Group 1: cables very sensitive to interference, such as analog measuring
cables
°
Group 2: cables sensitive to interference, such as device cables, communica‐
tion signals, bus signals
°
Group 3: cables that are a source of interference, such as control cables for
inductive loads and motor brakes
°
Group 4: cables that are a powerful source of interference, such as out‐
put cables from frequency inverters, welding system power supplies, power
cables
b
Cables in groups 1, 2 and 3, 4 must be crossed at right angles (
).
b
Route the cables in groups 1, 2 and 3, 4 in different cable channels or
use metallic separators (
). This applies partic‐
ularly if cables of devices with a high level of radiated emission, such as
frequency converters, are laid parallel to device cables.
1
2
4
3
1
2
4
3
90
90
Figure 16: Cross cables at right angles
1
2
3
4
Figure 17: Ideal laying – Place cables in different cable channels
1
2
3
4
Figure 18: Alternative laying – Separate cables with metallic separators
ELECTRICAL INSTALLATION
6
8014755/19H8/2021-10-15 | SICK