6.3
Integration using an EDS file
Common configuration tools can import an EDS file for integration of the WI180C-EN
into the Ethernet/IP™ network.
The EDS file for the WI180C-EN is available for download from www.sick.de (WI180C-
EN EDS file).
Refer to your configuration tool's documentation for how to import the file into your sys‐
tem.
Prerequisites
•
You are using an Allen Bradley control system with “RSLogix 5000” control soft‐
ware V22 or higher (or another control that facilitates integration using an EDS
file).
•
The WI180C-EN has an IP address (
see "IP address of the WI180C-EN",
).
•
The EDS file has been integrated into the control software using the Rockwell
Hardware Installation Tool.
Setting up communication
1.
Right-click on the Ethernet icon and select the
New Module…
command.
✓
The
Select Module Type
dialog box opens.
2.
Select the WI180C-EN on the
Catalog
index card.
✓
The
Module Properties [module name]
dialog box opens.
3.
Enter a name (freely selectable) in the
Name
field and the IP address defined for
the WI180C-EN in the
IP Address
field.
✓
In the
Module Definition
area, the default connection
Input Only (104)
is shown as
Con‐
nections
. This is instance 104 of the assembly object.
Changing the instance of the assembly object
1.
Click on
Change...
if you would like to change this instance.
2.
Select e.g. Exclusive Owner 101.
3.
Under
Size
, select the data format UINT-16.
Checking communication
The data received by the control from the WI180C-EN can be displayed in order to
check that communication between the control and the WI180C-EN is working cor‐
rectly.
1.
In the
Controller Organizer
, open the
Controller Test Setup
,
Controller Tags
folder.
2.
In the
Name
column of the
Controller Tags
, open the node with the name previously
entered for the WI180C-EN.
6.4
IP address of the WI180C-EN
The IP address of the WI180C-EN can be assigned as follows:
•
Static allocation
•
Via BOOTP
•
Via DHCP
Static allocation
Using the TCP/IP object, a fixed IP address can be configured via the control. To do so,
an initial connection must be established via the default address (192.168.0.1).
Assigning the IP address via BOOTP or DHCP
If your control has a BOOTP or DHCP server, you can assign an IP address to the
WI180C-EN via this server.