IO-Link ports
Tightening torque = 0.6 Nm
The length of cable of the sensor and actuator lines is generally limited to 30 m.
If an IO-Link connection is active, the length of cable is limited to max. 20 m.
Table 5: IO-Link ports (S1 – S8): M12 female contact, A-coded, port class A/B
PIN
IO-Link port class A
IO-Link port class B1
1)
Pin 1
L + (U
s
+)
L + (U
s
+)
Pin 2
DI/DO
2L + (U
A
+)
Pin 3
L - (U
s
-)
L - (U
s
-)
Pin 4
IO-Link/DI/DO
IO-Link/DI/DO
Pin 5
L - (U
s
-)
L - (U
s
-)
2
1
4
3
5
1)
No galvanic separation
Ethernet ports
Tightening torque = 0.6 Nm
Table 6: Ethernet ports (P1 – P2): M12 female contact, D-coded
PIN
Description
Pin 1
Tx +
Pin 2
Rx +
Pin 3
Tx -
Pin 4
Rx -
Pin 5
n. c.
3
2
4
1
5
Supply ports
US: 18 ... 30 V DC
UA: 18 … 30 V DC
Tightening torque = 0.6 Nm
Table 7: Power ports (PWR1 – PWR2): M12 male connector/female contact, L-coded
PIN
Description
Pin 1
+24 V DC US
Pin 2
0 V
Pin 3
0 V
Pin 4
+24 V DC UA
Pin 5
GND
ELECTRICAL INSTALLATION
6
8027836./2022-06-10 | SICK
O P E R A T I N G I N S T R U C T I O N S | Sensor Integration Gateway - SIG350
21