Operating Instructions
PAC50
8017612/ZAB1/2017-02-14 | PAC50
Subject to change without notice
9 Technical data
9 Technical data
9.1 Features
Medium
Dry compressed air
Compressed air quality
According to ISO 8573-1:2010
Max. particle size: ≤ 40 μm
Oil content: 0–40 mg/m
3
The pressure dew point must be at least 15°C below the ambient and medium tem-
peratures and must not exceed 3°C
Zero point adjustment
Max. 5 % of span
Measuring ranges
–1 bar ...0 bar; –1 bar ...+1 bar; 0 bar ... +6 bar; 0 bar ... +10 bar; –1 ... 10 bar
Process temperature
0 °C to 60 °C
Switching outputs
Depending on variant: 1 or 2 transistor switching outputs
PNP/NPN/push-pull can be set (in versions with IO-Link: switching output 1: option of
switching between IO-Link/PNP, and switching output 2: between PNP/NPN/push-pull)
Function: normally open/normally closed, window and hysteresis function freely
adjustable
Switching voltage: Supply voltage L
+
– 2 V [V DC]
Max. switching current per switching output: 100 mA
Switching delay: 0 s to 50 s (adjustable)
Switching time ≤ 5 ms
Versions with IO-Link: IO-Link version 1.1