Inductive load
NOTE
Provide an arc-suppression circuit at the digital switching output if an inductive load is
present.
b
Attach a freewheeling diode directly to the load for this purpose.
Table 48: Assignment of placeholders to digital switching outputs
Device
CDB650-204
Output A
Pin B
Signal C
Terminal D
Result 1
13
RES/OUT 1
20
Result 2
14
RES/OUT 2
21
Characteristic data of digital switching outputs
Table 49: Characteristic data of the digital switching outputs “Result 1” and “Result 2”
Switching behavior
PNP switching to supply voltage U
V
Default settings in the device: no function, logic: not inverted (active
high)
Properties
•
Short-circuit pro temperature protected
•
Not electrically isolated from V
S
Electrical values
0 V ≤ V
out
≤ V
S
(V
S
−1.5 V) ≤ V
out
≤ V
S
at I
out
≤ 100 mA
NOTE
Assign the functions for the digital switching outputs in the device with a configuration
tool, e.g. the configuration software SOPAS ET.
14.5.10
Wiring digital switching outputs “External output 1” and “External output 2” of the device in the
CDB650-204
Device = RFU630-131xx, RFU630-041xx
Device = RFU650-101xx
Load (e.g. PLC)
3
GND
V
out
For inductive load:
5
Device
1
Aux
(RS-232)
CDB650-204
CMC600
2
U
IN
*
“External
output
A
”
6
C
EXT. OUT
B
22
GND
6
Shield
4
Figure 56: Wiring external digital switching outputs “EXT. OUT 1” and “EXT. OUT 2” of the device in the connection module
CDB650-204
14
ANNEX
114
O P E R A T I N G I N S T R U C T I O N S | RFU63x, RFU65x
8014335/ZTL9/2018-10-14 | SICK