Index
(decimal)
Object name Format
Access Value range
Factory
setting
Remarks
67
OU1
8 Bit
Enumeration
R/W
0 = HNO = hysteresis function,
normally open
1 = HNC = hysteresis function,
normally closed
2 = FNO = window function,
normally open
3 = FNC = window function,
normally closed
0
Switching function switching
output 1
68
SP2 or FH2
16 Bit
unsigned
R/W
1,040 … 9,000
9,000
Switch point/window High
switching output 2
69
RP2 or FL2
16 Bit
unsigned
R/W
1,000 … 8,960
8,200
Reset point/window Low
switching output 2
70
OU2
8 Bit
Enumeration
R/W
0 = HNO = hysteresis function,
normally open
1 = HNC = hysteresis function,
normally closed
2 = FNO = window function,
normally open
3 = FNC = window function,
normally closed
0
Switching function switching
output 2
72
Unit
8 Bit
Enumeration
R/W
0 = bar
1 = Mpa
2 = kPa
3 = psi
4 = kg/cm²
Order-related
Unit change. MBA and MBE must
be read again after writing.
73
HIGH
16 Bit
unsigned
R
0 … 10,000
-
Max. value memory
74
LOW
16 Bit
unsigned
R
0 … 10,000
-
Min. value memory
75
DS1
16 Bit
unsigned
R/W
0 … 50,000 (0 ... 50 s)
0
Switch delay time switch point 1
76
DR1
16 Bit
unsigned
R/W
0 … 50,000 (0 ... 50 s)
0
Switch delay time reset point 1
77
DS2
16 Bit
unsigned
R/W
0 … 50,000 (0 ... 50 s)
0
Switch delay time switch point 2
78
DR2
16 Bit
unsigned
R/W
0 … 50,000 (0 ... 50 s)
0
Switch delay time reset point 2
6. Commissioning, operation