3

Product description

3.1

Structure and function

2

3

1

3

2

Figure 1: Components of the T4000 Multi transponder safety switch

1

Evaluation unit

2

Sensor

3

Actuator (transponder)

The T4000 Multi transponder safety switch consists of three components:

Sensor

The sensor is mounted on the fixed part of the guard and is connected to the eval‐
uation unit.

Actuator (transponder)

The actuator is mounted on the movable part of the guard.
Each actuator has a unique electronic code.

Evaluation unit

The evaluation unit must be installed in a control cabinet with an enclosure rating
of at least IP54. Depending on the evaluation unit variant (

see "Product variants",

page 11

), up to two or up to four sensors can be connected to the evaluation

unit.

Operating principle

The T4000 Multi transponder safety switch monitors movable physical guards:

Operation of the machine in automatic mode is possible only if the guards are
closed.

A stop command is triggered if the guard is opened while the machine is running.

The T4000 Multi transponder safety switch is uniquely coded: An actuator must be
taught in at the connected sensors during commissioning.

PRODUCT DESCRIPTION

10

O P E R A T I N G   I N S T R U C T I O N S | T4000 Multi

8022726/2019-05-07 | SICK

Subject to change without notice

Содержание T4000 Direct Unicode

Страница 1: ...O P E R A T I N G I N S T R U C T I O N S T4000 Multi Transponder safety switches...

Страница 2: ...is only permissible within the limits of the legal determination of Copyright Law Any modifica tion abridgment or translation of this document is prohibited without the express writ ten permission of...

Страница 3: ...r of the machine 13 4 2 Operating entity of the machine 13 4 3 Design 13 4 4 Integration into the electrical control 14 4 5 Thorough check concept 18 5 Mounting 20 5 1 Safety 20 5 2 Unpacking 20 5 3 M...

Страница 4: ...11 1 Evaluation units T4000 1RCA02 and T4000 1RCA04 36 11 2 Sensors T4000 DNA 38 11 3 T4000 1KBA actuator 39 11 4 Dimensional drawings 40 12 Ordering information 42 12 1 Devices 42 12 2 Accessories 42...

Страница 5: ...opera tion and maintenance In many applications the target groups consist of the manufacturer and the operating entity of the machine in which the safety switch is integrated Area of responsibility T...

Страница 6: ...f not prevented NOTE Indicates useful tips and recommendations Instructions to action b The arrow denotes instructions to action 1 The sequence of instructions for action is numbered 2 Follow the orde...

Страница 7: ...Visible and invisible beam A combination of multiple hazards ABOUT THIS DOCUMENT 1 8022726 2019 05 07 SICK O P E R A T I N G I N S T R U C T I O N S T4000 Multi 7 Subject to change without notice...

Страница 8: ...Movable physical guards Safe position monitoring The safety switch must be used only on the machine on which it was planned mounted installed and initially commissioned by qualified safety personnel i...

Страница 9: ...relevant field and is sufficiently familiar with the application of the protec tive device on the machine to be able to assess whether it is in an operationally safe state Operation and maintenance F...

Страница 10: ...trol cabinet with an enclosure rating of at least IP54 Depending on the evaluation unit variant see Product variants page 11 up to two or up to four sensors can be connected to the evaluation unit Ope...

Страница 11: ...T4000 1RCA04 for connection of up to four sensors Complete overview of all variants see Ordering information page 42 3 2 2 Sensing face The sensor has a sensing face see Dimensional drawings page 40 3...

Страница 12: ...tus of downstream contactors In order to use external device monitoring positively guided contactors must be used to switch off the machine If the auxiliary contacts of the positively guided contactor...

Страница 13: ...ty switch necessitate a new risk assessment The results of this risk assessment may require the operating entity of the machine to fulfill the manufac turer s obligations b Apart from during the proce...

Страница 14: ...r not stopped in a timely manner b Make sure that the following control and electrical requirements are met so the protective function can be fulfilled The output signals of the safety outputs must no...

Страница 15: ...be main tained until a reset device is activated and the machine can be restarted in a second step The reset brings the protective device back to the monitoring state after it has sent a stop command...

Страница 16: ...ulti transponder safety switch checks the contactors each time the safety outputs are switched off and before the machine restarts External device monitoring is then able to detect if one of the conta...

Страница 17: ...th two sensors including manual reset and external device monitoring EDM Figure 3 Connection example T4000 1RCA02 PROJECT PLANNING 4 8022726 2019 05 07 SICK O P E R A T I N G I N S T R U C T I O N S T...

Страница 18: ...CA04 4 5 Thorough check concept The safety switch must be tested by appropriately qualified safety personnel during commissioning after modifications and at regular intervals see Thorough check page 3...

Страница 19: ...Minimum requirements for the regular thorough check The following thorough checks must be carried out at least once a year Thorough check of the protective function of the safety switch see Thorough...

Страница 20: ...reseeable external influences b Do not use the sensor and actuator as a stop b The holder and mounting method for the sensor and actuator must be stable enough to ensure that correct operation can tak...

Страница 21: ...distance Sar NOTE At the assured switch off distance Sar the safety outputs relay outputs are reli ably switched off even in the event of an internal component failure b The sensor and actuator must...

Страница 22: ...ribed minimum distance Smin of 50 mm must be adhered to in order to avoid mutual interference Figure 5 Minimum distance when several safety switches are mounted 5 MOUNTING 22 O P E R A T I N G I N S T...

Страница 23: ...afety transformers EN 61558 2 6 or equivalent isolation measures b Use protected cable routing to prevent the risk of cross circuits and short circuits b All output contacts must have an adequate supp...

Страница 24: ...r 3 Shield 6 4 Evaluation unit connection DANGER Improper use of the safety switch Risk of ineffectiveness of the protective device The dangerous state may not be stopped in the event of non complianc...

Страница 25: ...ment UB 0 V Supply voltage J1 J2 Shorting jumper for teach in process H1a H1b H2a H2b Connection of sensors 1 2 for evaluation unit T4000 1RCA02 H1a H1b H4a H4b Connection of sensors 1 4 for evaluatio...

Страница 26: ...l CPU A Typ 1 Sensor Multiplexer 1 aus 2 CPU B CPU B CPU A CPU A Start CPU B Typ 2 DIP Schalter UB 0V Betriebsspannung J1 J2 Kurzschlussbr cke f r Einlernvorgang H1a H1b H2a H2b Anschluss Sensor 1 2 S...

Страница 27: ...der Trans ponder Trans ponder Trans ponder 0 V Zum Aktivieren des Einlernvorgangs J1 und J2 mit Kurzschlussbr cke berbr cken DC 24 V Betriebsspannung Sensor 1 UB 0V Betriebsspannung J1 J2 Kurzschlussb...

Страница 28: ...device The dangerous state may not be stopped in the event of non compliance b Document teaching in of an actuator b During regular thorough checks make sure that the taught in actuator is still being...

Страница 29: ...ch in process 3 Wait for the self test to be completed The green LED STATE flashes at 15 Hz for approx 10 seconds during the self test The teach in process now starts automatically The green LED STATE...

Страница 30: ...tions Before commissioning After changes to the configuration or the safety function After changes to the mounting the alignment or the electrical connection After exceptional events such as after a m...

Страница 31: ...tate of the machine may not be stopped or not stopped in a timely manner b Do not carry out any repairs on the device components b Do not modify or manipulate device components b Apart from during the...

Страница 32: ...nitoring was taught in e g because the contactors was open during teach in DIP switch setting was changed without a new teach in process Not all protective doors were closed during the teach in proces...

Страница 33: ...and detect any ineffectiveness due to modifications or external influences e g dam age or manipulation b Carry out the thorough checks according to the instructions from the machine manufacturer and...

Страница 34: ...not nec essary because the device monitors itself in real time Welding of an output contact relay output is detected by the device at the latest when the guard is next opened NOTE A cross circuit of t...

Страница 35: ...in accordance with national waste disposal regulations Complementary information SICK will be glad to help you dispose of these devices on request DECOMMISSIONING 10 8022726 2019 05 07 SICK O P E R A...

Страница 36: ...ety configuration of your machine system please consult your SICK subsidiary 2 At maximum switching load Table 7 Technical data of evaluation units T4000 1RCA02 and 1RCA04 Parameter Minimum Typical Ma...

Страница 37: ...A 30 V DC 12 6 A 30 V AC 15 1 5 A 230 V DC 13 1 2 A 24 V Rated insulation voltage Ui 250 V Rated impulse withstand voltage Uimp 4 kV Conditional rated short circuit current 100 A Vibration resistance...

Страница 38: ...e gold con tacts 4 It must be ensured that the current and voltage are chosen so that a switching capacity of at least 50 mW is achieved 5 After the supply voltage has been switched on the relay outpu...

Страница 39: ...rules Cable length for sensor T4000 DNA P 15 m T4000 DNAC sensor connection Plug connector M8 3 pin with latching and screw con nection Cable length T4000 DNAC 25 m 11 3 T4000 1KBA actuator Table 9 Te...

Страница 40: ...dimensions of the evaluation units T4000 1RCA02 and T4000 1RCA04 are identi cal The evaluation unit T4000 1RCA04 is shown Sensor T4000 DNA P with permanently connected cable Figure 12 Dimensional dra...

Страница 41: ...re 13 Dimensional drawing of sensor T4000 DNAC mm 1 Sensing face T4000 1KBA actuator Figure 14 Dimensional drawing of actuator T4000 1KBA mm 1 Sensing face TECHNICAL DATA 11 8022726 2019 05 07 SICK O...

Страница 42: ...includes two safety screws 12 2 Accessories Table 11 Accessories part numbers Part Description Part number T4000 DNA05C Connecting cable 5 m straight male connector 6034391 T4000 DNA10C Connecting ca...

Страница 43: ...ns of the following EU directive s including all applicable amendments and that the standards and or technical specifications stated in the EU declaration of conformity have been used as a basis for t...

Страница 44: ...gnment T4000 DNAC 24 8 Block diagram with two sensors 26 9 Block diagram with four sensors 27 10 Typical response range for cable length l 0 to 25 m 38 11 Dimensional drawing for evaluation units T400...

Страница 45: ...6 Safety related characteristic data of evaluation units T4000 1RCA02 and 1RCA04 36 7 Technical data of evaluation units T4000 1RCA02 and 1RCA04 36 8 Technical data of sensors T4000 DNA 39 9 Technica...

Страница 46: ...15 LIST OF TABLES 46 O P E R A T I N G I N S T R U C T I O N S T4000 Multi 8022726 2019 05 07 SICK Subject to change without notice...

Страница 47: ...LIST OF TABLES 15 8022726 2019 05 07 SICK O P E R A T I N G I N S T R U C T I O N S T4000 Multi 47 Subject to change without notice...

Страница 48: ...8080 7425 E Mail enquiry my sick com Mexico Phone 52 472 748 9451 E Mail mexico sick com Netherlands Phone 31 0 30 229 25 44 E Mail info sick nl New Zealand Phone 64 9 415 0459 0800 222 278 tollfree...

Отзывы: