. System Malfunction Schedule 

Check for lack of water or air in the cycle heating system heat 
exchanger and discharge the air. Check if the water temperature is 
too high. Check if the refrigerant charge is too great. Check whether 
the high pressure switch has been damaged.

EE1

EE2

EE3

EE4

Check for lack of refrigerant. Check whether the low pressure switch 
has been damaged

 or wire has become disconnected.

System high pressure 
protection

System low pressure 
protection

Aux.electric heater 
overheat protection

Check whether communication wires have been disconnected or 
there is a connection error.

EE8

Check whether the power supply is normal. Check whether the 
current is greater than normal. Check whether the a/c contactor 
connection is normal.

System is running in defrost mode.

Power phase
sequence protection

Communication failure

Not applicable

Unit defrosting status 

١. Check 

whether

 the temperature thermistor of the 

upper part of

    the

 water tank is connected loose or not .

upper part

٢. Connect temperature thermistor of the 

 of the water

   

 

 tank tight or change the temperature thermistor.  

١. Check 

whether

 the temperature thermistor of the 

 is connected

coil

   

 

 loose or not .

٢. Connect temperature thermistor of coil tight or change the 

    

temperature thermistor. 

١. Check 

whether

 the exhaust temperature thermistor is connected

    loose or not .
٢. Connect exhaust temperature thermistor tight or change the 
    exhaust temperature thermistor.

١. Check 

whether

 the ambient temperature thermistor is connected

    loose or not .
٢. Connect ambient temperature thermistor tight or change the
    ambient temperature thermistor

١.Check whether the temperature thermistor of the bottom of the 
    water tank is connected loose or not .
٢.Connect temperature thermistor of the bottom of the water tank
    tight or  change the temperature thermistor.

PP5

PP6

PP1

PP2

PP3

Malfunction and 
Protection Name

Fault 
code

Solution

Hot  water  tank 
temp. Sensor failure

Water outlet
temp.Sensor failure

System coil temp. 
Sensor failure

System suction 
temp. sensor failure

Solar collector
temp. sensor failure

Ambient temp. sensor 
failure

PP4

Normal start

Standby

PP7

Water flow protection

1:Check for 

lack of water or air in the cycle heating system heat

exchanger and discharge the air.
2:

Check whether the Grundfos water pump is working.

1. Check whether the resistor or temperature thermistor of the 

solar 

    collector 

 

is connected loose or not .

the 

solar 

2. Connect 

resistor or temperature thermistor of the 

    collector

 

 tight or change the temperature thermistor.

Содержание MAHRW015WAA

Страница 1: ...conjunction with the Installation and User Manual for models ELECTRONIC SPLIT HEAT PUMP OWNER S MANUAL For externally coiled tanks with refrigeration line connections Model MAHRW015WAA AIR TO WATER H...

Страница 2: ...g label on the side of the heat pump 1 7 Do not install this appliance close to flammable or explosive materials or naked flames 1 8 A filter in the mains water supply inlet is recommended and should...

Страница 3: ...tion valves on the heat pump to charge the whole system Mark the technical label on the tank deleting reference to R417a refrigerant charge and write in R134a The digital controller can be placed insi...

Страница 4: ...lit system allows flexible design options and with the storage tank installed inside or outside It is best for the heat pump to be installed outside and made accessible for any maintenance Also the ou...

Страница 5: ...DIMENSION mm NET WEIGHT INDOOR OUTDOOR COMPRESSOR TYPE LCD REMOTE CONTROL TEMPERATURE SETTING RANGE OPERATION MODES FAN SPEEDS 24 HOUR ON OFF TIMER W D H Kg Liquid Gas 780 258 540 Kg 10 40 CONNECTION...

Страница 6: ...eat comes apart easily Firstly remove the lid then unscrew the brace on top of the fan to the front panel then the screws along the base of the casing working from the front RHS corner along the base...

Страница 7: ...try shifting the compressor with your hands to ensure it squarely seated in the tray III Technical Guide 1 Starting Current and Peak Current When the Heat Pump starts up for the first time when the ta...

Страница 8: ...on 2 Electrical wiring 220V 1PH 50Hz 1 0 2 mm 1 0 2 mm 1 0 2 mm 0 5 2 mm 0 5 2 mm Host power Mode Phase line Zero line Ground line Max line length m Signal line Tem Sensor Max line length m MAHRW015WA...

Страница 9: ...Clock setting button Water cooing mode N A Additional water pump N A Heat pump fan only N A The remote controller is designed for standard wiring and to fit a standard electrical box with dimensions 8...

Страница 10: ...heater control is not applicable to Australian BOLT ON Heat Pump models A Independent electric heater mode Under the turn off status press the button you can turn on the independent electric heater m...

Страница 11: ...on again and the hour and timer OFF symbol flickers Press again and the hour display flickers press button to adjust the hour setting Press button again and the minute display flickers Press buttons t...

Страница 12: ...ank temperature Range 10 to60 Default 60 Note temperature rise above sensor probe approx 5 Parameter 9 Defrost time maximum time Range 1 to 12 min Default 8 min Parameter 8 Defrost exit temperature Ra...

Страница 13: ...nter defrost temperature setting Exit defrost temperature setting Exit defrost max time cycle setting High temperature disinfection maintain time Tank temperature difference value for the compressor r...

Страница 14: ...for the unit enter the ambient temp too low protection Note Applies to the heat pump with Aux electric heater Applies to the heat pump with Solar collector Not applicable The minus sign can t display...

Страница 15: ...connected coil loose or not Connect temperature thermistor of coil tight or change the temperature thermistor Check whether the exhaust temperature thermistor is connected loose or not Connect exhaust...

Страница 16: ...p1 Auxiliary electric heater overload protection switch close circuit T1 Hot water tank temperature T2 5K resistor T3 System coil temperature T4 System suction temperature T5 5K resistor T6 Ambient te...

Страница 17: ...MACON AIR TO WATER HEAT PUMP CODE MK4068 01...

Отзывы: