din 

665 CCA SAE

Min.Battery 

CCA by Din

12 V

330 A Din   

627 A SAE

350 CCA Din 

665 CCA SAE

24 V

160 A Din 

304 A SAE

200 CCA Din 

380 CCA SAE

SP5

5S2

IP

Min. Cable 

dimension

Min.Battery 

CCA by Din

350 CCA Din 

665 CCA SAE

400 CCA Din 

760 CCA SAE

400 CCA Din 

760 CCA SAE

Min.Battery 

CCA by DIN

Min. Cable 

dimension

Min. Cable 

dimension

Min.Battery 

CCA by DIN

16 - 19m total 

+

 &

 -

20 - 23m total 

+

 &

 -

24 - 27m total 

+

 &

 -

Model

Voltage

Current 

draw

Min. Cable 

dimension

Min.Battery 

CCA by DIN

Min. Cable 

dimension

Min. Cable 

dimension

Table for selection of main cable, 

battery, fuse and main-switch 

sizes.

up to 7m total 

+

 &

 -

8 - 11m total 

+

 &

 -

12 - 15m total 

+

 &

 -

 

SP55S2i ignition protected thruster assembly

1.1 - 2006

Explanation of electrical table

- All cable lengths are the total of + and - (to and from).

- Battery size is stated as minimum cold crank capacity, not Ah.

- Use slow fuse rated to hold stated Amp-Draw for min. 5 minutes.

* Cable size and main battery size when an extra bow battery with minimum the CCA mentioned as A is installed.

It is important that you use a good cable size and batteries with a high cranking capacity to feed the thruster, because it is the actual

voltage at the motor while running the thruster that decides the output rpm of the motor and thereby the actual thrust. Please see the list

below for advised min. sizes of cables and batteries. You can of course use larger cables for even better results.

A main switch (*C) that can take the load without noticable voltage drop must be installed in the main positive lead so the power for the

thruster can be turned off independently of the rest of the system when not on board or in emergencies. This should be placed in an easily

accessible place and the boats instructions should include information that this should be turned off like the other main switches of the boat.

We also advice to install a fuse (*D) in the positive lead for protection agains short circuiting of the main cables. This fuse should be of a

adequate quality which normally means that it is physically large as these have less voltage drop than the simple / small ones. It should

be of the slow type and sized to take the amperage draw for atleast 5 minutes.

Remember to use ignition protected fuses and switches if fitted in areas that require this feature.

A circuit breaker can be used instead of the fuse and main power switch as long as the functionality is the same.

The cable ends must be fitted with terminals and these must be well isolated against contact with anything but the proper connection point.

If the main switch and fuse are installed in the same gas area they also have to be ignition protected.

The negative / minus cable connects to the (-) terminal. Bolt M10. Tighten with 25 Nm / 18,43 lb/ft.

The positive / plus cable connects to the "+" terminal. Bolt M10. Tighten with 25 Nm / 18,43 lb/ft.

Electrical installation

Batter

y

12V

 or 2

4V

+

-

*D

*C

Counter Nut

Nut

Washer

Cable terminal

Washer

Counter Nut

Nut

Washer

35 mm2

60 mm2

5 mm2

5 mm2

120 mm2

120 m

m2

AW

G 1

AW

G OO 

AW

G OOO

AWG O

OOO

AW

G OOOO

2 x

 AW

G OOOO

25 mm2

25 mm2

35 mm2

35 mm2

50 mm2

50 mm2

AW

G 4

AW

G 4

AW

G 2

AW

G 2

AW

G 1

AW

G 1

Min

.Bat

ter

CCA b

y D

in

200 C

CA

 Din

 

380 C

CA

 SA

E

200 

CC

A D

in 

380 

CC

A S

AE

200 C

CA

 Din

 

380 C

CA

 SA

E

250 CC

A D

in 

475 C

CA

 SA

E

200 C

CA

 Din 

380 C

CA

 SA

E

400 C

CA

 Din

 

760 C

CA

 SA

E

350 

CC

A D

in 

665 

CC

A S

AE

Min.

Bat

tery

 

CCA b

y D

in

12 V

330 A D

in   

627 A S

AE

350 C

CA

 D

in 

665 C

CA

 S

AE

24 V

160 A D

in 

304 A S

AE

200 C

CA

 D

in 

380 C

CA

 S

AE

SP5

5S2

IP

Min

. Cab

le 

dim

en

sio

n

Min.

Bat

tery

 

CCA by D

in

350 C

CA

 Din

 

665 C

CA

 SA

E

400 CC

A D

in 

760 C

CA

 SA

E

400 C

CA

 Din 

760 C

CA

 SA

E

Min.

Batte

ry 

CCA b

y D

IN

Min

. Cab

le 

dim

en

sio

n

Min

. Cab

le 

dim

en

sio

n

Min.

Bat

tery

 

CCA b

y D

IN

16 - 19m

 tot

al 

+

 &

 -

20 - 23m

 tot

al 

+

 &

 -

24 - 27m

 tot

al 

+

 &

 -

Mode

l

Vo

lta

ge

Curr

en

draw

Min

. Cab

le 

dim

en

sio

n

Min.

Bat

tery

 

CCA b

y D

IN

Min

. Cab

le 

dim

en

sio

n

Min

. Cab

le 

dim

en

sio

n

Tab

le f

or s

elec

tio

n of m

ain c

abl

e, 

bat

ter

y, f

use an

d mai

n-s

witc

size

s.

up t

o 7m

 tot

al 

+

 &

 -

8 - 11m

 tot

al 

+

 &

 -

12 - 15m

 tot

al 

+

 &

 -

 

SP55S2i ignition protected thruster assembly

1.1 - 2006

Explanation of electrical table
- All cable lengths are the total of + and - (to and from).

- Battery size is stated as minimum cold crank capacity, not Ah.

- Use slow fuse rated to hold stated Amp-Draw for min. 5 minutes.
* Cable size and main battery size when an extra bow battery with minimum the CCA mentioned as A is installed.

It is important that you use a good cable size and batteries with a high cranking capacity to feed the thruster, because it is the actual
voltage at the motor while running the thruster that decides the output rpm of the motor and thereby the actual thrust. Please see the list

below for advised min. sizes of cables and batteries. You can of course use larger cables for even better results.

A main switch (*C) that can take the load without noticable voltage drop must be installed in the main positive lead so the power for the
thruster can be turned off independently of the rest of the system when not on board or in emergencies. This should be placed in an easily

accessible place and the boats instructions should include information that this should be turned off like the other main switches of the boat.

We also advice to install a fuse (*D) in the positive lead for protection agains short circuiting of the main cables. This fuse should be of a
adequate quality which normally means that it is physically large as these have less voltage drop than the simple / small ones. It should

be of the slow type and sized to take the amperage draw for atleast 5 minutes.

Remember to use ignition protected fuses and switches if fitted in areas that require this feature.

A circuit breaker can be used instead of the fuse and main power switch as long as the functionality is the same.

The cable ends must be fitted with terminals and these must be well isolated against contact with anything but the proper connection point.

If the main switch and fuse are installed in the same gas area they also have to be ignition protected.

The negative / minus cable connects to the (-) terminal. Bolt M10. Tighten with 25 Nm / 18,43 lb/ft.

The positive / plus cable connects to the "+" terminal. Bolt M10. Tighten with 25 Nm / 18,43 lb/ft.

Electrical installation

Battery

12V or 24V

+

-

*D

*C

Counter Nut
Nut
Washer
Cable terminal
Washer
Counter Nut
Nut
Washer

35 mm2

60 mm2

5 mm2

5 mm2

120 mm2

120 mm2

AWG 1

AWG OO 

AWG OOO

AWG OOOO

AWG OOOO

2 x AWG OOOO

25 mm2

25 mm2

35 mm2

35 mm2

50 mm2

50 mm2

AWG 4

AWG 4

AWG 2

AWG 2

AWG 1

AWG 1

Min.Battery 

CCA by Din

200 CCA Din 

380 CCA SAE

200 CCA Din 

380 CCA SAE

200 CCA Din 

380 CCA SAE

250 CCA Din 

475 CCA SAE

200 CCA Din 

380 CCA SAE

400 CCA Din 

760 CCA SAE

350 CCA Din 

665 CCA SAE

Min.Battery 

CCA by Din

12 V

330 A Din   

627 A SAE

350 CCA Din 

665 CCA SAE

24 V

160 A Din 

304 A SAE

200 CCA Din 

380 CCA SAE

SP5

5S2

IP

Min. Cable 

dimension

Min.Battery 

CCA by Din

350 CCA Din 

665 CCA SAE

400 CCA Din 

760 CCA SAE

400 CCA Din 

760 CCA SAE

Min.Battery 

CCA by DIN

Min. Cable 

dimension

Min. Cable 

dimension

Min.Battery 

CCA by DIN

16 - 19m total 

+

 &

 -

20 - 23m total 

+

 &

 -

24 - 27m total 

+

 &

 -

Model

Voltage

Current 

draw

Min. Cable 

dimension

Min.Battery 

CCA by DIN

Min. Cable 

dimension

Min. Cable 

dimension

Table for selection of main cable, 

battery, fuse and main-switch 

sizes.

up to 7m total 

+

 &

 -

8 - 11m total 

+

 &

 -

12 - 15m total 

+

 &

 -

RED:       +

BLACK:  -

Model

Voltage Nominal 

current 

draw

Min. battery  

CCA

>7m total + & - 7-14m total + & - 15-21m total + & - 22-28m total + & - 28-35m total + & - 36-45m total + & -

Min.

Rec. Min.

Rec.

Min.

Rec.

Min.

Rec.

Min.

Rec.

Min.

Rec.

SE130/250T

12 V

740 A

DIN: 750 

SAE: 1425

mm

AWG

95 

3/0

95 

3/0

2x 70 

2x 2/0

2x 95 

2x 3/0

2x 95

2x 3/0

280*

250* 

375*

NA

NA

NA

NA

24 V

340 A

DIN: 400 

SAE: 760

mm

AWG

35 

1

50 

1/0

50 

1/0

70 

2/0

60 

2/0

95 

3/0

95 

3/0

120 

4/0

120

4/0

2x 95 

2x 3/0

2x95

2x 3/0

2x 120 

2x 4/0

Minimum and recommended cable dimensions can be identical due to  safety margins and cable heat considerations for short cable lenghts.

* Minimum or recommended cable cross section in mm

2

Battery & cable recommendations:

  NB! Very important to check the following with mainswitch in off position:

  After all electrical connections have been completed check with an ohm meter that there is no electrical connection between electro  

  motor flange and positive terminal on the motor and between the electro motor flange and the negative (A1) terminal on the motor. 

 

  If you feel unsure on how to perform this check, contact skilled personnel for guidance. 

https://yachtaidmarine.com/product-category/marine-bow-thrusters/

Содержание SE 130/250T IP

Страница 1: ... i s m a n u a l o n b o a r d SIDE POWER Thruster Systems 2175 NW 34th Ave Miami FL 33142 USA Phone 786 621 3010 Fax 786 621 3046 Website https yachtaidmarine com product category marine bow thrusters Email info yachtaidmarine com https yachtaidmarine com product category marine bow thrusters ...

Страница 2: ...ing auto reset when electro motor cools down Flexible coupling between electro motor and driveshaft protects electromotor and gearsystem if propeller gets jammed If original Sidepower panel is used the panel shuts off automatically 6 minutes after last use Integrated microprocessor monitors solenoids reducing wear and risk of solenoid lock in Auto stop of thruster in case of accidental solenoid lo...

Страница 3: ...port for the hull integrity without checking with the boatbuilder that this can be safely done When installed in boats approved or classified according to international or special national rules the installer is responsible for following the demands in accordance with these regulations classification rules The instructions in this guide can not be guaranteed to comply with all different regulation...

Страница 4: ... that you fit the oil feed pipe also before the tunnel is bolted to the transom 5 When fitting the tunnel ensure that there is ample sealant Sikaflex or similar in the sealing tracks of the tunnel flange and around the bolts to make a water tight fitting Fig 1 2 Bolts washers and nuts are not included as they will wary de pending on the transom thickness We recommend A4 stain less with A4 lock nut...

Страница 5: ...h inside and outside Fig 2 Take care not to reduce the internal diameter much as this will make it more difficult to mount the thruster 8 Apply gelcoat or similar on all bonded areas 9 Install the gear leg on the stern tunnel as described in the installation manual for the thruster but fit the oil feed pipe first 10 Basic installation of the motor assembly and electrical installa tion are describe...

Страница 6: ... Ist die Tunnel innenseite ungleichmäßig etwas Sikaflex o ä auftragen damit keine undichte Stelle auftritt PS Die Durchgänge für das Öl 2 von Dichtmasse freihalten 7 Etwas Öl oder Fett auf die O ringe der Motorhalterung geben da diese sonst beim Montieren beschädigt werden können 8 Das Getriebegehäuse durch das Hauptloch im Tunnel führen und vorsichtig mit der Motorhalterung zusammenschieben 9 Das...

Страница 7: ...p between the propeller hub and the gearhouse 3 Place the washer 4 on the prop shaft and then tighten the lock nut 3 on the propeller shaft 4 Place the zinkanode 2 in its designated position and tighten the zincanode holding screw 1 Apply a thread glue Locktite or similar to ensure that the zincanode holding screw does not un screw itself from the propellers rotation Parts description 1 Screw for ...

Страница 8: ...24 lb ft Bolt tightening force 2x SP75Ti 17 Nm 12 4 lb ft SP795Ti 17 Nm 12 4 lb ft Final gearleg assembly 1 Remove the 4 bolts in the motorbracket 2 Mount the lower part of the flexible coupling and thighten the set screw Insert the red plastic ring in the lower part 3 Place the motor gently onto the driveshaft and the motor bracket Be careful the motor is very heavy Ensure that the plastic ring g...

Страница 9: ...voltage drop must be installed in the main positive lead so the power for the thruster can be turned off independently of the rest of the system when not on board or in emergencies This should be placed in an easily accessible place and the boats instructions should include information that this should be turned off like the other main switches of the boat We also advice to install a fuse D in the...

Страница 10: ...trol leads 10 SP75Ti SP95Ti ignition protected thruster assembly 1 2 1 2007 You can install as many panels as you wish by using optional Y connectors If two or more panels are operated at the same time in opposite directions the electronic controlbox will stop the thruster until it only receives a signal to go in one direction When using original Sidepower equipment it is all plug go If the drive ...

Страница 11: ... thruster assembly 1 2 1 2007 Visual wiring diagram A2 A1 Fuse 9 6 8 1 2 4 5 red grey blue black grey blue brown red 6 1230i Electronic control box Thermal switch Battery 12V or 24V Battery main switch M 4 3 2 1 3 red red black 7 white 6 1232i https yachtaidmarine com product category marine bow thrusters ...

Страница 12: ...ck panel Visual connection diagram for dual joystick panel y We advice to use different battery banks for each thruster to ensure maximum performance when both are used at the same time y When using the original Sidepower control cables just connect them to the corresponding joystick y There are no plus positive power connected from the bowthruster yellow BOW STERN black Technical wiring diagram E...

Страница 13: ... is fitted above the waterline as required and filled with gearoil Correct drive direction as per controlpanel All electrical connections are clean dry and tight and the correct cable fuse and main switch sizes have been used The bolts holding the gearhouse and motorbracket together are tightened correctly Very important for IP protection The main power cables have securely been connected as descr...

Страница 14: ...fore performing a directions change of the thruster as it might cause damage to the thruster If the thruster stops giving thrust while the electromotor is running chances are that there is a problem in the drive system You must then immediately stop trying to run it and turn it off as running the electromotor for more than a few seconds without resistance from the propeller can cause serious damag...

Страница 15: ... use Sidepower thrusters 15 SP75Ti SP95Ti ignition protected thruster assembly 1 2 1 2007 How to use a bowthruster 1 Turn main power switch for the bowthruster on Always turn off the main power switch when not onboard 2 Please take some time to exercise thruster usage in open water to avoid damages to your boat 3 Turn the controlpanel on by pushing both ON buttons on the original Sidepower panel s...

Страница 16: ...regular service lifts of the boat Consult your dealer for information on how to do this As a part of the seasonal service of your boat and before every season always check that The propeller is securely fastened The bolts holding the electric motor to the motorbracket are fastened correctly The area where the thruster is installed is clean and dry If there are signs of water you must try to find t...

Страница 17: ...re is contact through the magnetising spools of each side of the solenoid measure between the red and blue on one side and red and grey on the other side with an Ohm meter If there are no contact between these the solenoid is broken and needs replacing If less than 10 5 V 21V the thruster will not perform at specified effect If one or more brushes are loose has no tension from the brush spring the...

Страница 18: ...chase price Purchaser must submit a statement in writing from a professional boating equipment supplier that the installation instructions of the Installation and Operation Manual have been complied with and that the defect remains e warranty service shall be performed only by the Warrantor or an authorized Service Centre and any attempt to remedy the defect by anyone else shall render this warran...

Страница 19: ...7 1457 7 1457 16 Rubber element 7 1458 7 1458 15 Coupling gearleg side 7 1457 7 1457 14 Complete motor bracket N A N A 13 Bolt motor to flange 201360 201360 12 Bolt flange to bracket 11031 11031 11 Flange 921305 921305 10 Bracket 10 0501 10 0501 9 Complete gearleg 9 0601 9 0601 8 Gearleg bolt 10 1080 10 1080 7 Driveshaft key 10 1440 10 1440 6 Gasket 9 0610 9 0610 5 Zink anode 20 1180 20 1180 4 Loc...

Страница 20: ...ps yachtaidmarine com product category marine bow thrusters 2175 NW 34th Ave Miami FL 33142 USA Phone 786 621 3010 Fax 786 621 3046 Website https yachtaidmarine com product category marine bow thrusters Email info yachtaidmarine com ...

Отзывы: