![SICK UE10-3OS Скачать руководство пользователя страница 15](http://html.mh-extra.com/html/sick/ue10-3os/ue10-3os_operating-instructions-manual_1264299015.webp)
Minimum
Typical
Maximum
Max. contact load (see diagram)
Switching voltage AC
10 V
230 V AC
Switching voltage DC
10 V
300 V DC
Switching current
5 mA
6 A
Total current
12 A
Usage category (EN 60 947-5-1)
AC-15 Ue 230 V AC, Ie 4 A (360 switch‐
ing operations/h)
AC-15 Ue 230 V AC, Ie 3 A (3600
switching operations/h)
DC-13 Ue 24 V DC, Ie 4 A (360 switch‐
ing operations/h)
DC-13 Ue 24 V DC, Ie 2.5 A (3600
switching operations/h)
Contact fuse protection gG or circuit breaker with
characteristic B or C
6 A
Permissible switching frequency
3600/h
Service life, mechanical
10
7
switching operations
DC contact current-breaking capacity
Service life, electrical
Sw
itc
hi
ng
cur
rent (
A)
Switching voltage (V DC)
Switching operations
Sw
itc
hi
ng
cur
rent (
A)
AC-15: 230 V
AC-1: 230 V
DC-1: 24 V
DC-13: 24 V
Contact clearance:
1.2 mm
t
LB
: Arc duration
L/R = 40 ms
t
LB
> 5 ms
L/R = 40 ms
t
LB
< 5 ms
L/R = 0 ms
t
LB
< 5 ms
Operating data
Protection against physical contact (EN 60 6641,
EN 60 9471)
Rated impulse voltage V
Imp
4 kV
Overvoltage category
II
4)
Rated voltage
300 V AC
Test voltage U
rms
50 Hz
2 kV
Enclosure rating
Housing
IP 40 (EN 60 529)
Terminals
IP 20 (EN 60 529)
Mounting
Mounting rail (EN 60 715)
Ambient operating temperature
-25 °C
+55 °C
Storage temperature
-25 °C
+75 °C
Wire cross-sections
Single wire (1×)
0.14 mm²
2.5 mm²
Single wire (2×, same cross-section)
0.14 mm²
0.75 mm²
Fine stranded wire with ferrules (1×)
0.25 mm²
2.5 mm²
4)
To achieve overvoltage category III see note in chapter
"Electrical installation", page 9
TECHNICAL SPECIFICATIONS
11
8022191/2017-11-24 | SICK
O P E R A T I N G I N S T R U C T I O N S | UE10-3OS
15
Subject to change without notice