COMMISSIONING
6
53
8023732/2018-09-10|SICK
Subject to change without notice
O R I G I N A L O P E R A T I N G I N S T R U C T I O N S | AOS301-WWD
6.5
Configuring data output in TEMS Manager
6.5.1
Configuring I/O interface (TDC-E IO plug-in)
The data output is configured in TEMS Manager using plug-ins.
The
TDC-E IO
plug-in controls the output of the wrong-way driver signal to the customer
system via a digital I/O interface of the TDC-E. The system status and the Heartbeat can
also be output via this plug-in.
The
TDC-E IO
plug-in is created when the configuration file is loaded.
▸
At the level of the
TDC-E IO
plug-in, click on the
Show details
icon.
•
The TDC-E IO plug-in basically activates all digital interfaces of the TDC-E.
•
They are configured in the
DIO_A_Direction
,
DIO_B_Direction
etc. parameters, each
as an output (
Out
). They can also be configured as an input (
In
).
•
The
DIO_A_Value
,
DIO_B_Value
etc. parameters belonging to the interface define the
initial state set for the respective output.
If the value of an output is set to
True
, it is initialized with a high level when the
configuration is started, otherwise with a low level. This value is ignored for interfaces
configured as inputs.
Interfaces