O P E R AT I N G I N S T R U C T I O N S | C F P C U B I C
8021989 / 2017-10-20 | SICK AG
Subject to change without notice
5 1
14
TECHNICAL DATA
14.7
Electrical connections
Supply voltage
1)
DC 10 V ... 30 V
Current consumption
≤ 100 mA at 24 V without output load
Initialization time
≤ 5 s
Protection class
III
Connection type
M12 x 1 (5-pin)
M12 x 1 (8-pin)
Hysteresis
Min. 3 mm, min. 2 °C, freely configurable
Output signal
2)
• 2 switching outputs PNP/NPN/DRV
• 2 switching outputs PNP/NPN/DRV and 1
analog output 4 mA to 20 mA / 0 V to 10 V auto-
matically switchable depending on output load
• 4 switching outputs PNP/NPN/DRV and 2 ana-
log outputs 4 mA to 20 mA / 0 V to 10 V auto-
matically switchable depending on output load
Signal voltage HIGH
Uv –3 V
Signal voltage LOW
≤ 3 V
Output current
< 100 mA per output
Inductive load
< 1 H
Capacitive load
100 nF
Temperature drift
< 0.1 mm/K
Output load
4 mA to 20 mA < 500 ohms at U
v
> 15 V
4 mA to 20 mA < 350 ohms at U
v
> 2 V
0 V to 10 V > 750 ohms at U
v
≥
14 V
Lower signal level
3.8 mA to 4 mA
Upper signal level
20 mA to 20.5 mA
EMC
EN 61326-2-3, 2014/30/EU
1)
Use an energy-limited circuit for voltage supply as per UL61010-1 3rd Ed., Section 9.3.
2)
All connections are reverse polarity protected. All outputs are overload and short-circuit
protected.