7
Configuration
7.1
DIP switch
The safety relay is configured via four DIP switches. The DIP switches are attached to
the side of the safety relay.
REL
Y
PWR
O
UT
13
23
I1
Y1
14
24
I2
Y2
A2
34
33
S1
X1
A1
A
u
x I/O
Te
ac
h
0
1
CS
Manual
Auto
Reset
Off
No.
No. + Type
R
e
se
t
ReLy
LOOP
Figure 10: DIP switch
7.2
Configuring ReLy reset
Overview
The following reset options for the safety relay are available:
•
Manual
For manual reset, a pushbutton is connected between the input S1 and the supply
voltage U
v
. Pressing the pushbutton manually for min. 140 ms triggers a valid
reset sequence at the S1 input.
•
Auto
For automatic reset, the S1 input and the supply voltage U
v
are connected with
a wire jumper. This automatically triggers a valid reset sequence at the S1 input.
There is no restart interlock.
Important information
WARNING
Unexpected machine start-up due to automatic reset without restart interlock
In the case of non-compliance, it is possible that the dangerous state of the machine
may not be stopped or not stopped in a timely manner.
b
Take other protective measures to make sure that there is no one inside the
hazardous area.
Prerequisites
•
The safety relay is disconnected from the voltage supply.
•
The device connection is tailored to the reset option.
Approach
b
Set the DIP switch for the desired reset option to position 1.
CONFIGURATION
7
8024311/2021-07-30 | SICK
O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1
21
Subject to change without notice