![SICK PAC50 Скачать руководство пользователя страница 80](http://html1.mh-extra.com/html/sick/pac50/pac50_operating-instructions-manual_1264699080.webp)
8 0
O p e r a t i n g I n s t r u c t i o n s | S I C K
Operating Instructions
PAC50
8017612/ZAB1/2017-02-14 | PAC50
Subject to change without notice
9 Technical data
9.3 Mechanics/Electronics
Process connections
2 x G ¼
1)
PIF 4 mm + G ¼
2)
¼ NPT + G ¼
Electrical connection
Round connector M12 x 1, 4-pin for versions with 2 switching outputs and
versions with 1 switching analog output
Round connector M12 x 1, 5-pin for versions with 2 switching o
analog output
Supply voltage
3)
17 V DC ... 30 V DC
Current consumption
Max. 40 mA at L
+
= 24 V DC
Initialization time
300 ms
Housing material
Housing: Polycarbonate, Pushbuttons: TPE, Mounting rail clip: POM, Seals:
NBR
Electrical safety
Protection class: III
Overvoltage protection: 32 V DC
Short-circuit resistance: Q
A
, Q
1
, Q
2
towards M and L
+
Reverse polarity protection: L
+
towards M
CE-conformity
2004/108/EC, EN 61326-1 emissions (group 1, class B) and interference
immunity (industrial areas)
RoHS certificate
Yes
cULus certificate
Yes
1)
Underside: G ¼ female thread, rear: G ¼ female thread, both in acc. with DIN ISO 16030
2)
Underside: Push-in fitting for 4 mm pneumatic hose, rear: G ¼ female thread in acc. with DIN ISO 16030
3)
For the voltage supply, use an energy-limited circuit in accordance with UL61010-1 3nd Ed., Section 9.4